Lead and copper

MS0300162 , Houston Estates Utility-Palmetto Pointe

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for Houston Estates Utility-Palmetto Pointe, 20 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2022 – Dec 31, 2024 5 0.091 mg/l DS000 Accepted
Lead Jan 1, 2022 – Dec 31, 2024 5 0.0006 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2021 5 0.084 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2021 5 0.0006 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2018 5 0.41 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2018 5 0.0006 mg/l DS000 Accepted
Copper Jan 1, 2013 – Dec 31, 2015 6 0.4785 mg/l DS000 Accepted
Lead Jan 1, 2013 – Dec 31, 2015 6 0.001 mg/l DS000 Accepted
Copper Jan 1, 2010 – Dec 31, 2012 5 0.5026 mg/l DS000 Accepted
Lead Jan 1, 2010 – Dec 31, 2012 5 0 mg/l DS000 Accepted
Copper Jan 1, 2009 – Dec 31, 2009 6 0.0266 mg/l DS000 Accepted
Lead Jan 1, 2009 – Dec 31, 2009 6 0.002 mg/l DS000 Accepted
Copper Jan 1, 2008 – Dec 31, 2008 5 0.4423 mg/l DS000 Accepted
Lead Jan 1, 2008 – Dec 31, 2008 5 0.0026 mg/l DS000 Accepted
Copper Jul 1, 2007 – Dec 31, 2007 10 0.6896 mg/l DS000 Accepted
Lead Jul 1, 2007 – Dec 31, 2007 10 0.0115 mg/l DS000 Accepted
Copper Jan 1, 2007 – Jun 30, 2007 10 1.018 mg/l DS000 Accepted
Lead Jan 1, 2007 – Jun 30, 2007 10 0.0118 mg/l DS000 Accepted
Copper Jul 1, 2005 – Dec 31, 2005 5 0.2731 mg/l DS000 Accepted
Lead Jul 1, 2005 – Dec 31, 2005 5 0.0026 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.