This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0260005 , Town of Cruger
21 of the 57 analytes this system has been tested for have been detected at least once, across 193 samples on record.
The other 36 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 193 samples on record, detections range from May 10, 1994 to May 13, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 53 of 99 results | May 10, 1994 | Sep 17, 2024 |
| Lead 1030 | Inorganic Chemical | 52 of 99 results | May 10, 1994 | Sep 28, 2021 |
| Barium 1010 | Inorganic Chemical | 10 of 10 results | Sep 17, 2003 | May 13, 2025 |
| Fluoride 1025 | Inorganic Chemical | 8 of 10 results | Sep 17, 2003 | May 18, 2022 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 7 of 7 results | Jun 7, 2004 | May 13, 2025 |
| Chromium 1020 | Inorganic Chemical | 6 of 10 results | Sep 17, 2003 | May 13, 2025 |
| TTHM 2950 | Organic Chemical | 6 of 7 results | Jun 7, 2004 | May 13, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 5 results | Dec 15, 2011 | Jul 13, 2012 |
| Nickel 1036 | Inorganic Chemical | 4 of 10 results | Mar 14, 2005 | May 13, 2025 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 29, 2019 | Feb 7, 2024 |
| Dichloroacetic Acid 2451 | Organic Chemical | 2 of 2 results | Sep 26, 2011 | Jul 9, 2014 |
| Trichloroacetic Acid 2452 | Organic Chemical | 2 of 2 results | Sep 26, 2011 | Jul 9, 2014 |
| Chloroform 2941 | Organic Chemical | 2 of 3 results | Sep 20, 2006 | Jul 9, 2014 |
| Bromodichloromethane 2943 | Organic Chemical | 2 of 3 results | Sep 20, 2006 | Jul 9, 2014 |
| Xylenes, Total 2955 | Organic Chemical | 2 of 25 results | Apr 15, 2009 | Sep 27, 2012 |
| Selenium 1045 | Inorganic Chemical | 2 of 10 results | Mar 14, 2005 | Feb 6, 2006 |
| Sulfate 1055 | Inorganic Chemical | 2 of 2 results | Sep 17, 2003 | Feb 9, 2004 |
| Styrene 2996 | Organic Chemical | 1 of 25 results | Nov 8, 2012 | Nov 8, 2012 |
| Carbon Tetrachloride 2982 | Organic Chemical | 1 of 25 results | Sep 27, 2012 | Sep 27, 2012 |
| Nitrite 1041 | Inorganic Chemical | 1 of 23 results | Jun 23, 2008 | Jun 23, 2008 |
| Cadmium 1015 | Inorganic Chemical | 1 of 10 results | Feb 6, 2006 | Feb 6, 2006 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 121–130 of 193 samples, newest first — collected June 19, 2000 to February 9, 2004. The summary above covers all 193.
47 results from the 10 samples listed here: 13 detected, 34 not detected. Across the whole record it is 172 of 978. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Feb 9, 2004, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.003 mg/l , sample collected Sep 17, 2003, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.003 mg/l , sample collected Sep 17, 2003, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.116 mg/l , sample collected Sep 17, 2003, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 6.21 mg/l , sample collected Sep 17, 2003, sampling point TF101 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 17, 2003, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Xylenes, Total 2955 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Dichloromethane 2964 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | O-Dichlorobenzene 2968 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | P-Dichlorobenzene 2969 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Vinyl Chloride 2976 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | 1,1-Dichloroethylene 2977 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | 1,2-Dichloroethane 2980 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | 1,1,1-Trichloroethane 2981 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Carbon Tetrachloride 2982 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | 1,2-Dichloropropane 2983 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Trichloroethylene 2984 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | 1,1,2-Trichloroethane 2985 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Tetrachloroethylene 2987 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Chlorobenzene 2989 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Benzene 2990 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Toluene 2991 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Ethylbenzene 2992 | Not recorded |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 23, 2002, sampling point TF101 | Styrene 2996 | Not recorded |
|
||
| 0.026 mg/l , sample collected Sep 14, 2000, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.002 mg/l , sample collected Sep 14, 2000, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.03 mg/l , sample collected Sep 14, 2000, sampling point DS000 | Copper, Free 1022 | Not recorded |
| Not detected below 0.001 mg/l Method Detection Limit , sample collected Sep 14, 2000, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.035 mg/l , sample collected Jun 19, 2000, sampling point DS000 | Copper, Free 1022 | Not recorded |
| Not detected below 0.001 mg/l Method Detection Limit , sample collected Jun 19, 2000, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.017 mg/l , sample collected Jun 19, 2000, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.001 mg/l , sample collected Jun 19, 2000, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.021 mg/l , sample collected Jun 19, 2000, sampling point DS000 | Copper, Free 1022 | Not recorded |
| 0.001 mg/l , sample collected Jun 19, 2000, sampling point DS000 | Lead 1030 | Not recorded |
|
||
| 0.169 mg/l , sample collected Jun 19, 2000, sampling point DS000 | Copper, Free 1022 | Not recorded |
| Not detected below 0.001 mg/l Method Detection Limit , sample collected Jun 19, 2000, sampling point DS000 | Lead 1030 | Not recorded |
-
- Collected
- Feb 9, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040210-002CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Sep 17, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 030918-037CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Sep 17, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 030918-021IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.003 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.003 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.116 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- 6.21 mg/l
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- May 23, 2002
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 020524-001VO
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
1,2,4-Trichlorobenzene 2378
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Sep 14, 2000
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 000915-007L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.026 mg/l
-
Lead 1030
- Result
- 0.002 mg/l
-
- Collected
- Sep 14, 2000
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 000915-006L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.03 mg/l
-
Lead 1030
- Result
- Not detected below 0.001 mg/l Method Detection Limit
-
- Collected
- Jun 19, 2000
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 000620-058L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.035 mg/l
-
Lead 1030
- Result
- Not detected below 0.001 mg/l Method Detection Limit
-
- Collected
- Jun 19, 2000
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 000620-057L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.017 mg/l
-
Lead 1030
- Result
- 0.001 mg/l
-
- Collected
- Jun 19, 2000
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 000620-056L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.021 mg/l
-
Lead 1030
- Result
- 0.001 mg/l
-
- Collected
- Jun 19, 2000
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 000620-055L
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Copper, Free 1022
- Result
- 0.169 mg/l
-
Lead 1030
- Result
- Not detected below 0.001 mg/l Method Detection Limit
Routine (10).