This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0190004 , Providence Water Association
21 of the 58 analytes this system has been tested for have been detected at least once, across 212 samples on record.
The other 37 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 212 samples on record, detections range from October 18, 1993 to June 4, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 82 of 111 results | Oct 18, 1993 | Jun 4, 2025 |
| Lead 1030 | Inorganic Chemical | 48 of 111 results | Oct 18, 1993 | Jun 4, 2025 |
| Barium 1010 | Inorganic Chemical | 13 of 13 results | May 21, 2002 | Feb 4, 2025 |
| Nickel 1036 | Inorganic Chemical | 12 of 13 results | May 21, 2002 | Feb 4, 2025 |
| Fluoride 1025 | Inorganic Chemical | 11 of 13 results | Sep 10, 2003 | Feb 4, 2025 |
| TTHM 2950 | Organic Chemical | 10 of 10 results | May 19, 2004 | Feb 11, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 8 of 9 results | Oct 24, 2005 | Feb 11, 2025 |
| Chromium 1020 | Inorganic Chemical | 8 of 13 results | May 21, 2002 | Feb 4, 2025 |
| Chloroform 2941 | Organic Chemical | 6 of 6 results | Sep 11, 2006 | Jul 24, 2018 |
| Bromodichloromethane 2943 | Organic Chemical | 5 of 6 results | Sep 11, 2006 | Jul 24, 2018 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 5 results | Dec 12, 2011 | Jul 10, 2012 |
| Dichloroacetic Acid 2451 | Organic Chemical | 4 of 4 results | Sep 17, 2008 | Jul 24, 2018 |
| Sulfate 1055 | Inorganic Chemical | 4 of 4 results | May 21, 2002 | Feb 4, 2004 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 18, 2019 | Jan 29, 2024 |
| Trichloroacetic Acid 2452 | Organic Chemical | 3 of 4 results | Jul 9, 2012 | Jul 24, 2018 |
| Selenium 1045 | Inorganic Chemical | 3 of 13 results | May 21, 2002 | Feb 28, 2005 |
| Cadmium 1015 | Inorganic Chemical | 2 of 13 results | May 21, 2002 | Feb 28, 2005 |
| Xylenes, Total 2955 | Organic Chemical | 2 of 22 results | Apr 13, 2004 | Jul 14, 2004 |
| Styrene 2996 | Organic Chemical | 1 of 22 results | Oct 18, 2005 | Oct 18, 2005 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 1 of 23 results | May 12, 2004 | May 12, 2004 |
| Nitrate 1040 | Inorganic Chemical | 1 of 23 results | May 12, 2004 | May 12, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 21–30 of 212 samples, newest first — collected August 28, 2019 to June 14, 2022. The summary above covers all 212.
37 results from the 10 samples listed here: 11 detected, 26 not detected. Across the whole record it is 232 of 1,003. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
Units in this table
Sodium is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0679 mg/l , sample collected Jun 14, 2022 06:03, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.6 ug/l , sample collected Jun 14, 2022 06:03, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0024 mg/l , sample collected May 10, 2022 13:20, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.688 mg/l , sample collected May 10, 2022 13:20, sampling point TF102 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0008 mg/l , sample collected May 10, 2022 13:20, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2022 13:20, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 18, 2022 13:46, sampling point TF102 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 18, 2022 13:46, sampling point TF102 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 18, 2022 13:46, sampling point TF102 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected May 12, 2021 13:28, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 61.1 mg/l , sample collected Feb 9, 2021 15:11, sampling point TF102 | Sodium 1052 EPA method 200.7 | Not recorded |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 9, 2021 15:11, sampling point TF102 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2021 – Dec 31, 2021 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 9, 2021 15:11, sampling point TF102 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2021 – Dec 31, 2021 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 9, 2021 15:11, sampling point TF102 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2021 – Dec 31, 2021 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.00302 mg/l , sample collected Jan 19, 2021 11:35, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.00056 mg/l , sample collected Jan 19, 2021 11:35, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.742 mg/l , sample collected Jan 19, 2021 11:35, sampling point TF102 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.00097 mg/l , sample collected Jan 19, 2021 11:35, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 19, 2021 11:35, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 11, 2020 14:21, sampling point TF102 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 11, 2020 14:21, sampling point TF102 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 11, 2020 14:21, sampling point TF102 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
|
||
| 61000 ug/l , sample collected Sep 18, 2019 14:52, sampling point TF102 | Sodium 1052 EPA method 200.7 | Not recorded |
|
||
| Not detected below 0.19 mfl Minimum Reporting Level , sample collected Aug 28, 2019, sampling point DS000 | Asbestos 1094 EPA method 100.2 | Not recorded |
-
- Collected
- Jun 14, 2022 06:03
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- PB-220615-016
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0679 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.6 ug/l
-
- Collected
- May 10, 2022 13:20
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- IN-220511-007
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0024 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.688 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.0008 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
- Collected
- Jan 18, 2022 13:46
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- NI-220119-019
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2022
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- May 12, 2021 13:28
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- CN-210513-009
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Feb 9, 2021 15:11
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- NA-210210-038
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 61.1 mg/l
-
- Collected
- Feb 9, 2021 15:11
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- NI-210210-043
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2021 – Dec 31, 2021
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jan 19, 2021 11:35
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- IN-210120-020
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.00302 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- 0.00056 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.742 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.00097 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
- Collected
- Feb 11, 2020 14:21
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 200212-001NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2020
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Sep 18, 2019 14:52
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 680-174388-68
- Laboratory
- Test America-Savannah
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 61000 ug/l
-
- Collected
- Aug 28, 2019
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 041923334-0001
- Laboratory
- Emsl Analytical, Inc.
- Monitoring period
- Not recorded
-
Asbestos 1094 EPA method 100.2
- Result
- Not detected below 0.19 mfl Minimum Reporting Level
Routine (10).