This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0250025 , Town of Terry
26 of the 57 analytes this system has been tested for have been detected at least once, across 351 samples on record.
The other 31 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 351 samples on record, detections range from October 5, 1993 to December 17, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 107 of 125 results | Oct 5, 1993 | Jul 11, 2023 |
| Lead 1030 | Inorganic Chemical | 98 of 125 results | Oct 5, 1993 | Jul 11, 2023 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 42 of 46 results | Sep 15, 2004 | Apr 29, 2025 |
| TTHM 2950 | Organic Chemical | 39 of 43 results | Sep 15, 2004 | May 17, 2023 |
| Chloroform 2941 | Organic Chemical | 27 of 27 results | May 17, 2006 | Jul 25, 2017 |
| Bromodichloromethane 2943 | Organic Chemical | 23 of 27 results | May 17, 2006 | Jul 25, 2017 |
| Dichloroacetic Acid 2451 | Organic Chemical | 20 of 22 results | Jan 29, 2008 | Jul 25, 2017 |
| Trichloroacetic Acid 2452 | Organic Chemical | 20 of 22 results | Jan 29, 2008 | Jul 25, 2017 |
| Barium 1010 | Inorganic Chemical | 18 of 18 results | Sep 29, 2003 | Feb 13, 2025 |
| Fluoride 1025 | Inorganic Chemical | 18 of 18 results | Sep 29, 2003 | Feb 13, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 15 of 27 results | May 17, 2006 | Jul 25, 2017 |
| Chromium 1020 | Inorganic Chemical | 14 of 18 results | Sep 29, 2003 | Feb 13, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 10 of 10 results | Mar 5, 2012 | Oct 18, 2012 |
| Nickel 1036 | Inorganic Chemical | 8 of 18 results | Sep 29, 2003 | Feb 13, 2025 |
| Monochloroacetic Acid 2450 | Organic Chemical | 8 of 22 results | Jan 29, 2008 | Jul 25, 2017 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 6 of 41 results | Feb 14, 2018 | Feb 13, 2025 |
| Nitrate 1040 | Inorganic Chemical | 6 of 41 results | Feb 14, 2018 | Feb 13, 2025 |
| Sodium 1052 | Inorganic Chemical | 5 of 5 results | Sep 25, 2019 | Dec 17, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 4 of 22 results | Oct 28, 2008 | Jul 9, 2014 |
| Nitrite 1041 | Inorganic Chemical | 3 of 41 results | Feb 14, 2018 | Dec 1, 2021 |
| Monobromoacetic Acid 2453 | Organic Chemical | 3 of 22 results | Aug 12, 2009 | Nov 4, 2009 |
| Sulfate 1055 | Inorganic Chemical | 3 of 3 results | Sep 29, 2003 | Feb 11, 2004 |
| Cadmium 1015 | Inorganic Chemical | 2 of 18 results | Sep 29, 2003 | Mar 16, 2005 |
| Cyanide 1024 | Inorganic Chemical | 1 of 16 results | Feb 26, 2014 | Feb 26, 2014 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 39 results | Jun 23, 2010 | Jun 23, 2010 |
| Selenium 1045 | Inorganic Chemical | 1 of 18 results | Mar 16, 2005 | Mar 16, 2005 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 61–70 of 351 samples, newest first — collected April 21, 2020 to September 29, 2020. The summary above covers all 351.
47 results from the 10 samples listed here: 16 detected, 31 not detected. Across the whole record it is 502 of 1,770. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0454 mg/l , sample collected Sep 29, 2020 04:45, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0012 mg/l , sample collected Sep 29, 2020 04:45, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.089 mg/l , sample collected Sep 29, 2020 09:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0007 mg/l , sample collected Sep 29, 2020 09:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0095 mg/l , sample collected Sep 29, 2020 06:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 29, 2020 06:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0675 mg/l , sample collected Sep 29, 2020 09:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0018 mg/l , sample collected Sep 29, 2020 09:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.1086 mg/l , sample collected Sep 29, 2020 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0026 mg/l , sample collected Sep 29, 2020 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0879 mg/l , sample collected Sep 29, 2020, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0026 mg/l , sample collected Sep 29, 2020, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.6662 mg/l , sample collected Sep 29, 2020 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0028 mg/l , sample collected Sep 29, 2020 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Apr 29, 2020 13:00, sampling point TF103 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2018 – Dec 31, 2020 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Arsenic 1005 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0049 mg/l , sample collected Apr 21, 2020 12:10, sampling point TF103 | Barium 1010 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Cadmium 1015 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0018 mg/l , sample collected Apr 21, 2020 12:10, sampling point TF103 | Chromium 1020 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.236 mg/l , sample collected Apr 21, 2020 12:10, sampling point TF103 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Mercury 1035 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Selenium 1045 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 21, 2020 12:10, sampling point TF103 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Benzene 2990 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Toluene 2991 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Apr 21, 2020 12:35, sampling point TF103 | Styrene 2996 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2020 |
-
- Collected
- Sep 29, 2020 04:45
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-018PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0454 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0012 mg/l
-
- Collected
- Sep 29, 2020 09:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-017PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.089 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0007 mg/l
-
- Collected
- Sep 29, 2020 06:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-016PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0095 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Sep 29, 2020 09:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-015PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0675 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0018 mg/l
-
- Collected
- Sep 29, 2020 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-013PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1086 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0026 mg/l
-
- Collected
- Sep 29, 2020
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-012PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0879 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0026 mg/l
-
- Collected
- Sep 29, 2020 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200930-011PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.6662 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0028 mg/l
-
- Collected
- Apr 29, 2020 13:00
- Sampling point
- TF103 Treatment Plant 103
- Sample type
- Routine
- Lab sample
- 200430-011CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Apr 21, 2020 12:10
- Sampling point
- TF103 Treatment Plant 103
- Sample type
- Routine
- Lab sample
- 200422-003IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Barium 1010 EPA method 200.8
- Result
- 0.0049 mg/l
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Chromium 1020 EPA method 200.8
- Result
- 0.0018 mg/l
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.236 mg/l
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
- Collected
- Apr 21, 2020 12:35
- Sampling point
- TF103 Treatment Plant 103
- Sample type
- Routine
- Lab sample
- 200422-014VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2020
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
Routine (10).