This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0060053 , Deeson Roundlake #2
24 of the 58 analytes this system has been tested for have been detected at least once, across 204 samples on record.
The other 34 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 204 samples on record, detections range from December 11, 2000 to April 29, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 124 of 124 results | Dec 11, 2000 | Sep 27, 2024 |
| Lead 1030 | Inorganic Chemical | 105 of 124 results | Dec 11, 2000 | Sep 27, 2024 |
| Arsenic 1005 | Inorganic Chemical | 11 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Barium 1010 | Inorganic Chemical | 11 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Fluoride 1025 | Inorganic Chemical | 10 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Chromium 1020 | Inorganic Chemical | 9 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Selenium 1045 | Inorganic Chemical | 9 of 11 results | Jun 25, 2002 | Jan 13, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 8 of 10 results | Jun 25, 2007 | Apr 29, 2025 |
| TTHM 2950 | Organic Chemical | 7 of 10 results | Jun 25, 2007 | Apr 29, 2025 |
| Nickel 1036 | Inorganic Chemical | 4 of 11 results | Jan 12, 2004 | Jan 13, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 4 of 5 results | Aug 11, 2008 | Jul 14, 2014 |
| Chloroform 2941 | Organic Chemical | 4 of 5 results | Jun 25, 2007 | Jul 14, 2014 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 20, 2019 | Oct 15, 2024 |
| Monochloroacetic Acid 2450 | Organic Chemical | 3 of 5 results | Jun 21, 2011 | Aug 16, 2017 |
| Dichloroacetic Acid 2451 | Organic Chemical | 3 of 5 results | Jun 29, 2009 | Jul 14, 2014 |
| Bromoform 2942 | Organic Chemical | 3 of 5 results | Jun 29, 2009 | Jul 14, 2014 |
| Bromodichloromethane 2943 | Organic Chemical | 3 of 5 results | Jun 29, 2009 | Jul 14, 2014 |
| Dibromochloromethane 2944 | Organic Chemical | 3 of 5 results | Jun 29, 2009 | Jul 14, 2014 |
| Trichloroacetic Acid 2452 | Organic Chemical | 2 of 5 results | Jun 21, 2011 | Jul 14, 2014 |
| Monobromoacetic Acid 2453 | Organic Chemical | 2 of 5 results | Jun 21, 2011 | Jul 14, 2014 |
| Gross Alpha Particle Activity 4109 | Radionuclide | 1 of 4 results | Sep 17, 2012 | Sep 17, 2012 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 1 of 2 results | Sep 28, 2011 | Sep 28, 2011 |
| Radium-228 4030 | Radionuclide | 1 of 2 results | Sep 28, 2011 | Sep 28, 2011 |
| Nitrate 1040 | Inorganic Chemical | 1 of 22 results | Jun 5, 2006 | Jun 5, 2006 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 1–10 of 204 samples, newest first — collected August 27, 2024 to May 27, 2025. The summary above covers all 204.
26 results from the 10 samples listed here: 16 detected, 10 not detected. Across the whole record it is 332 of 700. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
We withheld the location of 5 sampling points below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected May 27, 2025 10:33, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2023 – Dec 31, 2025 |
|
||
| 2.52 ug/l , sample collected Apr 29, 2025 15:37, sampling point SMD | Total Haloacetic Acids (Haa5) 2456 EPA method 552.2 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| 37.7 ug/l , sample collected Apr 29, 2025 15:37, sampling point SMD | TTHM 2950 EPA method 524.2 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 24, 2025 23:01, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2025 – Dec 31, 2025 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 24, 2025 23:01, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2025 – Dec 31, 2025 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 24, 2025 23:01, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2025 – Dec 31, 2025 |
|
||
| 0.0018 mg/l , sample collected Jan 13, 2025 10:10, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| 0.0191 mg/l , sample collected Jan 13, 2025 10:10, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 13, 2025 10:10, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| 0.0034 mg/l , sample collected Jan 13, 2025 10:10, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| 0.16 mg/l , sample collected Jan 13, 2025 10:10, sampling point TF101 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2023 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 13, 2025 10:10, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| 0.0006 mg/l , sample collected Jan 13, 2025 10:10, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.0036 mg/l , sample collected Jan 13, 2025 10:10, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 13, 2025 10:10, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 13, 2025 10:10, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 13, 2025 10:10, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2023 – Dec 31, 2025 |
|
||
| 133 mg/l , sample collected Oct 15, 2024 14:10, sampling point TF101 | Sodium 1052 EPA method 200.7 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| 0.0033 mg/l , sample collected Sep 27, 2024 05:30, sampling point LC022 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| 0.5 ug/l , sample collected Sep 27, 2024 05:30, sampling point LC022 | Lead 1030 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| 0.0794 mg/l , sample collected Sep 27, 2024 08:00, sampling point LC021 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| 107 ug/l , sample collected Sep 27, 2024 08:00, sampling point LC021 | Lead 1030 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| 0.0543 mg/l , sample collected Sep 27, 2024 07:30, sampling point LC020 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| 5.1 ug/l , sample collected Sep 27, 2024 07:30, sampling point LC020 | Lead 1030 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| 0.0062 mg/l , sample collected Aug 27, 2024 06:30, sampling point LC0004 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Aug 27, 2024 06:30, sampling point LC0004 | Lead 1030 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
-
- Collected
- May 27, 2025 10:33
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- CN-250528-005
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Apr 29, 2025 15:37
- Sampling point
- SMD Location withheld
- Sample type
- Routine
- Lab sample
- HA-250430-001
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
Total Haloacetic Acids (Haa5) 2456 EPA method 552.2
- Result
- 2.52 ug/l
-
- Collected
- Apr 29, 2025 15:37
- Sampling point
- SMD Location withheld
- Sample type
- Routine
- Lab sample
- TH-250430-001
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
TTHM 2950 EPA method 524.2
- Result
- 37.7 ug/l
-
- Collected
- Feb 24, 2025 23:01
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NI-250225-044
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2025 – Dec 31, 2025
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jan 13, 2025 10:10
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-250114-042
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0018 mg/l
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Barium 1010 EPA method 200.8
- Result
- 0.0191 mg/l
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Chromium 1020 EPA method 200.8
- Result
- 0.0034 mg/l
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.16 mg/l
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Nickel 1036 EPA method 200.8
- Result
- 0.0006 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.0036 mg/l
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2023 – Dec 31, 2025
-
- Collected
- Oct 15, 2024 14:10
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NA-241016-056
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Sodium 1052 EPA method 200.7
- Result
- 133 mg/l
-
- Collected
- Sep 27, 2024 05:30
- Sampling point
- LC022 Location withheld
- Sample type
- Routine
- Lab sample
- PB-241001-038
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0033 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.5 ug/l
-
- Collected
- Sep 27, 2024 08:00
- Sampling point
- LC021 Location withheld
- Sample type
- Routine
- Lab sample
- PB-241001-041
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0794 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 107 ug/l
-
- Collected
- Sep 27, 2024 07:30
- Sampling point
- LC020 Location withheld
- Sample type
- Routine
- Lab sample
- PB-241001-040
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0543 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 5.1 ug/l
-
- Collected
- Aug 27, 2024 06:30
- Sampling point
- LC0004 Location withheld
- Sample type
- Routine
- Lab sample
- PB-240829-421
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0062 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
Routine (10).