This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0160009 , Southwest Covington W/A
25 of the 58 analytes this system has been tested for have been detected at least once, across 435 samples on record.
The other 33 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 435 samples on record, detections range from September 28, 1993 to October 28, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 195 of 214 results | Sep 28, 1993 | Jul 16, 2024 |
| Lead 1030 | Inorganic Chemical | 166 of 214 results | Sep 28, 1993 | Jul 16, 2024 |
| Barium 1010 | Inorganic Chemical | 33 of 33 results | Apr 23, 2002 | Feb 5, 2025 |
| Fluoride 1025 | Inorganic Chemical | 31 of 33 results | Apr 23, 2002 | Feb 5, 2025 |
| Chromium 1020 | Inorganic Chemical | 22 of 33 results | Apr 23, 2002 | Feb 5, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 15 of 15 results | Mar 6, 2012 | Oct 2, 2012 |
| Nickel 1036 | Inorganic Chemical | 11 of 33 results | Feb 28, 2005 | May 1, 2017 |
| Sulfate 1055 | Inorganic Chemical | 9 of 9 results | Apr 23, 2002 | Jan 26, 2004 |
| TTHM 2950 | Organic Chemical | 8 of 12 results | May 19, 2004 | Oct 28, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 8 of 14 results | Jul 10, 2007 | Dec 7, 2022 |
| Chloroform 2941 | Organic Chemical | 6 of 7 results | Jul 10, 2007 | Oct 28, 2025 |
| Sodium 1052 | Inorganic Chemical | 6 of 6 results | Sep 24, 2019 | Oct 14, 2024 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 5 of 19 results | Mar 6, 2012 | Oct 2, 2012 |
| Radium-228 4030 | Radionuclide | 5 of 19 results | Mar 6, 2012 | Oct 2, 2012 |
| Selenium 1045 | Inorganic Chemical | 4 of 33 results | Feb 28, 2005 | Jan 23, 2006 |
| Bromodichloromethane 2943 | Organic Chemical | 3 of 7 results | Jul 10, 2007 | Aug 30, 2011 |
| Dibromochloromethane 2944 | Organic Chemical | 3 of 7 results | Jul 10, 2007 | Aug 30, 2011 |
| Cadmium 1015 | Inorganic Chemical | 3 of 33 results | Jan 23, 2006 | Jan 23, 2006 |
| Monobromoacetic Acid 2453 | Organic Chemical | 2 of 7 results | Jul 25, 2018 | Jul 30, 2020 |
| Dichloroacetic Acid 2451 | Organic Chemical | 2 of 7 results | Sep 17, 2008 | Aug 30, 2011 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 7 results | Jul 25, 2018 | Jul 25, 2018 |
| Cyanide 1024 | Inorganic Chemical | 1 of 28 results | Jul 9, 2014 | Jul 9, 2014 |
| Trichloroacetic Acid 2452 | Organic Chemical | 1 of 7 results | Aug 30, 2011 | Aug 30, 2011 |
| Thallium, Total 1085 | Inorganic Chemical | 1 of 33 results | Jul 27, 2011 | Jul 27, 2011 |
| Mercury 1035 | Inorganic Chemical | 1 of 33 results | Feb 28, 2005 | Feb 28, 2005 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 311–320 of 435 samples, newest first — collected January 23, 2006 to April 18, 2007. The summary above covers all 435.
51 results from the 10 samples listed here: 15 detected, 36 not detected. Across the whole record it is 542 of 1,880. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 18, 2007, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2007 – Dec 31, 2007 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Apr 18, 2007, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2007 – Dec 31, 2007 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Apr 18, 2007, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2007 – Dec 31, 2007 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF101 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF101 | Nitrate 1040 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF101 | Nitrite 1041 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF103 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF103 | Nitrate 1040 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jun 14, 2006, sampling point TF103 | Nitrite 1041 EPA method 353.2 | Jan 1, 2006 – Dec 31, 2006 |
|
||
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2005 – Dec 31, 2007 |
|
||
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2005 – Dec 31, 2007 |
|
||
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2005 – Dec 31, 2007 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.005264 mg/l , sample collected Jan 23, 2006, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.000196 mg/l , sample collected Jan 23, 2006, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.000702 mg/l , sample collected Jan 23, 2006, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.121442 mg/l , sample collected Jan 23, 2006, sampling point TF101 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.001102 mg/l , sample collected Jan 23, 2006, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF101 | Uranium-238 4009 | Not recorded |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.004089 mg/l , sample collected Jan 23, 2006, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.000224 mg/l , sample collected Jan 23, 2006, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.000888 mg/l , sample collected Jan 23, 2006, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.105107 mg/l , sample collected Jan 23, 2006, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.001233 mg/l , sample collected Jan 23, 2006, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF102 | Uranium-238 4009 | Not recorded |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Arsenic 1005 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.005046 mg/l , sample collected Jan 23, 2006, sampling point TF103 | Barium 1010 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.00022 mg/l , sample collected Jan 23, 2006, sampling point TF103 | Cadmium 1015 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.000755 mg/l , sample collected Jan 23, 2006, sampling point TF103 | Chromium 1020 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| 0.114045 mg/l , sample collected Jan 23, 2006, sampling point TF103 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Mercury 1035 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.001126 mg/l , sample collected Jan 23, 2006, sampling point TF103 | Selenium 1045 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2005 – Dec 31, 2007 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 23, 2006, sampling point TF103 | Uranium-238 4009 | Not recorded |
-
- Collected
- Apr 18, 2007
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 070419-012NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2007 – Dec 31, 2007
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jun 14, 2006
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 060615-004NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2006 – Dec 31, 2006
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jun 14, 2006
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 060615-015NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2006 – Dec 31, 2006
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jun 14, 2006
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 060615-003NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2006 – Dec 31, 2006
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jan 23, 2006
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 060124-012CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
-
- Collected
- Jan 23, 2006
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 060124-011CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
-
- Collected
- Jan 23, 2006
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 060124-017CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
-
- Collected
- Jan 23, 2006
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 060124-090IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Barium 1010 EPA method 200.8
- Result
- 0.005264 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Cadmium 1015 EPA method 200.8
- Result
- 0.000196 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Chromium 1020 EPA method 200.8
- Result
- 0.000702 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.121442 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0002 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.001102 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Uranium-238 4009
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
- Collected
- Jan 23, 2006
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 060124-091IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Barium 1010 EPA method 200.8
- Result
- 0.004089 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Cadmium 1015 EPA method 200.8
- Result
- 0.000224 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Chromium 1020 EPA method 200.8
- Result
- 0.000888 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.105107 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0002 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.001233 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Uranium-238 4009
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
- Collected
- Jan 23, 2006
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 060124-089IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Barium 1010 EPA method 200.8
- Result
- 0.005046 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Cadmium 1015 EPA method 200.8
- Result
- 0.00022 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Chromium 1020 EPA method 200.8
- Result
- 0.000755 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.114045 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0002 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.001126 mg/l
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2005 – Dec 31, 2007
-
Uranium-238 4009
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
Routine (10).