Lead and copper

MS0360068 , Wellsgate

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for Wellsgate, 30 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2025 – Dec 31, 2025 10 0.0579 mg/l DS000 Accepted
Lead Jan 1, 2025 – Dec 31, 2025 2 0 mg/l DS000 Accepted
Copper Jan 1, 2024 – Dec 31, 2024 8 0.196 mg/l DS000 Accepted
Lead Jan 1, 2024 – Dec 31, 2024 8 0.0012 mg/l DS000 Accepted
Copper Jan 1, 2023 – Dec 31, 2023 10 0.876 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2023 10 0.0024 mg/l DS000 Accepted
Copper Jan 1, 2021 – Dec 31, 2021 9 0.736 mg/l DS000 Accepted
Lead Jan 1, 2021 – Dec 31, 2021 9 0.0027 mg/l DS000 Accepted
Copper Jan 1, 2015 – Dec 31, 2017 10 0.1772 mg/l DS000 Accepted
Lead Jan 1, 2015 – Dec 31, 2017 10 0.0026 mg/l DS000 Accepted
Copper Jan 1, 2012 – Dec 31, 2014 10 0.0693 mg/l DS000 Accepted
Lead Jan 1, 2012 – Dec 31, 2014 10 0.0007 mg/l DS000 Accepted
Copper Jan 1, 2011 – Dec 31, 2011 11 0.043 mg/l DS000 Accepted
Lead Jan 1, 2011 – Dec 31, 2011 11 0.0009 mg/l DS000 Accepted
Copper Jan 1, 2010 – Dec 31, 2010 10 0.3369 mg/l DS000 Accepted
Lead Jan 1, 2010 – Dec 31, 2010 10 0.0096 mg/l DS000 Accepted
Copper Jul 1, 2009 – Dec 31, 2009 20 0.0228 mg/l DS000 Accepted
Lead Jul 1, 2009 – Dec 31, 2009 20 0.0027 mg/l DS000 Accepted
Copper Jan 1, 2009 – Jun 30, 2009 22 0.0071 mg/l DS000 Accepted
Lead Jan 1, 2009 – Jun 30, 2009 22 0 mg/l DS000 Accepted
Copper Jan 1, 2007 – Dec 31, 2007 4 0.0933 mg/l DS000 Accepted
Lead Jan 1, 2007 – Dec 31, 2007 4 0.0046 mg/l DS000 Accepted
Copper Jan 1, 2006 – Dec 31, 2006 6 0.1653 mg/l DS000 Accepted
Lead Jan 1, 2006 – Dec 31, 2006 6 0.0009 mg/l DS000 Accepted
Copper Jan 1, 2005 – Jun 30, 2005 10 1.3493 mg/l DS000 Accepted
Lead Jan 1, 2005 – Jun 30, 2005 10 0.005 mg/l DS000 Accepted
Copper Jul 1, 2004 – Dec 31, 2004 10 0.5803 mg/l DS000 Accepted
Lead Jul 1, 2004 – Dec 31, 2004 10 0.0036 mg/l DS000 Accepted
Copper Jul 1, 2003 – Dec 31, 2003 19 0.585 mg/l DS000 Accepted
Lead Jul 1, 2003 – Dec 31, 2003 19 0.004 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.