Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Chemical and radiological sample results

MS0190008 , FCWA - Oldenburg

32 of the 71 analytes this system has been tested for have been detected at least once, across 261 samples on record.

The other 39 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 261 samples on record, detections range from September 15, 1993 to June 9, 2026. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for FCWA - Oldenburg, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 120 of 142 results Sep 15, 1993 Jun 4, 2025
Lead 1030 Inorganic Chemical 90 of 142 results Sep 15, 1993 Jun 4, 2025
TTHM 2950 Organic Chemical 29 of 29 results May 26, 2004 Jun 9, 2026
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 27 of 27 results May 26, 2004 Oct 3, 2025
Chloroform 2941 Organic Chemical 22 of 22 results Sep 11, 2006 Jun 9, 2026
Bromodichloromethane 2943 Organic Chemical 21 of 22 results Sep 11, 2006 Jun 9, 2026
Dichloroacetic Acid 2451 Organic Chemical 19 of 19 results Jun 30, 2008 Oct 3, 2025
Trichloroacetic Acid 2452 Organic Chemical 19 of 19 results Jun 30, 2008 Oct 3, 2025
Fluoride 1025 Inorganic Chemical 13 of 13 results May 21, 2002 Feb 4, 2025
Barium 1010 Inorganic Chemical 12 of 12 results May 21, 2002 Feb 4, 2025
Dibromochloromethane 2944 Organic Chemical 9 of 22 results Sep 11, 2006 Jun 9, 2026
Chromium 1020 Inorganic Chemical 6 of 12 results May 21, 2002 Feb 4, 2025
Sodium 1052 Inorganic Chemical 4 of 4 results Mar 21, 2017 Jan 29, 2024
Monochloroacetic Acid 2450 Organic Chemical 4 of 19 results May 11, 2009 Dec 17, 2019
Sulfate 1055 Inorganic Chemical 3 of 3 results May 21, 2002 Mar 21, 2017
Nickel 1036 Inorganic Chemical 3 of 12 results Jan 30, 2006 Apr 14, 2014
Dibromoacetic Acid 2454 Organic Chemical 2 of 19 results Aug 17, 2009 Aug 17, 2009
Monobromoacetic Acid 2453 Organic Chemical 1 of 19 results Dec 15, 2020 Dec 15, 2020
Calcium 1016 Inorganic Chemical 1 of 1 result Mar 21, 2017 Mar 21, 2017
Chloride 1017 Inorganic Chemical 1 of 1 result Mar 21, 2017 Mar 21, 2017
Iron 1028 Inorganic Chemical 1 of 1 result Mar 21, 2017 Mar 21, 2017
Magnesium 1031 Inorganic Chemical 1 of 1 result Mar 21, 2017 Mar 21, 2017
Manganese 1032 Inorganic Chemical 1 of 1 result Mar 21, 2017 Mar 21, 2017
Potassium 1042 Inorganic Chemical 1 of 1 result Mar 21, 2017 Mar 21, 2017
Residue, Total, Filterable 1057 Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
Alkalinity, Caco3 Stability 1067 Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
Color 1905 Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
Hardness, Total (As Caco3) 1915 Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
Alkalinity, Total 1927 Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
Calculated Sodium NACA Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
PH, Field Result PHFD Water Quality 1 of 1 result Mar 21, 2017 Mar 21, 2017
Selenium 1045 Inorganic Chemical 1 of 12 results Feb 28, 2005 Feb 28, 2005

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 111–120 of 261 samples, newest first — collected July 12, 2011 to July 9, 2012. The summary above covers all 261.

37 results from the 10 samples listed here: 7 detected, 30 not detected. Across the whole record it is 418 of 969. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for FCWA - Oldenburg, every result from 111 to 120 of 261 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Jul 9, 2012 12:13
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
120710-009HA
Laboratory
MSDH Lab
Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 12:13, sampling point MRT000 Monochloroacetic Acid 2450 EPA method 552.2 Not recorded
0.019 mg/l , sample collected Jul 9, 2012 12:13, sampling point MRT000 Dichloroacetic Acid 2451 EPA method 552.2 Not recorded
0.018 mg/l , sample collected Jul 9, 2012 12:13, sampling point MRT000 Trichloroacetic Acid 2452 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 12:13, sampling point MRT000 Monobromoacetic Acid 2453 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 12:13, sampling point MRT000 Dibromoacetic Acid 2454 EPA method 552.2 Not recorded
0.037 mg/l , sample collected Jul 9, 2012 12:13, sampling point MRT000 Total Haloacetic Acids (Haa5) 2456 Jan 1, 2011 – Dec 31, 2013
Collected
Apr 17, 2012 14:27
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
120418-036
Laboratory
Radiation Safety Engineering
Not detected below 0.34 pci/l Minimum Reporting Level , sample collected Apr 17, 2012 14:27, sampling point TF101 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.35 pci/l Minimum Reporting Level , sample collected Apr 17, 2012 14:27, sampling point TF101 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.246 pci/l Minimum Reporting Level , sample collected Apr 17, 2012 14:27, sampling point TF101 Radium-226 4020 EPA method 903.1 Apr 1, 2012 – Jun 30, 2012
Not detected below 0.35 pci/l Minimum Reporting Level , sample collected Apr 17, 2012 14:27, sampling point TF101 Radium-228 4030 EPA method 904.0 Apr 1, 2012 – Jun 30, 2012
Collected
Apr 17, 2012 14:27
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
120418-036RU
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 17, 2012 14:27, sampling point TF101 Combined Uranium 4006 EPA method 200.8 Apr 1, 2012 – Jun 30, 2012
Collected
Feb 14, 2012 11:30
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
120215-003
Laboratory
Radiation Safety Engineering
Not detected below 0.34 pci/l Minimum Reporting Level , sample collected Feb 14, 2012 11:30, sampling point TF101 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.35 pci/l Minimum Reporting Level , sample collected Feb 14, 2012 11:30, sampling point TF101 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.246 pci/l Minimum Reporting Level , sample collected Feb 14, 2012 11:30, sampling point TF101 Radium-226 4020 EPA method 903.1 Jan 1, 2012 – Mar 31, 2012
Not detected below 0.35 pci/l Minimum Reporting Level , sample collected Feb 14, 2012 11:30, sampling point TF101 Radium-228 4030 EPA method 904.0 Jan 1, 2012 – Mar 31, 2012
Collected
Feb 14, 2012 11:30
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
120215-003RU
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 14, 2012 11:30, sampling point TF101 Combined Uranium 4006 EPA method 200.8 Jan 1, 2012 – Mar 31, 2012
Collected
Jan 30, 2012 01:18
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
120131-029NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jan 30, 2012 01:18, sampling point TF101 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2012 – Dec 31, 2012
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jan 30, 2012 01:18, sampling point TF101 Nitrate 1040 EPA method 353.2 Jan 1, 2012 – Dec 31, 2012
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jan 30, 2012 01:18, sampling point TF101 Nitrite 1041 EPA method 353.2 Jan 1, 2012 – Dec 31, 2012
Collected
Dec 12, 2011 13:23
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
111213-016
Laboratory
Radiation Safety Engineering
Not detected below 0.34 pci/l Minimum Reporting Level , sample collected Dec 12, 2011 13:23, sampling point TF101 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.35 pci/l Minimum Reporting Level , sample collected Dec 12, 2011 13:23, sampling point TF101 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.246 pci/l Minimum Reporting Level , sample collected Dec 12, 2011 13:23, sampling point TF101 Radium-226 4020 EPA method 903.1 Oct 1, 2011 – Dec 31, 2011
Not detected below 0.35 pci/l Minimum Reporting Level , sample collected Dec 12, 2011 13:23, sampling point TF101 Radium-228 4030 EPA method 904.0 Oct 1, 2011 – Dec 31, 2011
Collected
Sep 12, 2011 02:41
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
110913-035CN
Laboratory
MSDH Lab
Not detected below 15 ug/l Minimum Reporting Level , sample collected Sep 12, 2011 02:41, sampling point TF101 Cyanide 1024 EPA method QC10204001X Jan 1, 2011 – Dec 31, 2013
Collected
Aug 1, 2011 03:30
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
110802-020IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Arsenic 1005 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
0.002333 mg/l , sample collected Aug 1, 2011 03:30, sampling point TF101 Barium 1010 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Cadmium 1015 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Chromium 1020 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
0.309 mg/l , sample collected Aug 1, 2011 03:30, sampling point TF101 Fluoride 1025 EPA method 380-75WE Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Mercury 1035 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Selenium 1045 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Antimony, Total 1074 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 03:30, sampling point TF101 Thallium, Total 1085 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Collected
Jul 12, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110713-070PB
Laboratory
MSDH Lab
0.1695 mg/l , sample collected Jul 12, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
0.0019 mg/l , sample collected Jul 12, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011

Routine (10).