Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Summarized field sample results

MS0250008 , City of Jackson , Treatment Facility TF082 (Curtis Conven)

51–78 of 78 summaries on record for this facility, latest period first.

No date range is applied: this list draws on every summary on record. Show the last two years only.

Summarized field sample results for Treatment Facility TF082 (Curtis Conven), 51 to 78 of 78 summaries shown, latest period first.
Monitoring period Analyte Summary type Samples exceeded % exceeded Period average Running annual average M&R complied Level complied Assessed against
Oct 1, 2007 to Oct 31, 2007 Turbidity
0100
CFE Maximum Turbidity 0 0.000 0 0 YES in compliance Yes Maximum 1 ntu
Oct 1, 2007 to Oct 31, 2007 Turbidity
0100
CFE 95% Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Oct 1, 2007 to Oct 31, 2007 Turbidity
0100
Individual Filter Effluent Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Oct 1, 2007 to Oct 31, 2007 Chloramine
1006
Entry Point RDC 0 0.000 0 0 YES in compliance Yes Minimum .2 mg/l
Oct 1, 2007 to Oct 31, 2007 Chlorine Dioxide
1008
EP Chlorine Dioxide 0 0.000 0 0 YES in compliance Yes Maximum 0.8 mg/l
Oct 1, 2007 to Oct 31, 2007 Chlorite
1009
EP Chlorite 0 0.000 0 0 YES in compliance Yes Maximum 1.0 mg/l
Sep 1, 2007 to Sep 30, 2007 Turbidity
0100
CFE Maximum Turbidity 0 0.000 0 0 YES in compliance Yes Maximum 1 ntu
Sep 1, 2007 to Sep 30, 2007 Turbidity
0100
CFE 95% Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Sep 1, 2007 to Sep 30, 2007 Turbidity
0100
Individual Filter Effluent Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Sep 1, 2007 to Sep 30, 2007 Chloramine
1006
Entry Point RDC 0 0.000 0 0 YES in compliance Yes Minimum .2 mg/l
Sep 1, 2007 to Sep 30, 2007 Chlorine Dioxide
1008
EP Chlorine Dioxide 0 0.000 0 0 YES in compliance Yes Maximum 0.8 mg/l
Sep 1, 2007 to Sep 30, 2007 Chlorite
1009
EP Chlorite 0 0.000 0 0 YES in compliance Yes Maximum 1.0 mg/l
Aug 1, 2007 to Aug 31, 2007 Turbidity
0100
CFE Maximum Turbidity 0 0.000 0 0 YES in compliance Yes Maximum 1 ntu
Aug 1, 2007 to Aug 31, 2007 Turbidity
0100
CFE 95% Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Aug 1, 2007 to Aug 31, 2007 Turbidity
0100
Individual Filter Effluent Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Aug 1, 2007 to Aug 31, 2007 Chloramine
1006
Entry Point RDC 0 0.000 0 0 YES in compliance Yes Minimum .2 mg/l
Aug 1, 2007 to Aug 31, 2007 Chlorine Dioxide
1008
EP Chlorine Dioxide 0 0.000 0 0 YES in compliance Yes Maximum 0.8 mg/l
Aug 1, 2007 to Aug 31, 2007 Chlorine Dioxide
1008
EP Chlorine Dioxide 0 0.000 0 0 YES in compliance Yes Maximum 0.8 mg/l
Aug 1, 2007 to Aug 31, 2007 Chlorite
1009
EP Chlorite 0 0.000 0 0 YES in compliance Yes Maximum 1.0 mg/l
Aug 1, 2007 to Aug 31, 2007 Chlorite
1009
EP Chlorite 0 0.000 0 0 YES in compliance Yes Maximum 1.0 mg/l
Jul 1, 2007 to Jul 31, 2007 Turbidity
0100
CFE Maximum Turbidity 0 0.000 0 0 YES in compliance Yes Maximum 1 ntu
Jul 1, 2007 to Jul 31, 2007 Turbidity
0100
CFE 95% Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Jul 1, 2007 to Jul 31, 2007 Turbidity
0100
Individual Filter Effluent Turbidity 0 0.000 0 0 YES in compliance Yes 95 Percent 0.3 ntu
Jul 1, 2007 to Jul 31, 2007 Chloramine
1006
Entry Point RDC 0 0.000 0 0 YES in compliance Yes Minimum .2 mg/l
Jul 1, 2007 to Jul 31, 2007 Chlorine Dioxide
1008
EP Chlorine Dioxide 0 0.000 0 0 YES in compliance Yes Maximum 0.8 mg/l
Jul 1, 2007 to Jul 31, 2007 Chlorine Dioxide
1008
EP Chlorine Dioxide 0 0.000 0 0 YES in compliance Yes Maximum 0.8 mg/l
Jul 1, 2007 to Jul 31, 2007 Chlorite
1009
EP Chlorite 0 0.000 0 0 YES in compliance Yes Maximum 1.0 mg/l
Jul 1, 2007 to Jul 31, 2007 Chlorite
1009
EP Chlorite 0 0.000 0 0 YES in compliance Yes Maximum 1.0 mg/l

How to read these columns

M&R complied is not a yes-or-no column. The agency records three values: Yes, in compliance, No-Major Violation and No-Minor Violation. Level complied is yes or no.

Samples exceeded counts samples on the wrong side of the designated level in either direction: where that level is a minimum, it counts samples below it. “Exceeded” is the agency’s word for both cases.

Assessed against is the designated level this period was measured against, from the levels on this facility’s record.