Lead and copper

MS0420003 , MS Valley State University

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for MS Valley State University, 38 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2022 – Dec 31, 2024 10 0.38 mg/l DS000 Accepted
Lead Jan 1, 2022 – Dec 31, 2024 10 0.0021 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2021 10 0.409 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2021 10 0.0058 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2018 10 0.4476 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2018 10 0.0027 mg/l DS000 Accepted
Copper Jan 1, 2013 – Dec 31, 2015 10 0.1883 mg/l DS000 Accepted
Lead Jan 1, 2013 – Dec 31, 2015 10 0.0012 mg/l DS000 Accepted
Copper Jan 1, 2012 – Dec 31, 2012 10 0.3407 mg/l DS000 Accepted
Lead Jan 1, 2012 – Dec 31, 2012 10 0.0024 mg/l DS000 Accepted
Copper Jan 1, 2011 – Dec 31, 2011 10 0.4012 mg/l DS000 Accepted
Lead Jan 1, 2011 – Dec 31, 2011 10 0.0024 mg/l DS000 Accepted
Copper Jan 1, 2010 – Dec 31, 2010 11 0.7095 mg/l DS000 Accepted
Lead Jan 1, 2010 – Dec 31, 2010 11 0.0037 mg/l DS000 Accepted
Copper Jul 1, 2009 – Dec 31, 2009 20 0.5407 mg/l DS000 Accepted
Lead Jul 1, 2009 – Dec 31, 2009 20 0.0026 mg/l DS000 Accepted
Copper Jan 1, 2009 – Jun 30, 2009 21 0.6497 mg/l DS000 Accepted
Lead Jan 1, 2009 – Jun 30, 2009 21 0.0049 mg/l DS000 Accepted
Copper Jul 1, 2008 – Dec 31, 2008 22 1.709 mg/l DS000 Accepted
Lead Jul 1, 2008 – Dec 31, 2008 22 0.022 mg/l DS000 Accepted
Copper Jan 1, 2008 – Jun 30, 2008 19 0.7405 mg/l DS000 Accepted
Lead Jan 1, 2008 – Jun 30, 2008 19 0.0149 mg/l DS000 Accepted
Copper Jul 1, 2004 – Dec 31, 2004 20 1.0304 mg/l DS000 Accepted
Lead Jul 1, 2004 – Dec 31, 2004 20 0.0727 mg/l DS000 Accepted
Copper Jan 1, 2004 – Jun 30, 2004 20 0.2704 mg/l DS000 Accepted
Lead Jan 1, 2004 – Jun 30, 2004 20 0.0036 mg/l DS000 Accepted
Copper Jan 1, 2000 – Jun 30, 2000 21 0.37 mg/l DS000 Accepted
Lead Jan 1, 2000 – Jun 30, 2000 21 0.006 mg/l DS000 Accepted
Copper Jan 1, 1997 – Jun 30, 1997 10 0.337 mg/l DS000 Accepted
Lead Jan 1, 1997 – Jun 30, 1997 10 0.002 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1996 15 1.631 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1996 15 0.031 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 10 0.145 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 10 0.012 mg/l DS000 Accepted
Copper Jan 1, 1994 – Jun 30, 1994 22 0.823 mg/l DS000 Accepted
Lead Jan 1, 1994 – Jun 30, 1994 22 0.012 mg/l DS000 Accepted
Copper Jul 1, 1993 – Dec 31, 1993 24 0.529 mg/l DS000 Accepted
Lead Jul 1, 1993 – Dec 31, 1993 24 0.01 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.