This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0410023 , Natchez Trace Parkway
38 of the 67 analytes this system has been tested for have been detected at least once, across 216 samples on record.
The other 29 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 216 samples on record, detections range from October 1, 2003 to March 10, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 45 of 45 results | Aug 4, 2004 | Aug 29, 2023 |
| Barium 1010 | Inorganic Chemical | 22 of 22 results | Oct 1, 2003 | Mar 10, 2025 |
| Fluoride 1025 | Inorganic Chemical | 22 of 24 results | Oct 1, 2003 | Mar 10, 2025 |
| Nickel 1036 | Inorganic Chemical | 17 of 22 results | Oct 1, 2003 | Mar 10, 2025 |
| Lead 1030 | Inorganic Chemical | 16 of 45 results | Aug 4, 2004 | Aug 29, 2023 |
| Chromium 1020 | Inorganic Chemical | 15 of 22 results | Oct 1, 2003 | Sep 26, 2022 |
| Xylenes, Total 2955 | Organic Chemical | 14 of 58 results | Aug 9, 2004 | Mar 3, 2025 |
| Arsenic 1005 | Inorganic Chemical | 8 of 22 results | May 10, 2010 | Mar 10, 2025 |
| TTHM 2950 | Organic Chemical | 6 of 8 results | Sep 17, 2007 | Feb 10, 2025 |
| Sulfate 1055 | Inorganic Chemical | 6 of 6 results | Oct 1, 2003 | Apr 14, 2017 |
| Selenium 1045 | Inorganic Chemical | 6 of 22 results | Oct 1, 2003 | Jul 9, 2012 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 5 of 8 results | Sep 17, 2007 | Dec 5, 2022 |
| Dichloromethane 2964 | Organic Chemical | 4 of 58 results | Aug 9, 2004 | Jun 21, 2022 |
| Sodium 1052 | Inorganic Chemical | 4 of 4 results | Apr 14, 2017 | Feb 14, 2022 |
| Bromoform 2942 | Organic Chemical | 4 of 5 results | Sep 17, 2007 | Sep 10, 2018 |
| Ethylbenzene 2992 | Organic Chemical | 3 of 58 results | Aug 9, 2004 | Oct 29, 2013 |
| Dichloroacetic Acid 2451 | Organic Chemical | 2 of 4 results | Jul 24, 2013 | Sep 10, 2018 |
| Dibromoacetic Acid 2454 | Organic Chemical | 2 of 4 results | Jul 24, 2013 | Sep 10, 2018 |
| Bromodichloromethane 2943 | Organic Chemical | 2 of 5 results | Jul 24, 2013 | Sep 10, 2018 |
| Dibromochloromethane 2944 | Organic Chemical | 2 of 5 results | Jul 24, 2013 | Sep 10, 2018 |
| Calcium 1016 | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Chloride 1017 | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Iron 1028 | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Magnesium 1031 | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Manganese 1032 | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Potassium 1042 | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Residue, Total, Filterable 1057 | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Carbon Dioxide 1901 | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Color 1905 | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Hardness, Total (As Caco3) 1915 | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Alkalinity, Total 1927 | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Iron, Field Result FEFD | Inorganic Chemical | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| Calculated Sodium NACA | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| PH, Field Result PHFD | Water Quality | 2 of 2 results | Apr 14, 2017 | Apr 14, 2017 |
| 1,2-Dichloroethane 2980 | Organic Chemical | 2 of 58 results | Mar 7, 2016 | Mar 14, 2017 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 4 results | Sep 10, 2018 | Sep 10, 2018 |
| Carbon Tetrachloride 2982 | Organic Chemical | 1 of 58 results | Mar 14, 2017 | Mar 14, 2017 |
| Cadmium 1015 | Inorganic Chemical | 1 of 22 results | Feb 27, 2006 | Feb 27, 2006 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 131–140 of 216 samples, newest first — collected November 9, 2009 to August 9, 2010. The summary above covers all 216.
51 results from the 10 samples listed here: 17 detected, 34 not detected. Across the whole record it is 238 of 1,809. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.25 mg/l Minimum Reporting Level , sample collected Aug 9, 2010, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2010 – Dec 31, 2010 |
| Not detected below 0.2 mg/l Minimum Reporting Level , sample collected Aug 9, 2010, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2010 – Dec 31, 2010 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected Aug 9, 2010, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2010 – Dec 31, 2010 |
|
||
| Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Monochloroacetic Acid 2450 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Dichloroacetic Acid 2451 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Trichloroacetic Acid 2452 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Monobromoacetic Acid 2453 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Dibromoacetic Acid 2454 EPA method 552.2 | Not recorded |
| 0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Jun 8, 2010, sampling point MRT000 | Total Haloacetic Acids (Haa5) 2456 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Chloroform 2941 EPA method 524.2 | Not recorded |
| 2.38 ug/l , sample collected Jun 8, 2010, sampling point MRT000 | Bromoform 2942 EPA method 524.2 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Bromodichloromethane 2943 EPA method 524.2 | Not recorded |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Jun 8, 2010, sampling point MRT000 | Dibromochloromethane 2944 EPA method 524.2 | Not recorded |
| 2.38 ug/l , sample collected Jun 8, 2010, sampling point MRT000 | TTHM 2950 EPA method 524.2 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.001 mg/l , sample collected May 10, 2010, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.1504 mg/l , sample collected May 10, 2010, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0013 mg/l , sample collected May 10, 2010, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.123 mg/l , sample collected May 10, 2010, sampling point TF101 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0025 mg/l , sample collected May 10, 2010, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0011 mg/l , sample collected May 10, 2010, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Not recorded |
| 0.1502 mg/l , sample collected May 10, 2010, sampling point TF102 | Barium 1010 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Not recorded |
| 0.0011 mg/l , sample collected May 10, 2010, sampling point TF102 | Chromium 1020 EPA method 200.8 | Not recorded |
| 0.132 mg/l , sample collected May 10, 2010, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF102 | Mercury 1035 EPA method 200.8 | Not recorded |
| 0.0016 mg/l , sample collected May 10, 2010, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF102 | Selenium 1045 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 10, 2010, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Not recorded |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected May 3, 2010, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected May 3, 2010, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected Dec 7, 2009, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected Dec 7, 2009, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Not recorded |
| 0.157715 mg/l , sample collected Nov 9, 2009, sampling point TF102 | Barium 1010 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Not recorded |
| 0.001834 mg/l , sample collected Nov 9, 2009, sampling point TF102 | Chromium 1020 EPA method 200.8 | Not recorded |
| 0.14 mg/l , sample collected Nov 9, 2009, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Mercury 1035 EPA method 200.8 | Not recorded |
| 0.0015 mg/l , sample collected Nov 9, 2009, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Selenium 1045 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 9, 2009, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Not recorded |
-
- Collected
- Aug 9, 2010
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 100810-082NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2010 – Dec 31, 2010
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.25 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.2 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
- Collected
- Jun 8, 2010
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 100609-002HA
- Laboratory
- MSDH Lab
-
Monochloroacetic Acid 2450 EPA method 552.2
- Result
- Not detected below 0.002 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dichloroacetic Acid 2451 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Trichloroacetic Acid 2452 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Monobromoacetic Acid 2453 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dibromoacetic Acid 2454 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Total Haloacetic Acids (Haa5) 2456
- Result
- 0 This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. The agency recorded a value but no unit of measure for it. The unit is NOT inferable from the analyte: many analytes are reported in more than one unit — TTHM and HAA5 in both MG/L and UG/L — so there is no per-analyte default to fall back on. The number is published as it stands and must not be compared to a limit. The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Jun 8, 2010
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 100609-002TH
- Laboratory
- MSDH Lab
-
Chloroform 2941 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Bromoform 2942 EPA method 524.2
- Result
- 2.38 ug/l
- Monitoring period
- Not recorded
-
Bromodichloromethane 2943 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dibromochloromethane 2944 EPA method 524.2
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
TTHM 2950 EPA method 524.2
- Result
- 2.38 ug/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- May 10, 2010
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 100511-048IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.1504 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- 0.0013 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.123 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- 0.0025 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- May 10, 2010
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 100511-047IN
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0011 mg/l
-
Barium 1010 EPA method 200.8
- Result
- 0.1502 mg/l
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Chromium 1020 EPA method 200.8
- Result
- 0.0011 mg/l
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.132 mg/l
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Nickel 1036 EPA method 200.8
- Result
- 0.0016 mg/l
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- May 3, 2010
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 100504-032CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- May 3, 2010
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 100504-031CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- Dec 7, 2009
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 091208-009CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- Dec 7, 2009
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 091208-008CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- Nov 9, 2009
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 091110-006IN
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Barium 1010 EPA method 200.8
- Result
- 0.157715 mg/l
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Chromium 1020 EPA method 200.8
- Result
- 0.001834 mg/l
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.14 mg/l
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Nickel 1036 EPA method 200.8
- Result
- 0.0015 mg/l
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
Routine (10).