Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0410044 , North Lee W/A-SWS #1

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for North Lee W/A-SWS #1, 18 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2025 – Dec 31, 2025 10 0.0218 mg/l DS000 Accepted
Lead Jan 1, 2025 – Dec 31, 2025 10 0 mg/l DS000 Accepted
Copper Jan 1, 2024 – Dec 31, 2024 10 0.0066 mg/l DS000 Accepted
Lead Jan 1, 2024 – Dec 31, 2024 10 0 mg/l DS000 Accepted
Copper Jan 1, 2023 – Dec 31, 2023 10 0.0348 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2023 10 0 mg/l DS000 Accepted
Copper Jul 1, 2022 – Dec 31, 2022 20 0.0559 mg/l DS000 Accepted
Lead Jul 1, 2022 – Dec 31, 2022 20 0.0006 mg/l DS000 Accepted
Copper Jan 1, 2022 – Jun 30, 2022 20 0.0392 mg/l DS000 Accepted
Lead Jan 1, 2022 – Jun 30, 2022 20 0.0005 mg/l DS000 Accepted
Copper Jul 1, 2021 – Dec 31, 2021 20 0.0392 mg/l DS000 Accepted
Lead Jul 1, 2021 – Dec 31, 2021 20 0.0009 mg/l DS000 Accepted
Copper Jan 1, 2021 – Jun 30, 2021 20 0.0659 mg/l DS000 Accepted
Lead Jan 1, 2021 – Jun 30, 2021 20 0.0023 mg/l DS000 Accepted
Copper Jul 1, 2020 – Dec 31, 2020 20 0.0791 mg/l DS000 Accepted
Lead Jul 1, 2020 – Dec 31, 2020 20 0.0009 mg/l DS000 Accepted
Copper Jul 1, 2019 – Dec 31, 2019 19 0.1066 mg/l DS000 Accepted
Lead Jul 1, 2019 – Dec 31, 2019 19 0.0015 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.