This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0060049 , Deeson-Roundlake Water Corp
26 of the 59 analytes this system has been tested for have been detected at least once, across 267 samples on record.
The other 33 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 267 samples on record, detections range from June 7, 1994 to March 3, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 177 of 187 results | Jun 7, 1994 | Sep 27, 2024 |
| Lead 1030 | Inorganic Chemical | 146 of 187 results | Jun 7, 1994 | Aug 16, 2024 |
| Arsenic 1005 | Inorganic Chemical | 11 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Barium 1010 | Inorganic Chemical | 11 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Fluoride 1025 | Inorganic Chemical | 9 of 11 results | Jan 12, 2004 | Jan 13, 2025 |
| Chromium 1020 | Inorganic Chemical | 7 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Selenium 1045 | Inorganic Chemical | 7 of 11 results | Jun 25, 2002 | May 5, 2014 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 6 of 9 results | Jun 25, 2007 | Mar 3, 2025 |
| TTHM 2950 | Organic Chemical | 6 of 8 results | Jun 25, 2007 | Mar 3, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 4 of 5 results | Jun 7, 2010 | Aug 4, 2014 |
| Chloroform 2941 | Organic Chemical | 4 of 5 results | Jun 25, 2007 | Aug 4, 2014 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 20, 2019 | Oct 15, 2024 |
| Bromoform 2942 | Organic Chemical | 3 of 5 results | Jun 7, 2010 | Aug 4, 2014 |
| Bromodichloromethane 2943 | Organic Chemical | 3 of 5 results | Jun 7, 2010 | Aug 4, 2014 |
| Dibromochloromethane 2944 | Organic Chemical | 3 of 5 results | Jun 7, 2010 | Aug 4, 2014 |
| Nickel 1036 | Inorganic Chemical | 2 of 11 results | Mar 10, 2008 | May 5, 2014 |
| Gross Alpha Particle Activity 4109 | Radionuclide | 2 of 5 results | Jun 25, 2012 | Sep 17, 2012 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 2 of 6 results | Nov 28, 2011 | Dec 19, 2011 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 1 of 1 result | Mar 18, 2016 | Mar 18, 2016 |
| Radium-228 4030 | Radionuclide | 1 of 6 results | Dec 19, 2011 | Dec 19, 2011 |
| Radium-226 4020 | Radionuclide | 1 of 6 results | Nov 28, 2011 | Nov 28, 2011 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 5 results | Jul 11, 2011 | Jul 11, 2011 |
| Dichloroacetic Acid 2451 | Organic Chemical | 1 of 5 results | Jul 11, 2011 | Jul 11, 2011 |
| Trichloroacetic Acid 2452 | Organic Chemical | 1 of 5 results | Jul 11, 2011 | Jul 11, 2011 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 5 results | Jul 11, 2011 | Jul 11, 2011 |
| Nitrate 1040 | Inorganic Chemical | 1 of 22 results | Jun 5, 2006 | Jun 5, 2006 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 21–30 of 267 samples, newest first — collected September 18, 2018 to July 5, 2021. The summary above covers all 267.
38 results from the 10 samples listed here: 10 detected, 28 not detected. Across the whole record it is 414 of 818. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
Units in this table
Sodium is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
We withheld the location of 2 sampling points below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0032 mg/l , sample collected Jul 5, 2021 08:15, sampling point LC0003 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 5, 2021 08:15, sampling point LC0003 | Lead 1030 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
|
||
| 0.0041 mg/l , sample collected Jul 5, 2021 07:15, sampling point LC0001 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 5, 2021 07:15, sampling point LC0001 | Lead 1030 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Mar 30, 2021 16:40, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 119 mg/l , sample collected Jan 20, 2021 16:45, sampling point TF101 | Sodium 1052 EPA method 200.7 | Not recorded |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 20, 2021 16:31, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2021 – Dec 31, 2021 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 20, 2021 16:31, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2021 – Dec 31, 2021 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 20, 2021 16:31, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2021 – Dec 31, 2021 |
|
||
| 0.0005 mg/l , sample collected Jan 12, 2021 16:27, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0189 mg/l , sample collected Jan 12, 2021 16:27, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.169 mg/l , sample collected Jan 12, 2021 16:27, sampling point TF101 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 12, 2021 16:27, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 21, 2020 16:01, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 21, 2020 16:01, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 21, 2020 16:01, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
|
||
| 240000 ug/l , sample collected Sep 20, 2019 08:25, sampling point TF101 | Sodium 1052 EPA method 200.7 | Not recorded |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 30, 2019 16:40, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 30, 2019 16:40, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 30, 2019 16:40, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
|
||
| 0.001 mg/l , sample collected Sep 18, 2018 04:01, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0827 mg/l , sample collected Sep 18, 2018 04:01, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.119 mg/l , sample collected Sep 18, 2018 04:01, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 18, 2018 04:01, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
-
- Collected
- Jul 5, 2021 08:15
- Sampling point
- LC0003 Location withheld
- Sample type
- Routine
- Lab sample
- PB-210708-190
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2021
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0032 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Jul 5, 2021 07:15
- Sampling point
- LC0001 Location withheld
- Sample type
- Routine
- Lab sample
- PB-210708-187
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2021
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0041 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Mar 30, 2021 16:40
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- CN-210331-006
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Jan 20, 2021 16:45
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NA-210121-008
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 119 mg/l
-
- Collected
- Jan 20, 2021 16:31
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NI-210121-062
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2021
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jan 12, 2021 16:27
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-210113-023
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0189 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.169 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
- Collected
- Jan 21, 2020 16:01
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 200122-043NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2020
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Sep 20, 2019 08:25
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 680-174566-109
- Laboratory
- Test America-Savannah
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 240000 ug/l
-
- Collected
- Jan 30, 2019 16:40
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 190131-034NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2019
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Sep 18, 2018 04:01
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 180919-024IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Barium 1010 EPA method 200.8
- Result
- 0.0827 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Fluoride 1025 EPA method 300.0
- Result
- 0.119 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
Routine (10).