Lead and copper

MS0060006 , City of Cleveland

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for City of Cleveland, 36 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2023 – Dec 31, 2025 30 0.693 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2025 30 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2020 – Dec 31, 2022 30 0.606 mg/l DS000 Accepted
Lead Jan 1, 2020 – Dec 31, 2022 30 0.0007 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2019 30 0.6041 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2019 30 0.0012 mg/l DS000 Accepted
Copper Jan 1, 2017 – Dec 31, 2019 23 0.5984 mg/l DS000 Accepted
Lead Jan 1, 2017 – Dec 31, 2019 23 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2018 23 0.5984 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2018 23 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2014 – Dec 31, 2016 34 0.573 mg/l DS000 Accepted
Lead Jan 1, 2014 – Dec 31, 2016 34 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2013 – Dec 31, 2015 34 0.573 mg/l DS000 Accepted
Lead Jan 1, 2013 – Dec 31, 2015 34 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2011 – Dec 31, 2013 30 0.5013 mg/l DS000 Accepted
Lead Jan 1, 2011 – Dec 31, 2013 30 0.0015 mg/l DS000 Accepted
Copper Jan 1, 2010 – Dec 31, 2012 30 0.5013 mg/l DS000 Accepted
Lead Jan 1, 2010 – Dec 31, 2012 30 0.0015 mg/l DS000 Accepted
Copper Jan 1, 2008 – Dec 31, 2010 30 0.5315 mg/l DS000 Accepted
Lead Jan 1, 2008 – Dec 31, 2010 30 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2005 – Dec 31, 2007 30 0.5358 mg/l DS000 Accepted
Lead Jan 1, 2005 – Dec 31, 2007 30 0.0016 mg/l DS000 Accepted
Copper Jan 1, 2002 – Dec 31, 2004 32 0.6673 mg/l DS000 Accepted
Lead Jan 1, 2002 – Dec 31, 2004 32 0.0021 mg/l DS000 Accepted
Copper Jan 1, 1999 – Dec 31, 2001 29 0.584 mg/l DS000 Accepted
Lead Jan 1, 1999 – Dec 31, 2001 29 0.002 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1998 29 0.596 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1998 29 0.003 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 30 0.413 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 30 0.002 mg/l DS000 Accepted
Copper Jan 1, 1994 – Dec 31, 1994 30 0.519 mg/l DS000 Accepted
Lead Jan 1, 1994 – Dec 31, 1994 30 0.003 mg/l DS000 Accepted
Copper Jan 1, 1993 – Jun 30, 1993 67 0.632 mg/l DS000 Accepted
Lead Jan 1, 1993 – Jun 30, 1993 67 0.001 mg/l DS000 Accepted
Copper Jul 1, 1992 – Dec 31, 1992 66 0.59 mg/l DS000 Accepted
Lead Jul 1, 1992 – Dec 31, 1992 66 0.003 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.