Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0370011 , West Lamar Water Assn #1

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for West Lamar Water Assn #1, 28 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2022 – Dec 31, 2024 30 0.105 mg/l DS000 Accepted
Lead Jan 1, 2022 – Dec 31, 2024 30 0.0017 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2021 30 0.12 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2021 30 0.001 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2018 30 0.2333 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2018 30 0.0025 mg/l DS000 Accepted
Copper Jan 1, 2014 – Dec 31, 2016 30 0.1627 mg/l DS000 Accepted
Lead Jan 1, 2014 – Dec 31, 2016 30 0.002 mg/l DS000 Accepted
Copper Jan 1, 2011 – Dec 31, 2013 30 0.0917 mg/l DS000 Accepted
Lead Jan 1, 2011 – Dec 31, 2013 30 0.0011 mg/l DS000 Accepted
Copper Jan 1, 2008 – Dec 31, 2010 30 0.1419 mg/l DS000 Accepted
Lead Jan 1, 2008 – Dec 31, 2010 30 0.0014 mg/l DS000 Accepted
Copper Jan 1, 2005 – Dec 31, 2007 30 0.1867 mg/l DS000 Accepted
Lead Jan 1, 2005 – Dec 31, 2007 30 0.0041 mg/l DS000 Accepted
Copper Jan 1, 2002 – Dec 31, 2004 30 0.1182 mg/l DS000 Accepted
Lead Jan 1, 2002 – Dec 31, 2004 30 0.0025 mg/l DS000 Accepted
Copper Jan 1, 1999 – Dec 31, 2001 20 0.133 mg/l DS000 Accepted
Lead Jan 1, 1999 – Dec 31, 2001 20 0.003 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1998 20 0.082 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1998 20 0.003 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 20 0.208 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 20 0.003 mg/l DS000 Accepted
Copper Jan 1, 1994 – Dec 31, 1994 20 0.203 mg/l DS000 Accepted
Lead Jan 1, 1994 – Dec 31, 1994 20 0.002 mg/l DS000 Accepted
Copper Jan 1, 1993 – Jun 30, 1993 40 0.631 mg/l DS000 Accepted
Lead Jan 1, 1993 – Jun 30, 1993 40 0.007 mg/l DS000 Accepted
Copper Jul 1, 1992 – Dec 31, 1992 80 0.06 mg/l DS000 Accepted
Lead Jul 1, 1992 – Dec 31, 1992 80 0.002 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.