This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0140009 , Lu-Rand Utility District
25 of the 56 analytes this system has been tested for have been detected at least once, across 251 samples on record.
The other 31 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 251 samples on record, detections range from June 29, 1993 to March 26, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Lead 1030 | Inorganic Chemical | 61 of 64 results | Jun 29, 1993 | Nov 9, 2020 |
| Copper, Free 1022 | Inorganic Chemical | 56 of 64 results | Jun 29, 1993 | Nov 9, 2020 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 35 of 37 results | Sep 25, 2007 | Mar 26, 2025 |
| TTHM 2950 | Organic Chemical | 33 of 35 results | Jul 26, 2007 | Mar 26, 2025 |
| Chloroform 2941 | Organic Chemical | 28 of 30 results | Jul 26, 2007 | Jun 25, 2018 |
| Bromodichloromethane 2943 | Organic Chemical | 28 of 30 results | Jul 26, 2007 | Jun 25, 2018 |
| Dibromoacetic Acid 2454 | Organic Chemical | 26 of 29 results | Oct 1, 2007 | Jun 25, 2018 |
| Dibromochloromethane 2944 | Organic Chemical | 26 of 30 results | Jul 26, 2007 | Jun 25, 2018 |
| Bromoform 2942 | Organic Chemical | 24 of 30 results | Jul 26, 2007 | Jun 25, 2018 |
| Barium 1010 | Inorganic Chemical | 21 of 21 results | Apr 16, 2002 | Feb 3, 2025 |
| Fluoride 1025 | Inorganic Chemical | 21 of 21 results | Apr 16, 2002 | Feb 3, 2025 |
| Chromium 1020 | Inorganic Chemical | 19 of 21 results | Apr 16, 2002 | Feb 3, 2025 |
| Selenium 1045 | Inorganic Chemical | 19 of 21 results | Apr 16, 2002 | Feb 3, 2025 |
| Dichloroacetic Acid 2451 | Organic Chemical | 18 of 29 results | Oct 1, 2007 | Nov 7, 2017 |
| Arsenic 1005 | Inorganic Chemical | 16 of 21 results | Sep 8, 2003 | Feb 3, 2025 |
| Trichloroacetic Acid 2452 | Organic Chemical | 14 of 29 results | Oct 1, 2007 | Jan 21, 2014 |
| Monobromoacetic Acid 2453 | Organic Chemical | 12 of 29 results | Oct 1, 2007 | Jul 23, 2014 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 10 of 10 results | Dec 7, 2011 | Jul 10, 2012 |
| Nickel 1036 | Inorganic Chemical | 7 of 21 results | Apr 15, 2008 | Sep 25, 2018 |
| Nitrite 1041 | Inorganic Chemical | 4 of 39 results | Jun 12, 2006 | Jan 27, 2014 |
| Monochloroacetic Acid 2450 | Organic Chemical | 3 of 29 results | Mar 3, 2009 | Apr 21, 2014 |
| Sodium 1052 | Inorganic Chemical | 2 of 2 results | Oct 28, 2019 | Oct 28, 2019 |
| Sulfate 1055 | Inorganic Chemical | 2 of 5 results | Sep 8, 2003 | Sep 8, 2003 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 19 results | Apr 20, 2021 | Apr 20, 2021 |
| Cyanide 1024 | Inorganic Chemical | 1 of 16 results | Aug 9, 2011 | Aug 9, 2011 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 21–30 of 251 samples, newest first — collected April 22, 2020 to January 12, 2022. The summary above covers all 251.
47 results from the 10 samples listed here: 14 detected, 33 not detected. Across the whole record it is 487 of 1,283. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 12, 2022 13:55, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 12, 2022 13:55, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 12, 2022 13:55, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| 1.03 ug/l , sample collected Apr 20, 2021 12:10, sampling point TF101 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Benzene 2990 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Toluene 2991 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 20, 2021 12:10, sampling point TF101 | Styrene 2996 EPA method 524.2 | Jan 1, 2016 – Dec 31, 2021 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Apr 20, 2021 12:05, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Apr 20, 2021 12:00, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 0.0367 mg/l , sample collected Nov 9, 2020 06:11, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0009 mg/l , sample collected Nov 9, 2020 06:11, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0403 mg/l , sample collected Nov 9, 2020 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0011 mg/l , sample collected Nov 9, 2020 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0239 mg/l , sample collected Nov 9, 2020 05:04, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2020 05:04, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0377 mg/l , sample collected Nov 9, 2020 05:35, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0031 mg/l , sample collected Nov 9, 2020 05:35, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0269 mg/l , sample collected Nov 9, 2020 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2020 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0032 mg/l , sample collected Apr 22, 2020 14:10, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0214 mg/l , sample collected Apr 22, 2020 14:10, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 22, 2020 14:10, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0021 mg/l , sample collected Apr 22, 2020 14:10, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.491 mg/l , sample collected Apr 22, 2020 14:10, sampling point TF102 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 22, 2020 14:10, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 22, 2020 14:10, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.0108 mg/l , sample collected Apr 22, 2020 14:10, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 22, 2020 14:10, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 22, 2020 14:10, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 22, 2020 14:10, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
-
- Collected
- Jan 12, 2022 13:55
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NI-220113-039
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2022
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Apr 20, 2021 12:10
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 210421-010VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2016 – Dec 31, 2021
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- 1.03 ug/l
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Apr 20, 2021 12:05
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- CN-210421-021
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Apr 20, 2021 12:00
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- CN-210421-020
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Nov 9, 2020 06:11
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 201110-005PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0367 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0009 mg/l
-
- Collected
- Nov 9, 2020 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 201110-004PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0403 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0011 mg/l
-
- Collected
- Nov 9, 2020 05:04
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 201110-003PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0239 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Nov 9, 2020 05:35
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 201110-002PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0377 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0031 mg/l
-
- Collected
- Nov 9, 2020 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 201110-001PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0269 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Apr 22, 2020 14:10
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 200423-017IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0032 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0214 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- 0.0021 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.491 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.0108 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
Routine (10).