This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0070002 , Big Creek Water Association
23 of the 57 analytes this system has been tested for have been detected at least once, across 356 samples on record.
The other 34 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 356 samples on record, detections range from November 11, 1993 to July 31, 2026. These figures cover the whole record; the list of samples further down is narrowed.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 129 of 147 results | Nov 11, 1993 | Jul 31, 2026 |
| Lead 1030 | Inorganic Chemical | 75 of 147 results | Nov 11, 1993 | Jun 22, 2022 |
| Fluoride 1025 | Inorganic Chemical | 44 of 44 results | Jun 25, 2002 | Jul 30, 2026 |
| Arsenic 1005 | Inorganic Chemical | 44 of 44 results | Jun 25, 2002 | Jun 11, 2026 |
| Barium 1010 | Inorganic Chemical | 44 of 44 results | Jun 25, 2002 | Jun 11, 2026 |
| Selenium 1045 | Inorganic Chemical | 37 of 44 results | Jun 25, 2002 | Jun 11, 2026 |
| Nickel 1036 | Inorganic Chemical | 37 of 43 results | Jun 25, 2002 | Oct 8, 2025 |
| Chromium 1020 | Inorganic Chemical | 31 of 44 results | Jun 25, 2002 | Oct 8, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 20 of 32 results | Jun 27, 2007 | Mar 26, 2025 |
| TTHM 2950 | Organic Chemical | 15 of 30 results | Jun 27, 2007 | Oct 11, 2023 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 12 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 11 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Radium-226 4020 | Radionuclide | 11 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Nitrate 1040 | Inorganic Chemical | 9 of 43 results | May 3, 2004 | Mar 14, 2016 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 7 of 43 results | Jul 18, 2005 | Mar 14, 2016 |
| Sodium 1052 | Inorganic Chemical | 6 of 6 results | Sep 20, 2019 | Jun 11, 2026 |
| Radium-228 4030 | Radionuclide | 6 of 12 results | Dec 8, 2011 | Mar 14, 2016 |
| Nitrite 1041 | Inorganic Chemical | 6 of 43 results | Jul 18, 2005 | Jan 18, 2011 |
| Dibromoacetic Acid 2454 | Organic Chemical | 4 of 7 results | Aug 13, 2008 | Jun 4, 2019 |
| Bromoform 2942 | Organic Chemical | 3 of 8 results | Aug 4, 2014 | Sep 6, 2017 |
| Dichloroacetic Acid 2451 | Organic Chemical | 1 of 7 results | Jun 4, 2019 | Jun 4, 2019 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 7 results | Jun 4, 2019 | Jun 4, 2019 |
| Dibromochloromethane 2944 | Organic Chemical | 1 of 8 results | Aug 4, 2014 | Aug 4, 2014 |
Showing samples collected between September 25, 2024 and September 25, 2026. That is this page’s default, not a limit on what the agency records.
Choose a date range
The most recent samples, result by result
The table below lists 1–10 of 20 samples, newest first — collected September 9, 2025 to July 31, 2026. The summary above covers all 20.
36 results from the 10 samples listed here: 16 detected, 20 not detected. Across the whole record it is 554 of 1,415. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
Units in this table
Antimony, Total is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Arsenic is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Barium is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Beryllium, Total is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Cadmium is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Chromium is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Mercury is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Selenium is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Thallium, Total is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
We withheld the location of 5 sampling points below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 91 ug/l , sample collected Jul 31, 2026, sampling point LC0013 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 31, 2026, sampling point LC0013 | Lead 1030 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| 63.3 ug/l , sample collected Jul 30, 2026, sampling point LC0006 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 30, 2026, sampling point LC0006 | Lead 1030 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| 282 ug/l , sample collected Jul 30, 2026, sampling point LC0001 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 30, 2026, sampling point LC0001 | Lead 1030 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| 115 ug/l , sample collected Jul 30, 2026, sampling point LC0010 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 30, 2026, sampling point LC0010 | Lead 1030 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| 5.1 ug/l , sample collected Jul 30, 2026, sampling point LC0012 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jul 30, 2026, sampling point LC0012 | Lead 1030 EPA method 200.8 | Jan 1, 2025 – Dec 31, 2027 |
|
||
| 0.45 mg/l , sample collected Jul 30, 2026, sampling point TF102 | Fluoride 1025 EPA method 300.0 | Not recorded |
|
||
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Jun 30, 2026, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2026 – Dec 31, 2026 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Jun 30, 2026, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2026 – Dec 31, 2026 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Jun 30, 2026, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2026 – Dec 31, 2026 |
|
||
| 1.3 ug/l , sample collected Jun 11, 2026, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Not recorded |
| 108 ug/l , sample collected Jun 11, 2026, sampling point TF102 | Barium 1010 EPA method 200.7 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 11, 2026, sampling point TF102 | Cadmium 1015 EPA method 200.7 | Not recorded |
| Not detected below 5 ug/l Minimum Reporting Level , sample collected Jun 11, 2026, sampling point TF102 | Chromium 1020 EPA method 200.7 | Not recorded |
| Not detected below 0.2 ug/l Minimum Reporting Level , sample collected Jun 11, 2026, sampling point TF102 | Mercury 1035 EPA method 245.1 | Not recorded |
| 2.9 ug/l , sample collected Jun 11, 2026, sampling point TF102 | Selenium 1045 EPA method 200.8 | Not recorded |
| 256000 ug/l , sample collected Jun 11, 2026, sampling point TF102 | Sodium 1052 EPA method 200.7 | Jan 1, 2026 – Dec 31, 2028 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 11, 2026, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Not recorded |
| Not detected below 4 ug/l Minimum Reporting Level , sample collected Jun 11, 2026, sampling point TF102 | Beryllium, Total 1075 EPA method 200.7 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 11, 2026, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Not recorded |
|
||
| 0.0041 mg/l , sample collected Oct 8, 2025 12:20, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| 0.102 mg/l , sample collected Oct 8, 2025 12:20, sampling point TF101 | Barium 1010 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 8, 2025 12:20, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| 0.0008 mg/l , sample collected Oct 8, 2025 12:20, sampling point TF101 | Chromium 1020 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| 0.401 mg/l , sample collected Oct 8, 2025 12:20, sampling point TF101 | Fluoride 1025 EPA method QC 10-109-12-2-A | Oct 1, 2025 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 8, 2025 12:20, sampling point TF101 | Mercury 1035 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| 0.0007 mg/l , sample collected Oct 8, 2025 12:20, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.006 mg/l , sample collected Oct 8, 2025 12:20, sampling point TF101 | Selenium 1045 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 8, 2025 12:20, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 8, 2025 12:20, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 8, 2025 12:20, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Oct 1, 2025 – Dec 31, 2025 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 9, 2025 16:30, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jul 1, 2025 – Sep 30, 2025 |
-
- Collected
- Jul 31, 2026
- Sampling point
- LC0013 Location withheld
- Sample type
- Routine
- Lab sample
- 35055010004
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
Copper, Free 1022 EPA method 200.8
- Result
- 91 ug/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
-
- Collected
- Jul 30, 2026
- Sampling point
- LC0006 Location withheld
- Sample type
- Routine
- Lab sample
- 35055010005
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
Copper, Free 1022 EPA method 200.8
- Result
- 63.3 ug/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
-
- Collected
- Jul 30, 2026
- Sampling point
- LC0001 Location withheld
- Sample type
- Routine
- Lab sample
- 35055010003
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
Copper, Free 1022 EPA method 200.8
- Result
- 282 ug/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
-
- Collected
- Jul 30, 2026
- Sampling point
- LC0010 Location withheld
- Sample type
- Routine
- Lab sample
- 35055010002
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
Copper, Free 1022 EPA method 200.8
- Result
- 115 ug/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
-
- Collected
- Jul 30, 2026
- Sampling point
- LC0012 Location withheld
- Sample type
- Routine
- Lab sample
- 35055010001
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Jan 1, 2025 – Dec 31, 2027
-
Copper, Free 1022 EPA method 200.8
- Result
- 5.1 ug/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
-
- Collected
- Jul 30, 2026
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 35055120001
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Not recorded
-
Fluoride 1025 EPA method 300.0
- Result
- 0.45 mg/l
-
- Collected
- Jun 30, 2026
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 35047595001
- Laboratory
- Pace Analytical Services, LLC
- Monitoring period
- Jan 1, 2026 – Dec 31, 2026
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
- Collected
- Jun 11, 2026
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 35043610001
- Laboratory
- Pace Analytical Services, LLC
-
Arsenic 1005 EPA method 200.8
- Result
- 1.3 ug/l
- Monitoring period
- Not recorded
-
Barium 1010 EPA method 200.7
- Result
- 108 ug/l
- Monitoring period
- Not recorded
-
Cadmium 1015 EPA method 200.7
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Chromium 1020 EPA method 200.7
- Result
- Not detected below 5 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Mercury 1035 EPA method 245.1
- Result
- Not detected below 0.2 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 2.9 ug/l
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 256000 ug/l
- Monitoring period
- Jan 1, 2026 – Dec 31, 2028
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Beryllium, Total 1075 EPA method 200.7
- Result
- Not detected below 4 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
- Collected
- Oct 8, 2025 12:20
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-251009-002
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0041 mg/l
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Barium 1010 EPA method 200.8
- Result
- 0.102 mg/l
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Chromium 1020 EPA method 200.8
- Result
- 0.0008 mg/l
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.401 mg/l
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Nickel 1036 EPA method 200.8
- Result
- 0.0007 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.006 mg/l
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2025 – Dec 31, 2025
-
- Collected
- Sep 9, 2025 16:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-250910-008
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2025 – Sep 30, 2025
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
Routine (10).