Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0100008 , Simpson Water Association #1

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for Simpson Water Association #1, 24 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2023 – Dec 31, 2025 10 0.184 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2025 10 0.0011 mg/l DS000 Accepted
Copper Jan 1, 2020 – Dec 31, 2022 10 0.164 mg/l DS000 Accepted
Lead Jan 1, 2020 – Dec 31, 2022 10 0.0008 mg/l DS000 Accepted
Copper Jan 1, 2017 – Dec 31, 2019 10 0.1506 mg/l DS000 Accepted
Lead Jan 1, 2017 – Dec 31, 2019 10 0.001 mg/l DS000 Accepted
Copper Jan 1, 2015 – Dec 31, 2017 10 0.188 mg/l DS000 Accepted
Lead Jan 1, 2015 – Dec 31, 2017 10 0.0016 mg/l DS000 Accepted
Copper Jan 1, 2012 – Dec 31, 2014 10 0.1528 mg/l DS000 Accepted
Lead Jan 1, 2012 – Dec 31, 2014 10 0.0009 mg/l DS000 Accepted
Copper Jan 1, 2009 – Dec 31, 2011 10 0.3295 mg/l DS000 Accepted
Lead Jan 1, 2009 – Dec 31, 2011 10 0.0021 mg/l DS000 Accepted
Copper Jan 1, 2006 – Dec 31, 2008 12 0.1436 mg/l DS000 Accepted
Lead Jan 1, 2006 – Dec 31, 2008 12 0.0016 mg/l DS000 Accepted
Copper Jan 1, 2000 – Dec 31, 2002 5 0.124 mg/l DS000 Accepted
Lead Jan 1, 2000 – Dec 31, 2002 5 0.003 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1996 5 0.472 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1996 5 0.011 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 5 0.396 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 5 0.002 mg/l DS000 Accepted
Copper Jan 1, 1994 – Jun 30, 1994 11 0.202 mg/l DS000 Accepted
Lead Jan 1, 1994 – Jun 30, 1994 11 0.002 mg/l DS000 Accepted
Copper Jul 1, 1993 – Dec 31, 1993 11 0.522 mg/l DS000 Accepted
Lead Jul 1, 1993 – Dec 31, 1993 11 0.004 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.