This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Lead and copper
MS0290010 , Town of Tremont
Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.
| Analyte | Monitoring period | Samples | 90th percentile | Facility | Data quality |
|---|---|---|---|---|---|
| Copper | Jan 1, 2026 – Dec 31, 2026 | 10 | 0.0027 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2026 – Dec 31, 2026 | 10 | 0 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2025 – Dec 31, 2025 | 10 | 0.0032 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2025 – Dec 31, 2025 | 10 | 0 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2024 – Dec 31, 2024 | 10 | 0.0029 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2024 – Dec 31, 2024 | 10 | 0 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2023 – Dec 31, 2023 | 10 | 0.0036 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2023 – Dec 31, 2023 | 10 | 0 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2022 – Dec 31, 2022 | 20 | 0.0035 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2022 – Dec 31, 2022 | 20 | 0 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2022 – Jun 30, 2022 | 20 | 0.0044 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2022 – Jun 30, 2022 | 20 | 0 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2021 – Dec 31, 2021 | 18 | 0.016 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2021 – Dec 31, 2021 | 18 | 0.0036 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2021 – Jun 30, 2021 | 20 | 0.33 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2021 – Jun 30, 2021 | 20 | 0.0008 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2020 – Jun 30, 2020 | 20 | 0.6745 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2020 – Jun 30, 2020 | 20 | 0.0038 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2016 – Dec 31, 2018 | 12 | 1.693 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2016 – Dec 31, 2018 | 12 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2013 – Dec 31, 2015 | 10 | 0.6626 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2013 – Dec 31, 2015 | 10 | 0.0017 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2012 – Dec 31, 2012 | 10 | 0.8456 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2012 – Dec 31, 2012 | 10 | 0.0024 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2011 – Dec 31, 2011 | 14 | 0.0966 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2011 – Dec 31, 2011 | 14 | 0.001 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2010 – Dec 31, 2010 | 10 | 0.0052 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2010 – Dec 31, 2010 | 10 | 0.0009 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2009 – Dec 31, 2009 | 20 | 0.1032 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2009 – Dec 31, 2009 | 20 | 0.0045 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2009 – Jun 30, 2009 | 20 | 0.0573 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2009 – Jun 30, 2009 | 20 | 0.0104 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2006 – Dec 31, 2008 | 50 | 1.5173 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2006 – Dec 31, 2008 | 50 | 0.0062 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2000 – Dec 31, 2002 | 10 | 0.852 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2000 – Dec 31, 2002 | 10 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1997 – Dec 31, 1999 | 10 | 0.497 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1997 – Dec 31, 1999 | 10 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1996 – Dec 31, 1996 | 10 | 0.812 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1996 – Dec 31, 1996 | 10 | 0.01 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1995 – Dec 31, 1995 | 10 | 0.937 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1995 – Dec 31, 1995 | 10 | 0.006 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1994 – Jun 30, 1994 | 20 | 0.482 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1994 – Jun 30, 1994 | 20 | 0.007 mg/l | DS000 | Accepted |
| Copper | Jul 1, 1993 – Dec 31, 1993 | 20 | 0.529 mg/l | DS000 | Accepted |
| Lead | Jul 1, 1993 – Dec 31, 1993 | 20 | 0.003 mg/l | DS000 | Accepted |
No date of receipt is recorded for any of these summaries.
What the 90th percentile is
The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.
From the help text published with these pages.