This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0340011 , Oak Grove Water Assn
22 of the 58 analytes this system has been tested for have been detected at least once, across 302 samples on record.
The other 36 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 302 samples on record, detections range from September 24, 2003 to November 19, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 61 of 61 results | Jul 24, 2007 | Aug 22, 2023 |
| Lead 1030 | Inorganic Chemical | 42 of 61 results | Jul 24, 2007 | Aug 22, 2023 |
| Barium 1010 | Inorganic Chemical | 24 of 24 results | Sep 24, 2003 | Feb 24, 2025 |
| Fluoride 1025 | Inorganic Chemical | 24 of 24 results | Sep 24, 2003 | Feb 24, 2025 |
| TTHM 2950 | Organic Chemical | 22 of 22 results | Jun 16, 2004 | Oct 13, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 20 of 21 results | Aug 16, 2007 | Nov 19, 2025 |
| Chloroform 2941 | Organic Chemical | 17 of 17 results | Aug 16, 2007 | Oct 13, 2025 |
| Bromodichloromethane 2943 | Organic Chemical | 17 of 17 results | Aug 16, 2007 | Oct 13, 2025 |
| Dichloroacetic Acid 2451 | Organic Chemical | 15 of 15 results | Sep 21, 2009 | Nov 19, 2025 |
| Trichloroacetic Acid 2452 | Organic Chemical | 15 of 15 results | Sep 21, 2009 | Nov 19, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 12 of 17 results | Sep 21, 2009 | Oct 13, 2025 |
| Sodium 1052 | Inorganic Chemical | 9 of 9 results | Sep 18, 2019 | Feb 3, 2025 |
| Nickel 1036 | Inorganic Chemical | 8 of 24 results | Feb 13, 2006 | Feb 24, 2025 |
| Chromium 1020 | Inorganic Chemical | 7 of 24 results | Sep 24, 2003 | May 30, 2017 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 6 of 11 results | Dec 15, 2011 | Dec 2, 2013 |
| Xylenes, Total 2955 | Organic Chemical | 5 of 66 results | Feb 2, 2004 | May 31, 2005 |
| Sulfate 1055 | Inorganic Chemical | 4 of 4 results | Sep 24, 2003 | Feb 25, 2004 |
| Ethylbenzene 2992 | Organic Chemical | 2 of 66 results | Feb 2, 2004 | Feb 2, 2004 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 15 results | Sep 8, 2020 | Sep 8, 2020 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 15 results | Jul 1, 2015 | Jul 1, 2015 |
| Arsenic 1005 | Inorganic Chemical | 1 of 24 results | Apr 2, 2014 | Apr 2, 2014 |
| Dichloromethane 2964 | Organic Chemical | 1 of 66 results | Aug 4, 2004 | Aug 4, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 161–170 of 302 samples, newest first — collected September 12, 2013 to April 2, 2014. The summary above covers all 302.
67 results from the 10 samples listed here: 6 detected, 61 not detected. Across the whole record it is 314 of 2,230. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0006 mg/l , sample collected Apr 2, 2014 12:36, sampling point TF103 | Arsenic 1005 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| 0.0052 mg/l , sample collected Apr 2, 2014 12:36, sampling point TF103 | Barium 1010 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 2, 2014 12:36, sampling point TF103 | Cadmium 1015 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| 0.0055 mg/l , sample collected Apr 2, 2014 12:36, sampling point TF103 | Chromium 1020 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| 0.255 mg/l , sample collected Apr 2, 2014 12:36, sampling point TF103 | Fluoride 1025 EPA method 300.0 | Jan 1, 2013 – Dec 31, 2015 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 2, 2014 12:36, sampling point TF103 | Mercury 1035 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| 0.0019 mg/l , sample collected Apr 2, 2014 12:36, sampling point TF103 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Apr 2, 2014 12:36, sampling point TF103 | Selenium 1045 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 2, 2014 12:36, sampling point TF103 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 2, 2014 12:36, sampling point TF103 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 2, 2014 12:36, sampling point TF103 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2013 – Dec 31, 2015 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Mar 3, 2014 09:05, sampling point TF103 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2013 – Dec 31, 2015 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Benzene 2990 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Toluene 2991 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Feb 6, 2014 08:15, sampling point TF103 | Styrene 2996 EPA method 524.2 | Jan 1, 2014 – Mar 31, 2014 |
|
||
| 0.5 pci/l , sample collected Dec 2, 2013 14:18, sampling point TF103 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Oct 1, 2013 – Dec 31, 2013 |
|
||
| Not detected below 0.34 pci/l Minimum Reporting Level , sample collected Dec 2, 2013 14:18, sampling point TF103 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.149 pci/l Minimum Reporting Level , sample collected Dec 2, 2013 14:18, sampling point TF103 | Radium-226 4020 EPA method 903.1 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.34 pci/l Minimum Reporting Level , sample collected Dec 2, 2013 14:18, sampling point TF103 | Radium-228 4030 EPA method 904 | Oct 1, 2013 – Dec 31, 2013 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Dec 2, 2013 14:18, sampling point TF103 | Combined Uranium 4006 EPA method 200.8 | Oct 1, 2013 – Dec 31, 2013 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Nov 11, 2013 03:30, sampling point TF103 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2013 – Dec 31, 2013 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Nov 11, 2013 03:30, sampling point TF103 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2013 – Dec 31, 2013 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Nov 11, 2013 03:30, sampling point TF103 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2013 – Dec 31, 2013 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Xylenes, Total 2955 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Dichloromethane 2964 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | O-Dichlorobenzene 2968 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | P-Dichlorobenzene 2969 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Vinyl Chloride 2976 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | 1,2-Dichloroethane 2980 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Carbon Tetrachloride 2982 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | 1,2-Dichloropropane 2983 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Trichloroethylene 2984 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Tetrachloroethylene 2987 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Chlorobenzene 2989 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Benzene 2990 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Toluene 2991 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Ethylbenzene 2992 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Oct 24, 2013 03:48, sampling point TF103 | Styrene 2996 EPA method 524.2 | Oct 1, 2013 – Dec 31, 2013 |
|
||
| Not detected below 0.3 pci/l Minimum Reporting Level , sample collected Sep 12, 2013 15:19, sampling point TF103 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.194 pci/l Minimum Reporting Level , sample collected Sep 12, 2013 15:19, sampling point TF103 | Radium-226 4020 EPA method 903.1 | Jul 1, 2013 – Sep 30, 2013 |
| Not detected below 0.3 pci/l Minimum Reporting Level , sample collected Sep 12, 2013 15:19, sampling point TF103 | Radium-228 4030 EPA method 904 | Jul 1, 2013 – Sep 30, 2013 |
| Not detected below 0.31 pci/l Minimum Reporting Level , sample collected Sep 12, 2013 15:19, sampling point TF103 | Gross Alpha Particle Activity 4109 EPA method 00-02 | Not recorded |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 12, 2013 15:12, sampling point TF103 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2013 – Sep 30, 2013 |
-
- Collected
- Apr 2, 2014 12:36
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 140403-034IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0006 mg/l
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Barium 1010 EPA method 200.8
- Result
- 0.0052 mg/l
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Chromium 1020 EPA method 200.8
- Result
- 0.0055 mg/l
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Fluoride 1025 EPA method 300.0
- Result
- 0.255 mg/l
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Nickel 1036 EPA method 200.8
- Result
- 0.0019 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
- Collected
- Mar 3, 2014 09:05
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 140304-026CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2013 – Dec 31, 2015
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Feb 6, 2014 08:15
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 140207-007VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2014 – Mar 31, 2014
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Dec 2, 2013 14:18
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 201402280123GA
- Laboratory
- Radiation Safety Engineering
- Monitoring period
- Oct 1, 2013 – Dec 31, 2013
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.5 pci/l
-
- Collected
- Dec 2, 2013 14:18
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 201402280123
- Laboratory
- Radiation Safety Engineering
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.34 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.149 pci/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2013 – Dec 31, 2013
-
Radium-228 4030 EPA method 904
- Result
- Not detected below 0.34 pci/l Minimum Reporting Level
- Monitoring period
- Oct 1, 2013 – Dec 31, 2013
-
- Collected
- Dec 2, 2013 14:18
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 131203-001RU
- Laboratory
- MSDH Lab
- Monitoring period
- Oct 1, 2013 – Dec 31, 2013
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Nov 11, 2013 03:30
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 131112-016NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2013 – Dec 31, 2013
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Oct 24, 2013 03:48
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 131025-001VO
- Laboratory
- MSDH Lab
- Monitoring period
- Oct 1, 2013 – Dec 31, 2013
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Sep 12, 2013 15:19
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 201309260162
- Laboratory
- Radiation Safety Engineering
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.3 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.194 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2013 – Sep 30, 2013
-
Radium-228 4030 EPA method 904
- Result
- Not detected below 0.3 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2013 – Sep 30, 2013
-
Gross Alpha Particle Activity 4109 EPA method 00-02
- Result
- Not detected below 0.31 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
- Collected
- Sep 12, 2013 15:12
- Sampling point
- TF103 Treatment Facility TF103
- Sample type
- Routine
- Lab sample
- 130913-003RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2013 – Sep 30, 2013
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
Routine (10).