This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0140002 , Clarksdale Public Utilities
30 of the 59 analytes this system has been tested for have been detected at least once, across 1,252 samples on record.
The other 29 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 1,252 samples on record, detections range from July 6, 1992 to July 9, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 440 of 479 results | Jul 6, 1992 | Sep 11, 2024 |
| Lead 1030 | Inorganic Chemical | 367 of 479 results | Jul 6, 1992 | Sep 11, 2024 |
| TTHM 2950 | Organic Chemical | 144 of 144 results | Mar 18, 2004 | Jul 9, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 134 of 141 results | Sep 6, 2005 | Jul 9, 2025 |
| Barium 1010 | Inorganic Chemical | 98 of 99 results | Apr 9, 2002 | Feb 10, 2025 |
| Fluoride 1025 | Inorganic Chemical | 96 of 99 results | Apr 9, 2002 | Feb 10, 2025 |
| Chromium 1020 | Inorganic Chemical | 77 of 99 results | Apr 9, 2002 | Feb 10, 2025 |
| Chloroform 2941 | Organic Chemical | 72 of 72 results | Jul 25, 2006 | Dec 15, 2020 |
| Bromodichloromethane 2943 | Organic Chemical | 66 of 72 results | Jul 25, 2006 | Dec 15, 2020 |
| Selenium 1045 | Inorganic Chemical | 62 of 99 results | Apr 9, 2002 | Feb 10, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 62 of 72 results | Jul 25, 2006 | Dec 15, 2020 |
| Trichloroacetic Acid 2452 | Organic Chemical | 60 of 67 results | Aug 10, 2010 | Dec 15, 2020 |
| Dibromoacetic Acid 2454 | Organic Chemical | 60 of 67 results | Jun 23, 2008 | Dec 15, 2020 |
| Dichloroacetic Acid 2451 | Organic Chemical | 56 of 67 results | Jun 23, 2008 | Jul 27, 2020 |
| Bromoform 2942 | Organic Chemical | 54 of 72 results | Nov 14, 2006 | Dec 15, 2020 |
| Arsenic 1005 | Inorganic Chemical | 49 of 99 results | Apr 9, 2002 | Feb 10, 2025 |
| Nickel 1036 | Inorganic Chemical | 42 of 99 results | Apr 9, 2002 | Feb 10, 2025 |
| Sodium 1052 | Inorganic Chemical | 15 of 15 results | Oct 2, 2019 | Feb 1, 2021 |
| Cyanide 1024 | Inorganic Chemical | 12 of 84 results | Sep 8, 2003 | Jun 4, 2025 |
| Radium-226 4020 | Radionuclide | 10 of 28 results | Mar 26, 2018 | May 29, 2019 |
| Sulfate 1055 | Inorganic Chemical | 9 of 26 results | Sep 8, 2003 | Sep 8, 2003 |
| Thallium, Total 1085 | Inorganic Chemical | 8 of 99 results | Mar 9, 2005 | Apr 7, 2020 |
| Nitrite 1041 | Inorganic Chemical | 7 of 175 results | May 19, 2008 | Jan 10, 2022 |
| Monobromoacetic Acid 2453 | Organic Chemical | 6 of 67 results | Jun 4, 2014 | Dec 17, 2019 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 6 of 28 results | Mar 26, 2018 | May 29, 2019 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 10 results | May 29, 2019 | May 29, 2019 |
| Radium-228 4030 | Radionuclide | 4 of 28 results | May 29, 2019 | May 29, 2019 |
| Cadmium 1015 | Inorganic Chemical | 4 of 99 results | Mar 9, 2005 | Jan 23, 2006 |
| Monochloroacetic Acid 2450 | Organic Chemical | 3 of 67 results | Nov 29, 2016 | Dec 17, 2019 |
| Nitrate 1040 | Inorganic Chemical | 1 of 175 results | Jun 12, 2006 | Jun 12, 2006 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 291–300 of 1,252 samples, newest first — collected May 29, 2019 to May 29, 2019. The summary above covers all 1,252.
20 results from the 10 samples listed here: 12 detected, 8 not detected. Across the whole record it is 2,029 of 5,159. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 1.02 pci/l , sample collected May 29, 2019 10:15, sampling point TF112 | Combined Radium (-226 & -228) 4010 EPA method 7500-RA | Not recorded |
| 0.38 pci/l , sample collected May 29, 2019 10:15, sampling point TF112 | Radium-226 4020 EPA method 7500-RAB | Jan 1, 2019 – Dec 31, 2027 |
| 0.64 pci/l , sample collected May 29, 2019 10:15, sampling point TF112 | Radium-228 4030 EPA method 7500-RAD | Jan 1, 2019 – Dec 31, 2027 |
|
||
| 3.7 pci/l , sample collected May 29, 2019 10:15, sampling point TF112 | Gross Alpha, Incl. Radon & U 4002 EPA method 7110B | Jan 1, 2019 – Dec 31, 2027 |
|
||
| 2.06 pci/l , sample collected May 29, 2019 09:55, sampling point TF111 | Combined Radium (-226 & -228) 4010 EPA method 7500-RA | Not recorded |
| 0.46 pci/l , sample collected May 29, 2019 09:55, sampling point TF111 | Radium-226 4020 EPA method 7500-RAB | Jan 1, 2019 – Dec 31, 2027 |
| 1.6 pci/l , sample collected May 29, 2019 09:55, sampling point TF111 | Radium-228 4030 EPA method 7500-RAD | Jan 1, 2019 – Dec 31, 2027 |
|
||
| Not detected below 1.8 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:55, sampling point TF111 | Gross Alpha, Incl. Radon & U 4002 EPA method 7110B | Jan 1, 2019 – Dec 31, 2027 |
|
||
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:35, sampling point TF108 | Combined Radium (-226 & -228) 4010 EPA method 7500-RA | Not recorded |
| 0.36 pci/l , sample collected May 29, 2019 09:35, sampling point TF108 | Radium-226 4020 EPA method 7500-RAB | Jan 1, 2019 – Dec 31, 2027 |
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:35, sampling point TF108 | Radium-228 4030 EPA method 7500-RAD | Jan 1, 2019 – Dec 31, 2027 |
|
||
| 2.1 pci/l , sample collected May 29, 2019 09:35, sampling point TF108 | Gross Alpha, Incl. Radon & U 4002 EPA method 7110B | Jan 1, 2019 – Dec 31, 2027 |
|
||
| Not detected below 0.6 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:15, sampling point TF109 | Combined Radium (-226 & -228) 4010 EPA method 7500-RA | Not recorded |
| 0.34 pci/l , sample collected May 29, 2019 09:15, sampling point TF109 | Radium-226 4020 EPA method 7500-RAB | Jan 1, 2019 – Dec 31, 2027 |
| Not detected below 0.6 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:15, sampling point TF109 | Radium-228 4030 EPA method 7500-RAD | Jan 1, 2019 – Dec 31, 2027 |
|
||
| Not detected below 1.3 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:15, sampling point TF109 | Gross Alpha, Incl. Radon & U 4002 EPA method 7110B | Jan 1, 2019 – Dec 31, 2027 |
|
||
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:00, sampling point TF081 | Combined Radium (-226 & -228) 4010 EPA method 7500-RA | Not recorded |
| 0.2 pci/l , sample collected May 29, 2019 09:00, sampling point TF081 | Radium-226 4020 EPA method 7500-RAB | Jan 1, 2019 – Dec 31, 2027 |
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected May 29, 2019 09:00, sampling point TF081 | Radium-228 4030 EPA method 7500-RAD | Jan 1, 2019 – Dec 31, 2027 |
|
||
| 1.9 pci/l , sample collected May 29, 2019 09:00, sampling point TF081 | Gross Alpha, Incl. Radon & U 4002 EPA method 7110B | Jan 1, 2019 – Dec 31, 2027 |
-
- Collected
- May 29, 2019 10:15
- Sampling point
- TF112 Treatment Plant T112
- Sample type
- Routine
- Lab sample
- 4311725
- Laboratory
- Eurofins Eaton Analytical South Bend in
-
Combined Radium (-226 & -228) 4010 EPA method 7500-RA
- Result
- 1.02 pci/l
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 7500-RAB
- Result
- 0.38 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Radium-228 4030 EPA method 7500-RAD
- Result
- 0.64 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
- Collected
- May 29, 2019 10:15
- Sampling point
- TF112 Treatment Plant T112
- Sample type
- Routine
- Lab sample
- 4311724
- Laboratory
- Eurofins Eaton Analytical South Bend in
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Gross Alpha, Incl. Radon & U 4002 EPA method 7110B
- Result
- 3.7 pci/l
-
- Collected
- May 29, 2019 09:55
- Sampling point
- TF111 Treatment Plant T111
- Sample type
- Routine
- Lab sample
- 4311723
- Laboratory
- Eurofins Eaton Analytical South Bend in
-
Combined Radium (-226 & -228) 4010 EPA method 7500-RA
- Result
- 2.06 pci/l
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 7500-RAB
- Result
- 0.46 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Radium-228 4030 EPA method 7500-RAD
- Result
- 1.6 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
- Collected
- May 29, 2019 09:55
- Sampling point
- TF111 Treatment Plant T111
- Sample type
- Routine
- Lab sample
- 4311722
- Laboratory
- Eurofins Eaton Analytical South Bend in
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Gross Alpha, Incl. Radon & U 4002 EPA method 7110B
- Result
- Not detected below 1.8 pci/l Minimum Reporting Level
-
- Collected
- May 29, 2019 09:35
- Sampling point
- TF108 Treatment Plant T108
- Sample type
- Routine
- Lab sample
- 4311721
- Laboratory
- Eurofins Eaton Analytical South Bend in
-
Combined Radium (-226 & -228) 4010 EPA method 7500-RA
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 7500-RAB
- Result
- 0.36 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Radium-228 4030 EPA method 7500-RAD
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
- Collected
- May 29, 2019 09:35
- Sampling point
- TF108 Treatment Plant T108
- Sample type
- Routine
- Lab sample
- 4311720
- Laboratory
- Eurofins Eaton Analytical South Bend in
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Gross Alpha, Incl. Radon & U 4002 EPA method 7110B
- Result
- 2.1 pci/l
-
- Collected
- May 29, 2019 09:15
- Sampling point
- TF109 Treatment Plant T109
- Sample type
- Routine
- Lab sample
- 4311719
- Laboratory
- Eurofins Eaton Analytical South Bend in
-
Combined Radium (-226 & -228) 4010 EPA method 7500-RA
- Result
- Not detected below 0.6 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 7500-RAB
- Result
- 0.34 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Radium-228 4030 EPA method 7500-RAD
- Result
- Not detected below 0.6 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
- Collected
- May 29, 2019 09:15
- Sampling point
- TF109 Treatment Plant T109
- Sample type
- Routine
- Lab sample
- 4311718
- Laboratory
- Eurofins Eaton Analytical South Bend in
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Gross Alpha, Incl. Radon & U 4002 EPA method 7110B
- Result
- Not detected below 1.3 pci/l Minimum Reporting Level
-
- Collected
- May 29, 2019 09:00
- Sampling point
- TF081 Treatment Plant T081
- Sample type
- Routine
- Lab sample
- 4311717
- Laboratory
- Eurofins Eaton Analytical South Bend in
-
Combined Radium (-226 & -228) 4010 EPA method 7500-RA
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 7500-RAB
- Result
- 0.2 pci/l
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Radium-228 4030 EPA method 7500-RAD
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
- Collected
- May 29, 2019 09:00
- Sampling point
- TF081 Treatment Plant T081
- Sample type
- Routine
- Lab sample
- 4311716
- Laboratory
- Eurofins Eaton Analytical South Bend in
- Monitoring period
- Jan 1, 2019 – Dec 31, 2027
-
Gross Alpha, Incl. Radon & U 4002 EPA method 7110B
- Result
- 1.9 pci/l
Routine (10).