This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0190006 , Sixtown Water Association
31 of the 71 analytes this system has been tested for have been detected at least once, across 374 samples on record.
The other 40 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 374 samples on record, detections range from December 13, 1993 to July 27, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Lead 1030 | Inorganic Chemical | 263 of 272 results | Dec 13, 1993 | Jul 27, 2026 |
| Copper, Free 1022 | Inorganic Chemical | 259 of 272 results | Dec 13, 1993 | Jul 27, 2026 |
| Barium 1010 | Inorganic Chemical | 12 of 12 results | May 21, 2002 | Feb 4, 2025 |
| Nickel 1036 | Inorganic Chemical | 10 of 12 results | May 21, 2002 | Feb 4, 2025 |
| TTHM 2950 | Organic Chemical | 9 of 24 results | Aug 2, 2007 | Aug 13, 2025 |
| Bromodichloromethane 2943 | Organic Chemical | 6 of 19 results | Dec 18, 2023 | Aug 13, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 6 of 19 results | Dec 18, 2023 | Aug 13, 2025 |
| Chloroform 2941 | Organic Chemical | 5 of 19 results | Dec 18, 2023 | Aug 13, 2025 |
| Sodium 1052 | Inorganic Chemical | 5 of 5 results | Apr 4, 2017 | Jan 29, 2024 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 5 results | Dec 7, 2011 | Jul 17, 2012 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 4 of 24 results | Aug 2, 2007 | Aug 26, 2020 |
| Chromium 1020 | Inorganic Chemical | 4 of 12 results | May 21, 2002 | Oct 9, 2018 |
| Bromoform 2942 | Organic Chemical | 3 of 19 results | Dec 18, 2023 | Oct 31, 2024 |
| Monochloroacetic Acid 2450 | Organic Chemical | 2 of 18 results | Jul 23, 2018 | Aug 26, 2020 |
| Calcium 1016 | Inorganic Chemical | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Chloride 1017 | Inorganic Chemical | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Iron 1028 | Inorganic Chemical | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Magnesium 1031 | Inorganic Chemical | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Manganese 1032 | Inorganic Chemical | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Potassium 1042 | Inorganic Chemical | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Residue, Total, Filterable 1057 | Water Quality | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Carbon Dioxide 1901 | Water Quality | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Color 1905 | Water Quality | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Hardness, Total (As Caco3) 1915 | Water Quality | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Alkalinity, Total 1927 | Water Quality | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| PH, Field Result PHFD | Water Quality | 2 of 2 results | Apr 4, 2017 | Apr 4, 2017 |
| Nitrate 1040 | Inorganic Chemical | 2 of 23 results | Aug 8, 2005 | Apr 18, 2007 |
| Fluoride 1025 | Inorganic Chemical | 1 of 14 results | Oct 9, 2018 | Oct 9, 2018 |
| Calculated Sodium NACA | Water Quality | 1 of 1 result | Apr 4, 2017 | Apr 4, 2017 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 1 of 23 results | Apr 18, 2007 | Apr 18, 2007 |
| Selenium 1045 | Inorganic Chemical | 1 of 12 results | Feb 4, 2004 | Feb 4, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 301–310 of 374 samples, newest first — collected June 12, 2000 to February 4, 2004. The summary above covers all 374.
58 results from the 10 samples listed here: 19 detected, 39 not detected. Across the whole record it is 623 of 1,200. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
We withheld the location of 1 sampling point below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.045 mg/l , sample collected Feb 4, 2004, sampling point TF080 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.001 mg/l , sample collected Feb 4, 2004, sampling point TF080 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.001 mg/l , sample collected Feb 4, 2004, sampling point TF080 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.001 mg/l , sample collected Feb 4, 2004, sampling point TF080 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2004, sampling point TF080 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | 1,2,4-Trichlorobenzene 2378 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Cis-1,2-Dichloroethylene 2380 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Xylenes, Total 2955 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Dichloromethane 2964 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | O-Dichlorobenzene 2968 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | P-Dichlorobenzene 2969 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Vinyl Chloride 2976 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | 1,1-Dichloroethylene 2977 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Trans-1,2-Dichloroethylene 2979 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | 1,2-Dichloroethane 2980 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | 1,1,1-Trichloroethane 2981 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Carbon Tetrachloride 2982 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | 1,2-Dichloropropane 2983 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Trichloroethylene 2984 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | 1,1,2-Trichloroethane 2985 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Tetrachloroethylene 2987 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Chlorobenzene 2989 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Benzene 2990 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Toluene 2991 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Ethylbenzene 2992 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jan 21, 2004, sampling point TF080 | Styrene 2996 | Jan 1, 2004 – Mar 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Arsenic 1005 EPA method 200.8 | Not recorded |
| 0.04 mg/l , sample collected May 21, 2002, sampling point TF080 | Barium 1010 EPA method 200.8 | Not recorded |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Cadmium 1015 EPA method 200.8 | Not recorded |
| 0.001 mg/l , sample collected May 21, 2002, sampling point TF080 | Chromium 1020 EPA method 200.8 | Not recorded |
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Fluoride 1025 EPA method 300.0 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Mercury 1035 EPA method 200.8 | Not recorded |
| 0.001 mg/l , sample collected May 21, 2002, sampling point TF080 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Selenium 1045 EPA method 200.8 | Not recorded |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Antimony, Total 1074 EPA method 200.8 | Not recorded |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Beryllium, Total 1075 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 21, 2002, sampling point TF080 | Thallium, Total 1085 EPA method 200.8 | Not recorded |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected May 7, 2002, sampling point TF080 | Cyanide 1024 EPA method 335.4 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| 1.027 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Copper, Free 1022 | Not recorded |
| 0.001 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Lead 1030 | Not recorded |
|
||
| 1.196 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Copper, Free 1022 | Not recorded |
| 0.004 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Lead 1030 | Not recorded |
|
||
| 0.118 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Copper, Free 1022 | Not recorded |
| 0.003 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Lead 1030 | Not recorded |
|
||
| 0.092 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Copper, Free 1022 | Not recorded |
| 0.003 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Lead 1030 | Not recorded |
|
||
| 0.605 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Copper, Free 1022 | Not recorded |
| 0.002 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Lead 1030 | Not recorded |
|
||
| 0.106 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Copper, Free 1022 | Not recorded |
| 0.002 mg/l , sample collected Jun 12, 2000, sampling point LC0019 | Lead 1030 | Not recorded |
-
- Collected
- Feb 4, 2004
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- 040205-017IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.045 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Jan 21, 2004
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- 040122-067VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Mar 31, 2004
-
1,2,4-Trichlorobenzene 2378
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- May 21, 2002
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- 020522-021IN
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Barium 1010 EPA method 200.8
- Result
- 0.04 mg/l
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
-
Chromium 1020 EPA method 200.8
- Result
- 0.001 mg/l
-
Fluoride 1025 EPA method 300.0
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Nickel 1036 EPA method 200.8
- Result
- 0.001 mg/l
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- May 7, 2002
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- 020508-005CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method 335.4
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Jun 12, 2000
- Sampling point
- LC0019 Location withheld
- Sample type
- Routine
- Lab sample
- 000613-020L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 1.027 mg/l
-
Lead 1030
- Result
- 0.001 mg/l
-
- Collected
- Jun 12, 2000
- Sampling point
- LC0019 Location withheld
- Sample type
- Routine
- Lab sample
- 000613-019L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 1.196 mg/l
-
Lead 1030
- Result
- 0.004 mg/l
-
- Collected
- Jun 12, 2000
- Sampling point
- LC0019 Location withheld
- Sample type
- Routine
- Lab sample
- 000613-018L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.118 mg/l
-
Lead 1030
- Result
- 0.003 mg/l
-
- Collected
- Jun 12, 2000
- Sampling point
- LC0019 Location withheld
- Sample type
- Routine
- Lab sample
- 000613-017L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.092 mg/l
-
Lead 1030
- Result
- 0.003 mg/l
-
- Collected
- Jun 12, 2000
- Sampling point
- LC0019 Location withheld
- Sample type
- Routine
- Lab sample
- 000613-016L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.605 mg/l
-
Lead 1030
- Result
- 0.002 mg/l
-
- Collected
- Jun 12, 2000
- Sampling point
- LC0019 Location withheld
- Sample type
- Routine
- Lab sample
- 000613-015L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.106 mg/l
-
Lead 1030
- Result
- 0.002 mg/l
Routine (10).