This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0140012 , Moore Bayou Water Association
25 of the 57 analytes this system has been tested for have been detected at least once, across 463 samples on record.
The other 32 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 463 samples on record, detections range from November 23, 1993 to July 29, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 157 of 162 results | Nov 23, 1993 | Jun 20, 2023 |
| Lead 1030 | Inorganic Chemical | 138 of 162 results | Nov 23, 1993 | Jun 20, 2023 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 94 of 116 results | Sep 13, 2004 | Jul 29, 2025 |
| TTHM 2950 | Organic Chemical | 82 of 117 results | Sep 13, 2004 | Jul 29, 2025 |
| Bromoform 2942 | Organic Chemical | 51 of 76 results | May 15, 2006 | Nov 26, 2018 |
| Bromodichloromethane 2943 | Organic Chemical | 50 of 76 results | May 15, 2006 | Nov 26, 2018 |
| Dibromochloromethane 2944 | Organic Chemical | 50 of 76 results | May 15, 2006 | Nov 26, 2018 |
| Dibromoacetic Acid 2454 | Organic Chemical | 47 of 69 results | Dec 14, 2005 | Nov 26, 2018 |
| Chloroform 2941 | Organic Chemical | 43 of 76 results | May 15, 2006 | Nov 26, 2018 |
| Dichloroacetic Acid 2451 | Organic Chemical | 33 of 69 results | Dec 14, 2005 | Nov 26, 2018 |
| Trichloroacetic Acid 2452 | Organic Chemical | 21 of 69 results | Jan 29, 2008 | Nov 26, 2018 |
| Monobromoacetic Acid 2453 | Organic Chemical | 17 of 69 results | Jan 29, 2008 | Aug 28, 2017 |
| Barium 1010 | Inorganic Chemical | 11 of 11 results | May 14, 2002 | Feb 3, 2025 |
| Fluoride 1025 | Inorganic Chemical | 11 of 11 results | May 14, 2002 | Feb 3, 2025 |
| Selenium 1045 | Inorganic Chemical | 11 of 11 results | May 14, 2002 | Feb 3, 2025 |
| Arsenic 1005 | Inorganic Chemical | 9 of 11 results | Jan 26, 2004 | Feb 3, 2025 |
| Chromium 1020 | Inorganic Chemical | 9 of 11 results | May 14, 2002 | Feb 3, 2025 |
| Monochloroacetic Acid 2450 | Organic Chemical | 6 of 69 results | Dec 14, 2005 | Dec 1, 2016 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 24, 2019 | Oct 21, 2024 |
| Nickel 1036 | Inorganic Chemical | 3 of 11 results | Mar 1, 2005 | Apr 21, 2014 |
| Nitrite 1041 | Inorganic Chemical | 2 of 22 results | Jun 12, 2006 | Jan 29, 2014 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 1 of 22 results | Jun 12, 2006 | Jun 12, 2006 |
| Nitrate 1040 | Inorganic Chemical | 1 of 22 results | Jun 12, 2006 | Jun 12, 2006 |
| Cadmium 1015 | Inorganic Chemical | 1 of 11 results | Mar 1, 2005 | Mar 1, 2005 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 13 results | Jul 12, 2004 | Jul 12, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 361–370 of 463 samples, newest first — collected June 26, 2003 to January 26, 2004. The summary above covers all 463.
47 results from the 10 samples listed here: 17 detected, 30 not detected. Across the whole record it is 852 of 1,706. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| 0.001 mg/l , sample collected Jan 26, 2004, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.008 mg/l , sample collected Jan 26, 2004, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.002 mg/l , sample collected Jan 26, 2004, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.261 mg/l , sample collected Jan 26, 2004, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.005 mg/l , sample collected Jan 26, 2004, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 26, 2004, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Xylenes, Total 2955 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Dichloromethane 2964 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | O-Dichlorobenzene 2968 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | P-Dichlorobenzene 2969 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Vinyl Chloride 2976 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | 1,1-Dichloroethylene 2977 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | 1,2-Dichloroethane 2980 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | 1,1,1-Trichloroethane 2981 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Carbon Tetrachloride 2982 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | 1,2-Dichloropropane 2983 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Trichloroethylene 2984 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | 1,1,2-Trichloroethane 2985 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Tetrachloroethylene 2987 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Chlorobenzene 2989 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Benzene 2990 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Toluene 2991 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Ethylbenzene 2992 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 12, 2004, sampling point TF101 | Styrene 2996 | Jan 1, 2004 – Mar 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Nov 24, 2003, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Not recorded |
|
||
| 0.172 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.006 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.15 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.001 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.127 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.002 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.185 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.002 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.141 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.002 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.264 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.001 mg/l , sample collected Jun 26, 2003, sampling point DS000 | Lead 1030 | Not recorded |
-
- Collected
- Jan 26, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040127-062CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Jan 26, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040127-023IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.008 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.002 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.261 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.005 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Jan 12, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040113-082VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Mar 31, 2004
-
1,2,4-Trichlorobenzene 2378
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Nov 24, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 031125-012CN
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Jun 26, 2003
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 030627-250PB
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.172 mg/l
-
Lead 1030
- Result
- 0.006 mg/l
-
- Collected
- Jun 26, 2003
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 030627-200PB
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.15 mg/l
-
Lead 1030
- Result
- 0.001 mg/l
-
- Collected
- Jun 26, 2003
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 030627-199PB
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.127 mg/l
-
Lead 1030
- Result
- 0.002 mg/l
-
- Collected
- Jun 26, 2003
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 030627-195PB
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.185 mg/l
-
Lead 1030
- Result
- 0.002 mg/l
-
- Collected
- Jun 26, 2003
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 030627-194PB
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.141 mg/l
-
Lead 1030
- Result
- 0.002 mg/l
-
- Collected
- Jun 26, 2003
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 030627-193PB
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.264 mg/l
-
Lead 1030
- Result
- 0.001 mg/l
Routine (10).