This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0420043 , America's Catch Catfish Plant
15 of the 53 analytes this system has been tested for have been detected at least once, across 179 samples on record.
The other 38 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 179 samples on record, detections range from October 6, 2003 to March 10, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 62 of 62 results | Sep 14, 2004 | Aug 12, 2024 |
| Barium 1010 | Inorganic Chemical | 16 of 16 results | Oct 6, 2003 | Mar 10, 2025 |
| Fluoride 1025 | Inorganic Chemical | 16 of 16 results | Oct 6, 2003 | Mar 10, 2025 |
| Lead 1030 | Inorganic Chemical | 16 of 62 results | Sep 14, 2004 | Aug 12, 2024 |
| Chromium 1020 | Inorganic Chemical | 11 of 16 results | Oct 6, 2003 | Apr 29, 2020 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 5 of 8 results | Aug 20, 2007 | Feb 25, 2025 |
| TTHM 2950 | Organic Chemical | 5 of 8 results | Jun 28, 2004 | Feb 25, 2025 |
| Nickel 1036 | Inorganic Chemical | 4 of 16 results | Mar 1, 2004 | Jan 8, 2024 |
| Sodium 1052 | Inorganic Chemical | 2 of 2 results | Mar 2, 2022 | Mar 2, 2022 |
| Dichloroacetic Acid 2451 | Organic Chemical | 2 of 4 results | Jun 7, 2010 | Jul 24, 2013 |
| Chloroform 2941 | Organic Chemical | 2 of 5 results | Aug 20, 2007 | Jun 7, 2010 |
| Trichloroacetic Acid 2452 | Organic Chemical | 1 of 4 results | Jun 7, 2010 | Jun 7, 2010 |
| Dichloromethane 2964 | Organic Chemical | 1 of 16 results | Aug 9, 2004 | Aug 9, 2004 |
| Toluene 2991 | Organic Chemical | 1 of 16 results | Aug 9, 2004 | Aug 9, 2004 |
| Sulfate 1055 | Inorganic Chemical | 1 of 2 results | Oct 6, 2003 | Oct 6, 2003 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 11–20 of 179 samples, newest first — collected September 27, 2022 to August 12, 2024. The summary above covers all 179.
40 results from the 10 samples listed here: 9 detected, 31 not detected. Across the whole record it is 145 of 852. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
We withheld the location of 3 sampling points below. The location on record identifies a private home, and we do not publish those. That is our decision, not the agency’s. The sampling point, its type and every result taken there are published unchanged.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0257 mg/l , sample collected Aug 12, 2024 07:25, sampling point LC0008 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Aug 12, 2024 07:25, sampling point LC0008 | Lead 1030 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| 0.0528 mg/l , sample collected Aug 12, 2024 07:40, sampling point LC0006 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Aug 12, 2024 07:40, sampling point LC0006 | Lead 1030 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 18, 2024 13:10, sampling point TF102 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2024 – Dec 31, 2024 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 18, 2024 13:10, sampling point TF102 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2024 – Dec 31, 2024 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 18, 2024 13:10, sampling point TF102 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2024 – Dec 31, 2024 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 18, 2024 13:10, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2024 – Dec 31, 2024 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 18, 2024 13:10, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2024 – Dec 31, 2024 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 18, 2024 13:10, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2024 – Dec 31, 2024 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| 0.15 mg/l , sample collected Jan 8, 2024 13:00, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| 0.139 mg/l , sample collected Jan 8, 2024 13:00, sampling point TF102 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| 0.0011 mg/l , sample collected Jan 8, 2024 13:00, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 8, 2024 13:00, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2022 – Dec 31, 2024 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 28, 2023 14:00, sampling point TF102 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 28, 2023 14:00, sampling point TF102 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 28, 2023 14:00, sampling point TF102 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 28, 2023 14:00, sampling point TF101 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 28, 2023 14:00, sampling point TF101 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 28, 2023 14:00, sampling point TF101 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2023 – Dec 31, 2023 |
|
||
| 4.2 ug/l , sample collected Dec 7, 2022 13:30, sampling point SMD | Total Haloacetic Acids (Haa5) 2456 EPA method 552.2 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 3.09 ug/l , sample collected Dec 7, 2022 13:30, sampling point SMD | TTHM 2950 EPA method 524.2 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0033 mg/l , sample collected Sep 27, 2022 13:45, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.175 mg/l , sample collected Sep 27, 2022 13:45, sampling point TF101 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Sep 27, 2022 13:45, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
-
- Collected
- Aug 12, 2024 07:25
- Sampling point
- LC0008 Location withheld
- Sample type
- Routine
- Lab sample
- PB-240813-020
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0257 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Aug 12, 2024 07:40
- Sampling point
- LC0006 Location withheld
- Sample type
- Routine
- Lab sample
- PB-240813-019
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0528 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Mar 18, 2024 13:10
- Sampling point
- TF102
- Sample type
- Routine
- Lab sample
- NI-240319-003
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2024 – Dec 31, 2024
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Mar 18, 2024 13:10
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NI-240319-004
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2024 – Dec 31, 2024
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jan 8, 2024 13:00
- Sampling point
- TF102
- Sample type
- Routine
- Lab sample
- IN-240109-046
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Barium 1010 EPA method 200.8
- Result
- 0.15 mg/l
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.139 mg/l
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Nickel 1036 EPA method 200.8
- Result
- 0.0011 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2022 – Dec 31, 2024
-
- Collected
- Feb 28, 2023 14:00
- Sampling point
- TF102
- Sample type
- Routine
- Lab sample
- NI-230301-011
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2023 – Dec 31, 2023
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Feb 28, 2023 14:00
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- NI-230301-010
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2023 – Dec 31, 2023
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Dec 7, 2022 13:30
- Sampling point
- SMD Location withheld
- Sample type
- Routine
- Lab sample
- HA-221208-016
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Total Haloacetic Acids (Haa5) 2456 EPA method 552.2
- Result
- 4.2 ug/l
-
- Collected
- Dec 7, 2022 13:30
- Sampling point
- SMD Location withheld
- Sample type
- Routine
- Lab sample
- TH-221208-016
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
TTHM 2950 EPA method 524.2
- Result
- 3.09 ug/l
-
- Collected
- Sep 27, 2022 13:45
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-220928-025
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0033 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.175 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
Routine (10).