Chemical and radiological sample results
MS0360064 , Sanders Water Association,inc
20 of the 57 analytes this system has been tested for have been detected at least once, across 198 samples on record.
The other 37 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 198 samples on record, detections range from September 29, 2003 to September 30, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 60 of 60 results | Aug 2, 2007 | Jun 17, 2025 |
| Lead 1030 | Inorganic Chemical | 41 of 60 results | Aug 2, 2007 | Jun 17, 2025 |
| Barium 1010 | Inorganic Chemical | 18 of 18 results | Sep 29, 2003 | Mar 5, 2025 |
| Fluoride 1025 | Inorganic Chemical | 18 of 18 results | Sep 29, 2003 | Mar 5, 2025 |
| Chromium 1020 | Inorganic Chemical | 13 of 18 results | Sep 29, 2003 | Apr 2, 2019 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 10 of 10 results | Dec 6, 2011 | Jul 11, 2012 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 6 of 21 results | Sep 23, 2009 | May 3, 2022 |
| Arsenic 1005 | Inorganic Chemical | 6 of 18 results | Sep 29, 2003 | Apr 2, 2019 |
| TTHM 2950 | Organic Chemical | 5 of 21 results | Aug 15, 2007 | Sep 30, 2025 |
| Sulfate 1055 | Inorganic Chemical | 4 of 4 results | Sep 29, 2003 | Mar 3, 2004 |
| Chloroform 2941 | Organic Chemical | 3 of 16 results | Jul 6, 2015 | Sep 30, 2025 |
| Nitrite 1041 | Inorganic Chemical | 3 of 38 results | Aug 17, 2005 | Feb 23, 2011 |
| Sodium 1052 | Inorganic Chemical | 2 of 2 results | Feb 16, 2022 | Feb 5, 2025 |
| Nickel 1036 | Inorganic Chemical | 2 of 18 results | Mar 23, 2005 | Mar 23, 2005 |
| Bromoform 2942 | Organic Chemical | 1 of 16 results | Sep 16, 2024 | Sep 16, 2024 |
| Dibromochloromethane 2944 | Organic Chemical | 1 of 16 results | Sep 16, 2024 | Sep 16, 2024 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 16 results | Sep 30, 2020 | Sep 30, 2020 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 16 results | Aug 14, 2019 | Aug 14, 2019 |
| Dibromoacetic Acid 2454 | Organic Chemical | 1 of 16 results | Jun 5, 2019 | Jun 5, 2019 |
| Cyanide 1024 | Inorganic Chemical | 1 of 17 results | Dec 9, 2009 | Dec 9, 2009 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 111–120 of 198 samples, newest first — collected February 22, 2012 to July 10, 2012. The summary above covers all 198.
34 results from the 10 samples listed here: 7 detected, 27 not detected. Across the whole record it is 197 of 963. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.5 pci/l , sample collected Jul 10, 2012 13:55, sampling point TF102 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.241 pci/l Minimum Reporting Level , sample collected Jul 10, 2012 13:55, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.241 pci/l Minimum Reporting Level , sample collected Jul 10, 2012 13:55, sampling point TF102 | Radium-226 4020 EPA method 903.1 | Jul 1, 2012 – Sep 30, 2012 |
| Not detected below 0.24 pci/l Minimum Reporting Level , sample collected Jul 10, 2012 13:55, sampling point TF102 | Radium-228 4030 EPA method 904.0 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| 0.4 pci/l , sample collected Jul 10, 2012 14:12, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.23 pci/l Minimum Reporting Level , sample collected Jul 10, 2012 14:12, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.212 pci/l Minimum Reporting Level , sample collected Jul 10, 2012 14:12, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Jul 1, 2012 – Sep 30, 2012 |
| Not detected below 0.23 pci/l Minimum Reporting Level , sample collected Jul 10, 2012 14:12, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 10, 2012 13:55, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 10, 2012 14:15, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.00691 mg/l , sample collected May 2, 2012 02:35, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.00326 mg/l , sample collected May 2, 2012 02:35, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 1.04 mg/l , sample collected May 2, 2012 02:35, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 2, 2012 02:35, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.5 pci/l , sample collected Apr 19, 2012 14:55, sampling point TF102 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.241 pci/l Minimum Reporting Level , sample collected Apr 19, 2012 14:55, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.241 pci/l Minimum Reporting Level , sample collected Apr 19, 2012 14:55, sampling point TF102 | Radium-226 4020 EPA method 903.1 | Apr 1, 2012 – Jun 30, 2012 |
| Not detected below 0.24 pci/l Minimum Reporting Level , sample collected Apr 19, 2012 14:55, sampling point TF102 | Radium-228 4030 EPA method 904.0 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| 0.4 pci/l , sample collected Apr 19, 2012 14:38, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.23 pci/l Minimum Reporting Level , sample collected Apr 19, 2012 14:38, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.212 pci/l Minimum Reporting Level , sample collected Apr 19, 2012 14:38, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Apr 1, 2012 – Jun 30, 2012 |
| Not detected below 0.23 pci/l Minimum Reporting Level , sample collected Apr 19, 2012 14:38, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 19, 2012 14:55, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 19, 2012 14:18, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 22, 2012 02:45, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 22, 2012 02:45, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 22, 2012 02:45, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
-
- Collected
- Jul 10, 2012 13:55
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120711-008
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.5 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.241 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.241 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.24 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
- Collected
- Jul 10, 2012 14:12
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120711-007
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.4 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.23 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.212 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.23 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
- Collected
- Jul 10, 2012 13:55
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120711-008RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jul 10, 2012 14:15
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120711-007RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- May 2, 2012 02:35
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120503-013IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.00691 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- 0.00326 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 380-75WE
- Result
- 1.04 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- Apr 19, 2012 14:55
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120420-008
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.5 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.241 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.241 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.24 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
- Collected
- Apr 19, 2012 14:38
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120420-007
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.4 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.23 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.212 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.23 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
- Collected
- Apr 19, 2012 14:55
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120420-008RU
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Apr 19, 2012 14:18
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120420-007RU
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Feb 22, 2012 02:45
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120223-114NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2012 – Dec 31, 2012
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
Routine (10).