Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0300006 , City of Pascagoula

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for City of Pascagoula, 30 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2023 – Dec 31, 2025 30 0.179 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2025 30 0.0012 mg/l DS000 Accepted
Copper Jan 1, 2020 – Dec 31, 2022 30 0.167 mg/l DS000 Accepted
Lead Jan 1, 2020 – Dec 31, 2022 30 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2017 – Dec 31, 2019 32 0.1375 mg/l DS000 Accepted
Lead Jan 1, 2017 – Dec 31, 2019 32 0.0011 mg/l DS000 Accepted
Copper Jan 1, 2014 – Dec 31, 2016 30 0.261 mg/l DS000 Accepted
Lead Jan 1, 2014 – Dec 31, 2016 30 0.002 mg/l DS000 Accepted
Copper Jan 1, 2011 – Dec 31, 2013 31 0.219 mg/l DS000 Accepted
Lead Jan 1, 2011 – Dec 31, 2013 31 0.001 mg/l DS000 Accepted
Copper Jan 1, 2008 – Dec 31, 2010 31 0.4034 mg/l DS000 Accepted
Lead Jan 1, 2008 – Dec 31, 2010 31 0.002 mg/l DS000 Accepted
Copper Jan 1, 2005 – Dec 31, 2007 30 0.749 mg/l DS000 Accepted
Lead Jan 1, 2005 – Dec 31, 2007 30 0.004 mg/l DS000 Accepted
Copper Jan 1, 2004 – Jun 30, 2004 60 0.19 mg/l DS000 Accepted
Lead Jan 1, 2004 – Jun 30, 2004 60 0.008 mg/l DS000 Accepted
Copper Jul 1, 2002 – Dec 31, 2002 60 0.34 mg/l DS000 Accepted
Lead Jul 1, 2002 – Dec 31, 2002 60 0.007 mg/l DS000 Accepted
Copper Jan 1, 1999 – Dec 31, 2001 29 0.384 mg/l DS000 Accepted
Lead Jan 1, 1999 – Dec 31, 2001 29 0.079 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1998 30 0.396 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1998 30 0.015 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 30 0.88 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 30 0.007 mg/l DS000 Accepted
Copper Jan 1, 1994 – Dec 31, 1994 30 0.74 mg/l DS000 Accepted
Lead Jan 1, 1994 – Dec 31, 1994 30 0.008 mg/l DS000 Accepted
Copper Jan 1, 1993 – Jun 30, 1993 60 0.6 mg/l DS000 Accepted
Lead Jan 1, 1993 – Jun 30, 1993 60 0.007 mg/l DS000 Accepted
Copper Jul 1, 1992 – Dec 31, 1992 60 0.62 mg/l DS000 Accepted
Lead Jul 1, 1992 – Dec 31, 1992 60 0.009 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.