Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0220002 , G T & Y Water District Inc

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for G T & Y Water District Inc, 32 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2025 – Dec 31, 2025 20 0.564 mg/l DS000 Accepted
Lead Jan 1, 2025 – Dec 31, 2025 20 0.0009 mg/l DS000 Accepted
Copper Jan 1, 2024 – Dec 31, 2024 20 0.894 mg/l DS000 Accepted
Lead Jan 1, 2024 – Dec 31, 2024 20 0.0022 mg/l DS000 Accepted
Copper Jan 1, 2023 – Dec 31, 2023 20 0.638 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2023 20 0.0018 mg/l DS000 Accepted
Copper Jan 1, 2021 – Dec 31, 2023 18 0.51 mg/l DS000 Accepted
Lead Jan 1, 2021 – Dec 31, 2023 18 0.0015 mg/l DS000 Accepted
Copper Jan 1, 2020 – Dec 31, 2022 18 0.51 mg/l DS000 Accepted
Lead Jan 1, 2020 – Dec 31, 2022 18 0.0015 mg/l DS000 Accepted
Copper Jan 1, 2018 – Dec 31, 2020 20 0.7749 mg/l DS000 Accepted
Lead Jan 1, 2018 – Dec 31, 2020 20 0.0018 mg/l DS000 Accepted
Copper Jan 1, 2017 – Dec 31, 2019 20 0.7749 mg/l DS000 Accepted
Lead Jan 1, 2017 – Dec 31, 2019 20 0.0018 mg/l DS000 Accepted
Copper Jan 1, 2015 – Dec 31, 2017 20 0.7847 mg/l DS000 Accepted
Lead Jan 1, 2015 – Dec 31, 2017 20 0.0048 mg/l DS000 Accepted
Copper Jan 1, 2012 – Dec 31, 2014 20 0.9795 mg/l DS000 Accepted
Lead Jan 1, 2012 – Dec 31, 2014 20 0.0064 mg/l DS000 Accepted
Copper Jan 1, 2009 – Dec 31, 2011 20 0.558 mg/l DS000 Accepted
Lead Jan 1, 2009 – Dec 31, 2011 20 0.0031 mg/l DS000 Accepted
Copper Jan 1, 2006 – Dec 31, 2008 20 0.5741 mg/l DS000 Accepted
Lead Jan 1, 2006 – Dec 31, 2008 20 0.005 mg/l DS000 Accepted
Copper Jan 1, 2000 – Dec 31, 2002 10 0.441 mg/l DS000 Accepted
Lead Jan 1, 2000 – Dec 31, 2002 10 0.003 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1996 10 0.711 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1996 10 0.003 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 10 0.487 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 10 0.004 mg/l DS000 Accepted
Copper Jan 1, 1994 – Jun 30, 1994 30 1.063 mg/l DS000 Accepted
Lead Jan 1, 1994 – Jun 30, 1994 30 0.005 mg/l DS000 Accepted
Copper Jul 1, 1993 – Dec 31, 1993 20 0.892 mg/l DS000 Accepted
Lead Jul 1, 1993 – Dec 31, 1993 20 0.006 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.