This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Lead and copper
MS0340019 , Southwest Jones W/A-North
Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.
| Analyte | Monitoring period | Samples | 90th percentile | Facility | Data quality |
|---|---|---|---|---|---|
| Copper | Jan 1, 2022 – Dec 31, 2024 | 20 | 0.237 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2022 – Dec 31, 2024 | 20 | 0.0024 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2019 – Dec 31, 2021 | 20 | 0.468 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2019 – Dec 31, 2021 | 20 | 0.0055 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2016 – Dec 31, 2018 | 20 | 0.3955 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2016 – Dec 31, 2018 | 20 | 0.0031 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2014 – Dec 31, 2016 | 21 | 0.3214 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2014 – Dec 31, 2016 | 21 | 0.0038 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2011 – Dec 31, 2013 | 20 | 0.2611 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2011 – Dec 31, 2013 | 20 | 0.0054 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2008 – Dec 31, 2010 | 20 | 0.274 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2008 – Dec 31, 2010 | 20 | 0.0015 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2005 – Dec 31, 2007 | 23 | 0.3315 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2005 – Dec 31, 2007 | 23 | 0.0035 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2000 – Dec 31, 2002 | 10 | 0.674 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2000 – Dec 31, 2002 | 10 | 0.006 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1996 – Dec 31, 1996 | 10 | 0.593 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1996 – Dec 31, 1996 | 10 | 0.007 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1995 – Dec 31, 1995 | 10 | 0.182 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1995 – Dec 31, 1995 | 10 | 0.005 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1994 – Jun 30, 1994 | 20 | 0.338 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1994 – Jun 30, 1994 | 20 | 0.003 mg/l | DS000 | Accepted |
| Copper | Jul 1, 1993 – Dec 31, 1993 | 20 | 0.279 mg/l | DS000 | Accepted |
| Lead | Jul 1, 1993 – Dec 31, 1993 | 20 | 0.004 mg/l | DS000 | Accepted |
No date of receipt is recorded for any of these summaries.
What the 90th percentile is
The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.
From the help text published with these pages.