Chemical and radiological sample results

MS0360016 , Westover Water Association, Inc

20 of the 62 analytes this system has been tested for have been detected at least once, across 230 samples on record.

The other 42 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 230 samples on record, detections range from June 27, 2002 to February 24, 2026. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Westover Water Association, Inc, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 61 of 61 results Aug 2, 2007 Jun 17, 2024
Nitrate-Nitrite 1038 Inorganic Chemical 42 of 44 results May 17, 2004 Feb 24, 2026
Nitrate 1040 Inorganic Chemical 42 of 44 results May 17, 2004 Feb 24, 2026
Lead 1030 Inorganic Chemical 33 of 61 results Aug 2, 2007 Jun 17, 2024
Barium 1010 Inorganic Chemical 20 of 20 results Sep 29, 2003 Feb 26, 2025
Gross Alpha, Incl. Radon & U 4002 Radionuclide 10 of 10 results Dec 15, 2011 Jul 13, 2012
Combined Radium (-226 & -228) 4010 Radionuclide 10 of 10 results Dec 15, 2011 Jul 13, 2012
Radium-226 4020 Radionuclide 10 of 10 results Dec 15, 2011 Jul 13, 2012
Sodium 1052 Inorganic Chemical 8 of 8 results May 24, 2021 Feb 5, 2025
Xylenes, Total 2955 Organic Chemical 6 of 26 results Jun 27, 2002 Aug 18, 2003
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 5 of 20 results Sep 21, 2009 May 8, 2024
Ethylbenzene 2992 Organic Chemical 5 of 26 results Aug 27, 2002 Aug 18, 2003
Calcium 1016 Inorganic Chemical 4 of 4 results May 24, 2021 May 24, 2021
Chloride 1017 Inorganic Chemical 4 of 4 results May 24, 2021 May 24, 2021
Conductivity @ 25 C Umhos/CM 1064 Water Quality 4 of 4 results May 24, 2021 May 24, 2021
TTHM 2950 Organic Chemical 3 of 22 results Aug 15, 2007 Aug 15, 2023
Chromium 1020 Inorganic Chemical 2 of 20 results Apr 15, 2015 Apr 15, 2015
Fluoride 1025 Inorganic Chemical 2 of 24 results Apr 15, 2015 Apr 15, 2015
Monobromoacetic Acid 2453 Organic Chemical 1 of 15 results Sep 17, 2020 Sep 17, 2020
Monochloroacetic Acid 2450 Organic Chemical 1 of 15 results Aug 22, 2018 Aug 22, 2018

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 171–180 of 230 samples, newest first — collected August 2, 2007 to February 4, 2009. The summary above covers all 230.

34 results from the 10 samples listed here: 16 detected, 18 not detected. Across the whole record it is 273 of 1,315. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Westover Water Association, Inc, every result from 171 to 180 of 230 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Feb 4, 2009
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
090205-032IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Arsenic 1005 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
0.010916 mg/l , sample collected Feb 4, 2009, sampling point TF080 Barium 1010 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Cadmium 1015 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Chromium 1020 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Fluoride 1025 EPA method 380-75WE Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Mercury 1035 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Selenium 1045 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Antimony, Total 1074 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Feb 4, 2009, sampling point TF080 Thallium, Total 1085 EPA method 200.8 Jan 1, 2008 – Dec 31, 2010
Collected
Jun 16, 2008
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
080617-090NI
Laboratory
MSDH Lab
0.26 mg/l , sample collected Jun 16, 2008, sampling point TF080 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2008 – Dec 31, 2008
0.26 mg/l , sample collected Jun 16, 2008, sampling point TF080 Nitrate 1040 EPA method 353.2 Jan 1, 2008 – Dec 31, 2008
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jun 16, 2008, sampling point TF080 Nitrite 1041 EPA method 353.2 Jan 1, 2008 – Dec 31, 2008
Collected
Jun 16, 2008
Sampling point
TF081 Treatment Plant T081
Sample type
Routine
Lab sample
080617-053NI
Laboratory
MSDH Lab
0.16 mg/l , sample collected Jun 16, 2008, sampling point TF081 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2008 – Dec 31, 2008
0.16 mg/l , sample collected Jun 16, 2008, sampling point TF081 Nitrate 1040 EPA method 353.2 Jan 1, 2008 – Dec 31, 2008
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jun 16, 2008, sampling point TF081 Nitrite 1041 EPA method 353.2 Jan 1, 2008 – Dec 31, 2008
Collected
Aug 15, 2007
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
070816-008TH
Laboratory
MSDH Lab
Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 15, 2007, sampling point MRT000 Chloroform 2941 EPA method 524.2 Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 15, 2007, sampling point MRT000 Bromoform 2942 EPA method 524.2 Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 15, 2007, sampling point MRT000 Bromodichloromethane 2943 EPA method 524.2 Not recorded
Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 15, 2007, sampling point MRT000 Dibromochloromethane 2944 EPA method 524.2 Not recorded
0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Aug 15, 2007, sampling point MRT000 TTHM 2950 EPA method 524.2 Jan 1, 2005 – Dec 31, 2007
Collected
Aug 2, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070803-037PB
Laboratory
MSDH Lab
0.1409 mg/l , sample collected Aug 2, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
0.0024 mg/l , sample collected Aug 2, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Collected
Aug 2, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070803-038PB
Laboratory
MSDH Lab
0.0284 mg/l , sample collected Aug 2, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 2, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Collected
Aug 2, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070803-034PB
Laboratory
MSDH Lab
0.0325 mg/l , sample collected Aug 2, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
0.0022 mg/l , sample collected Aug 2, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Collected
Aug 2, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070803-039PB
Laboratory
MSDH Lab
0.146 mg/l , sample collected Aug 2, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
0.0042 mg/l , sample collected Aug 2, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Collected
Aug 2, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070803-041PB
Laboratory
MSDH Lab
0.0052 mg/l , sample collected Aug 2, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 2, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
Collected
Aug 2, 2007
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
070803-042PB
Laboratory
MSDH Lab
0.0129 mg/l , sample collected Aug 2, 2007, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008
0.0022 mg/l , sample collected Aug 2, 2007, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2006 – Dec 31, 2008

Routine (10).