This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0320004 , Union Church Waterworks Assn
22 of the 57 analytes this system has been tested for have been detected at least once, across 141 samples on record.
The other 35 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 141 samples on record, detections range from September 24, 2003 to May 20, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 49 of 50 results | Jul 26, 2007 | Aug 6, 2024 |
| Lead 1030 | Inorganic Chemical | 28 of 50 results | Jul 26, 2007 | Aug 6, 2024 |
| Barium 1010 | Inorganic Chemical | 18 of 18 results | Sep 24, 2003 | May 20, 2025 |
| Fluoride 1025 | Inorganic Chemical | 12 of 18 results | Sep 24, 2003 | May 20, 2025 |
| Arsenic 1005 | Inorganic Chemical | 9 of 18 results | Jan 12, 2009 | Feb 20, 2024 |
| Nickel 1036 | Inorganic Chemical | 8 of 18 results | Jan 12, 2009 | May 20, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 8 of 15 results | Sep 24, 2008 | Apr 9, 2025 |
| TTHM 2950 | Organic Chemical | 5 of 13 results | Jun 16, 2004 | May 17, 2023 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 5 results | Dec 13, 2011 | Jul 31, 2012 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 5 of 5 results | Dec 13, 2011 | Jul 31, 2012 |
| Radium-226 4020 | Radionuclide | 5 of 5 results | Dec 13, 2011 | Jul 31, 2012 |
| Chromium 1020 | Inorganic Chemical | 3 of 18 results | Apr 8, 2015 | May 20, 2025 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 24, 2019 | Feb 26, 2025 |
| Chloroform 2941 | Organic Chemical | 3 of 8 results | Aug 9, 2007 | Aug 27, 2012 |
| Bromodichloromethane 2943 | Organic Chemical | 3 of 8 results | Aug 9, 2007 | Aug 27, 2012 |
| Monochloroacetic Acid 2450 | Organic Chemical | 2 of 9 results | Aug 27, 2012 | Aug 15, 2018 |
| Dichloroacetic Acid 2451 | Organic Chemical | 2 of 9 results | Aug 27, 2012 | Jun 29, 2015 |
| Dibromochloromethane 2944 | Organic Chemical | 2 of 8 results | Aug 9, 2007 | Sep 24, 2008 |
| Sulfate 1055 | Inorganic Chemical | 2 of 2 results | Sep 24, 2003 | Apr 7, 2004 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 9 results | Aug 15, 2018 | Aug 15, 2018 |
| Dibromoacetic Acid 2454 | Organic Chemical | 1 of 9 results | Aug 15, 2018 | Aug 15, 2018 |
| Trichloroacetic Acid 2452 | Organic Chemical | 1 of 9 results | Aug 27, 2012 | Aug 27, 2012 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 31–40 of 141 samples, newest first — collected October 20, 2021 to December 12, 2022. The summary above covers all 141.
74 results from the 10 samples listed here: 16 detected, 58 not detected. Across the whole record it is 175 of 652. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
We withheld the location of 2 sampling points below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Dec 12, 2022 11:45, sampling point MRT000 | TTHM 2950 EPA method 524.2 | Jan 1, 2022 – Dec 31, 2022 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Benzene 2990 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Toluene 2991 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 7, 2022 12:30, sampling point TF080 | Styrene 2996 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Arsenic 1005 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| 0.0977 mg/l , sample collected Apr 26, 2022 13:00, sampling point TF080 | Barium 1010 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Cadmium 1015 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Chromium 1020 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Fluoride 1025 EPA method QC 10-109-12-2-A | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Mercury 1035 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Selenium 1045 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Antimony, Total 1074 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Beryllium, Total 1075 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 26, 2022 13:00, sampling point TF080 | Thallium, Total 1085 EPA method 200.8 | Apr 1, 2022 – Jun 30, 2022 |
|
||
| 0.0005 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Arsenic 1005 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.102 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Barium 1010 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Cadmium 1015 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Chromium 1020 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.108 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Mercury 1035 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.0005 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Selenium 1045 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
|
||
| 0.0005 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Arsenic 1005 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.0995 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Barium 1010 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Cadmium 1015 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Chromium 1020 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.106 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Mercury 1035 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.0005 mg/l , sample collected Mar 21, 2022 11:00, sampling point TF080 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Selenium 1045 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:00, sampling point TF080 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
|
||
| 0.0005 mg/l , sample collected Mar 21, 2022 11:15, sampling point TF080 | Arsenic 1005 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.101 mg/l , sample collected Mar 21, 2022 11:15, sampling point TF080 | Barium 1010 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Cadmium 1015 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Chromium 1020 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.109 mg/l , sample collected Mar 21, 2022 11:15, sampling point TF080 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Mercury 1035 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| 0.0005 mg/l , sample collected Mar 21, 2022 11:15, sampling point TF080 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Selenium 1045 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 21, 2022 11:15, sampling point TF080 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2022 – Mar 31, 2022 |
|
||
| 19.6 mg/l , sample collected Feb 9, 2022 11:00, sampling point TF080 | Sodium 1052 EPA method 200.7 | Not recorded |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 9, 2022 11:00, sampling point TF080 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 9, 2022 11:00, sampling point TF080 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 9, 2022 11:00, sampling point TF080 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2022 – Dec 31, 2022 |
|
||
| 0.0026 mg/l , sample collected Oct 20, 2021 05:30, sampling point LC0010 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 20, 2021 05:30, sampling point LC0010 | Lead 1030 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
|
||
| 0.0024 mg/l , sample collected Oct 20, 2021 08:00, sampling point LC0009 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 20, 2021 08:00, sampling point LC0009 | Lead 1030 EPA method 200.8 | Jan 1, 2019 – Dec 31, 2021 |
-
- Collected
- Dec 12, 2022 11:45
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- TH-221213-017
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2022
-
TTHM 2950 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
-
- Collected
- Jun 7, 2022 12:30
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- VO-220608-042
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2022
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Apr 26, 2022 13:00
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- IN-220427-055
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0977 mg/l
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2022 – Jun 30, 2022
-
- Collected
- Mar 21, 2022 11:00
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- IN-220322-001
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.102 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.108 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
- Collected
- Mar 21, 2022 11:00
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- IN-220322-003
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0995 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.106 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
- Collected
- Mar 21, 2022 11:15
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- IN-220322-002
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.101 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.109 mg/l
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.0005 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Mar 31, 2022
-
- Collected
- Feb 9, 2022 11:00
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- NA-220210-012
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 19.6 mg/l
-
- Collected
- Feb 9, 2022 11:00
- Sampling point
- TF080 Treatment Plant T080
- Sample type
- Routine
- Lab sample
- NI-220210-014
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2022
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Oct 20, 2021 05:30
- Sampling point
- LC0010 Location withheld
- Sample type
- Routine
- Lab sample
- PB-211021-021
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2021
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0026 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Oct 20, 2021 08:00
- Sampling point
- LC0009 Location withheld
- Sample type
- Routine
- Lab sample
- PB-211021-026
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2021
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0024 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
Routine (10).