Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0300156 , West Jackson Co Utility Dist

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for West Jackson Co Utility Dist, 22 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2022 – Dec 31, 2024 30 0.133 mg/l DS000 Accepted
Lead Jan 1, 2022 – Dec 31, 2024 30 0.0026 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2021 30 0.142 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2021 30 0.0012 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2018 30 0.1991 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2018 30 0.0029 mg/l DS000 Accepted
Copper Jan 1, 2013 – Dec 31, 2015 30 0.1057 mg/l DS000 Accepted
Lead Jan 1, 2013 – Dec 31, 2015 30 0.0019 mg/l DS000 Accepted
Copper Jan 1, 2010 – Dec 31, 2012 30 0.0966 mg/l DS000 Accepted
Lead Jan 1, 2010 – Dec 31, 2012 30 0.0012 mg/l DS000 Accepted
Copper Jan 1, 2007 – Dec 31, 2009 21 0.0901 mg/l DS000 Accepted
Lead Jan 1, 2007 – Dec 31, 2009 21 0.0013 mg/l DS000 Accepted
Copper Jan 1, 2004 – Dec 31, 2006 11 0.0808 mg/l DS000 Accepted
Lead Jan 1, 2004 – Dec 31, 2006 11 0.0055 mg/l DS000 Accepted
Copper Jan 1, 2003 – Dec 31, 2003 10 0.117 mg/l DS000 Accepted
Lead Jan 1, 2003 – Dec 31, 2003 10 0.002 mg/l DS000 Accepted
Copper Jan 1, 2002 – Dec 31, 2002 10 0.129 mg/l DS000 Accepted
Lead Jan 1, 2002 – Dec 31, 2002 10 0.002 mg/l DS000 Accepted
Copper Jan 1, 2001 – Jun 30, 2001 5 0.002 mg/l DS000 Accepted
Lead Jan 1, 2001 – Jun 30, 2001 5 0 mg/l DS000 Accepted
Copper Jul 1, 2000 – Dec 31, 2000 5 0.004 mg/l DS000 Accepted
Lead Jul 1, 2000 – Dec 31, 2000 5 0.001 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.