This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0220004 , Grenada-Bogue Basin/Holcomb
25 of the 56 analytes this system has been tested for have been detected at least once, across 351 samples on record.
The other 31 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 351 samples on record, detections range from September 16, 1993 to September 30, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 123 of 140 results | Sep 16, 1993 | Sep 30, 2025 |
| Lead 1030 | Inorganic Chemical | 70 of 140 results | Sep 16, 1993 | Sep 30, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 20 of 22 results | May 26, 2004 | Sep 25, 2025 |
| TTHM 2950 | Organic Chemical | 20 of 20 results | May 26, 2004 | Sep 25, 2025 |
| Barium 1010 | Inorganic Chemical | 20 of 20 results | Jun 18, 2002 | Feb 3, 2025 |
| Fluoride 1025 | Inorganic Chemical | 19 of 20 results | Jun 18, 2002 | Feb 3, 2025 |
| Dichloroacetic Acid 2451 | Organic Chemical | 16 of 16 results | Sep 16, 2008 | Sep 25, 2025 |
| Chloroform 2941 | Organic Chemical | 15 of 15 results | Jul 31, 2007 | Sep 25, 2025 |
| Bromodichloromethane 2943 | Organic Chemical | 14 of 15 results | Jul 31, 2007 | Sep 25, 2025 |
| Chromium 1020 | Inorganic Chemical | 14 of 20 results | Jun 18, 2002 | Feb 3, 2025 |
| Trichloroacetic Acid 2452 | Organic Chemical | 13 of 16 results | Sep 16, 2008 | Sep 25, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 9 of 15 results | Jul 31, 2007 | Sep 25, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 7 of 16 results | Sep 10, 2014 | May 13, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 10 results | Dec 5, 2011 | Jul 12, 2012 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 5 of 10 results | Dec 5, 2011 | Jul 12, 2012 |
| Radium-226 4020 | Radionuclide | 5 of 10 results | Dec 5, 2011 | Jul 12, 2012 |
| Bromoform 2942 | Organic Chemical | 4 of 15 results | Jul 31, 2007 | May 13, 2025 |
| Nickel 1036 | Inorganic Chemical | 4 of 20 results | Apr 2, 2008 | Apr 7, 2014 |
| Selenium 1045 | Inorganic Chemical | 4 of 20 results | Feb 4, 2004 | Apr 2, 2008 |
| Cyanide 1024 | Inorganic Chemical | 2 of 20 results | May 17, 2021 | Jun 17, 2025 |
| Monochloroacetic Acid 2450 | Organic Chemical | 2 of 16 results | Sep 10, 2014 | Aug 26, 2020 |
| Arsenic 1005 | Inorganic Chemical | 2 of 20 results | Apr 2, 2008 | Apr 2, 2008 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 76 results | Jun 1, 2009 | Jun 1, 2009 |
| Cadmium 1015 | Inorganic Chemical | 1 of 20 results | Feb 28, 2005 | Feb 28, 2005 |
| Carbon Tetrachloride 2982 | Organic Chemical | 1 of 76 results | Jul 20, 2004 | Jul 20, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 191–200 of 351 samples, newest first — collected July 12, 2011 to February 1, 2012. The summary above covers all 351.
41 results from the 10 samples listed here: 13 detected, 28 not detected. Across the whole record it is 396 of 2,484. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 1, 2012 12:32, sampling point TF101 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 1, 2012 12:32, sampling point TF101 | Nitrate 1040 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 1, 2012 12:32, sampling point TF101 | Nitrite 1041 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
|
||
| 0.6 pci/l , sample collected Dec 5, 2011 12:05, sampling point TF103 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.23 pci/l Minimum Reporting Level , sample collected Dec 5, 2011 12:05, sampling point TF103 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.196 pci/l Minimum Reporting Level , sample collected Dec 5, 2011 12:05, sampling point TF103 | Radium-226 4020 EPA method 903.1 | Oct 1, 2011 – Dec 31, 2011 |
| Not detected below 0.23 pci/l Minimum Reporting Level , sample collected Dec 5, 2011 12:05, sampling point TF103 | Radium-228 4030 EPA method 904.0 | Oct 1, 2011 – Dec 31, 2011 |
|
||
| Not detected below 0.34 pci/l Minimum Reporting Level , sample collected Dec 5, 2011 12:28, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| 0.3 pci/l , sample collected Dec 5, 2011 12:28, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| 0.3 pci/l , sample collected Dec 5, 2011 12:28, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Oct 1, 2011 – Dec 31, 2011 |
| Not detected below 0.2 pci/l Minimum Reporting Level , sample collected Dec 5, 2011 12:28, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Oct 1, 2011 – Dec 31, 2011 |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected Sep 12, 2011 12:05, sampling point TF103 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2011 – Dec 31, 2013 |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected Sep 12, 2011 12:15, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2011 – Dec 31, 2013 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.020152 mg/l , sample collected Aug 1, 2011 12:15, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.001112 mg/l , sample collected Aug 1, 2011 12:15, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.182 mg/l , sample collected Aug 1, 2011 12:15, sampling point TF101 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:15, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.018731 mg/l , sample collected Aug 1, 2011 12:05, sampling point TF103 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.002355 mg/l , sample collected Aug 1, 2011 12:05, sampling point TF103 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.186 mg/l , sample collected Aug 1, 2011 12:05, sampling point TF103 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2011 12:05, sampling point TF103 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.2339 mg/l , sample collected Jul 12, 2011, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2009 – Dec 31, 2011 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 12, 2011, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2009 – Dec 31, 2011 |
|
||
| 0.0065 mg/l , sample collected Jul 12, 2011, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2009 – Dec 31, 2011 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 12, 2011, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2009 – Dec 31, 2011 |
|
||
| 0.1087 mg/l , sample collected Jul 12, 2011, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2009 – Dec 31, 2011 |
| 0.0012 mg/l , sample collected Jul 12, 2011, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2009 – Dec 31, 2011 |
-
- Collected
- Feb 1, 2012 12:32
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120202-048NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2012 – Dec 31, 2012
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Dec 5, 2011 12:05
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 111206-020
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.6 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.23 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.196 pci/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2011 – Dec 31, 2011
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.23 pci/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2011 – Dec 31, 2011
-
- Collected
- Dec 5, 2011 12:28
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 111206-052
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- Not detected below 0.34 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- 0.3 pci/l
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- 0.3 pci/l
- Monitoring period
- Oct 1, 2011 – Dec 31, 2011
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.2 pci/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2011 – Dec 31, 2011
-
- Collected
- Sep 12, 2011 12:05
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 110913-031CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- Sep 12, 2011 12:15
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 110913-028CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- Aug 1, 2011 12:15
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 110802-029IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.020152 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- 0.001112 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.182 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- Aug 1, 2011 12:05
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 110802-028IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.018731 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- 0.002355 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.186 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- Jul 12, 2011
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 110713-119PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2011
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.2339 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jul 12, 2011
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 110713-123PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2011
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0065 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jul 12, 2011
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 110713-122PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2011
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1087 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0012 mg/l
Routine (10).