This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0420044 , Viking Specialty Products
21 of the 53 analytes this system has been tested for have been detected at least once, across 190 samples on record.
The other 32 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 190 samples on record, detections range from October 6, 2003 to October 13, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 75 of 75 results | Jul 27, 2006 | Oct 13, 2025 |
| Lead 1030 | Inorganic Chemical | 40 of 75 results | Jul 27, 2006 | Oct 13, 2025 |
| Xylenes, Total 2955 | Organic Chemical | 16 of 43 results | May 17, 2004 | Sep 27, 2016 |
| Ethylbenzene 2992 | Organic Chemical | 15 of 43 results | May 17, 2004 | Sep 27, 2016 |
| Barium 1010 | Inorganic Chemical | 11 of 11 results | Oct 6, 2003 | Mar 10, 2025 |
| Fluoride 1025 | Inorganic Chemical | 10 of 11 results | Oct 6, 2003 | Mar 10, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 10 of 12 results | Nov 17, 2005 | Mar 5, 2025 |
| TTHM 2950 | Organic Chemical | 10 of 13 results | Jun 30, 2004 | Mar 5, 2025 |
| Chromium 1020 | Inorganic Chemical | 6 of 11 results | Oct 6, 2003 | Mar 2, 2016 |
| Dichloroacetic Acid 2451 | Organic Chemical | 5 of 6 results | Jun 14, 2011 | Jul 11, 2018 |
| Chloroform 2941 | Organic Chemical | 5 of 6 results | Jun 14, 2011 | Jul 11, 2018 |
| Trichloroacetic Acid 2452 | Organic Chemical | 4 of 6 results | Jun 14, 2011 | Jul 11, 2018 |
| Toluene 2991 | Organic Chemical | 4 of 43 results | Aug 9, 2004 | Nov 2, 2009 |
| Bromodichloromethane 2943 | Organic Chemical | 2 of 6 results | Jul 9, 2014 | Aug 26, 2015 |
| Sodium 1052 | Inorganic Chemical | 1 of 1 result | Mar 1, 2022 | Mar 1, 2022 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 6 results | Nov 13, 2017 | Nov 13, 2017 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 6 results | Jul 9, 2014 | Jul 9, 2014 |
| Dibromochloromethane 2944 | Organic Chemical | 1 of 6 results | Jul 9, 2014 | Jul 9, 2014 |
| Nickel 1036 | Inorganic Chemical | 1 of 11 results | May 12, 2010 | May 12, 2010 |
| Arsenic 1005 | Inorganic Chemical | 1 of 11 results | Mar 8, 2006 | Mar 8, 2006 |
| Selenium 1045 | Inorganic Chemical | 1 of 11 results | Mar 8, 2006 | Mar 8, 2006 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 181–190 of 190 samples, newest first — collected October 6, 2003 to September 8, 2004. The summary above covers all 190.
94 results from the 10 samples listed here: 12 detected, 82 not detected. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
Units in this table
Ethylbenzene is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Toluene is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
Xylenes, Total is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Sep 8, 2004, sampling point MRT000 | Total Haloacetic Acids (Haa5) 2456 EPA method 552.2 | Jan 1, 2004 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| 16.8 ug/l , sample collected Aug 9, 2004, sampling point TF101 | Xylenes, Total 2955 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Dichloromethane 2964 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | O-Dichlorobenzene 2968 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | P-Dichlorobenzene 2969 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Vinyl Chloride 2976 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Carbon Tetrachloride 2982 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Trichloroethylene 2984 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Tetrachloroethylene 2987 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Chlorobenzene 2989 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Benzene 2990 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| 1.14 ug/l , sample collected Aug 9, 2004, sampling point TF101 | Toluene 2991 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| 2.65 ug/l , sample collected Aug 9, 2004, sampling point TF101 | Ethylbenzene 2992 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Aug 9, 2004, sampling point TF101 | Styrene 2996 EPA method 524.2 | Jul 1, 2004 – Sep 30, 2004 |
|
||
| 66.6 ug/l , sample collected Jun 30, 2004, sampling point MRT000 | TTHM 2950 EPA method 524.2 | Jan 1, 2004 – Dec 31, 2004 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Jun 7, 2004, sampling point TF101 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2004 – Dec 31, 2004 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Jun 7, 2004, sampling point TF101 | Nitrate 1040 EPA method 353.2 | Jan 1, 2004 – Dec 31, 2004 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Jun 7, 2004, sampling point TF101 | Nitrite 1041 EPA method 353.2 | Jan 1, 2004 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| 5.78 ug/l , sample collected May 17, 2004, sampling point TF101 | Xylenes, Total 2955 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Dichloromethane 2964 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | O-Dichlorobenzene 2968 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | P-Dichlorobenzene 2969 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Vinyl Chloride 2976 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | 1,2-Dichloroethane 2980 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Carbon Tetrachloride 2982 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | 1,2-Dichloropropane 2983 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Trichloroethylene 2984 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Tetrachloroethylene 2987 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Chlorobenzene 2989 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Benzene 2990 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Toluene 2991 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| 0.85 ug/l , sample collected May 17, 2004, sampling point TF101 | Ethylbenzene 2992 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected May 17, 2004, sampling point TF101 | Styrene 2996 EPA method 524.2 | Apr 1, 2004 – Jun 30, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.012 mg/l , sample collected Mar 3, 2004, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.001 mg/l , sample collected Mar 3, 2004, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.237 mg/l , sample collected Mar 3, 2004, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 3, 2004, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Xylenes, Total 2955 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Dichloromethane 2964 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | O-Dichlorobenzene 2968 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | P-Dichlorobenzene 2969 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Vinyl Chloride 2976 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | 1,1-Dichloroethylene 2977 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | 1,2-Dichloroethane 2980 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | 1,1,1-Trichloroethane 2981 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Carbon Tetrachloride 2982 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | 1,2-Dichloropropane 2983 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Trichloroethylene 2984 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | 1,1,2-Trichloroethane 2985 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Tetrachloroethylene 2987 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Chlorobenzene 2989 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Benzene 2990 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Toluene 2991 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Ethylbenzene 2992 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Feb 17, 2004, sampling point TF101 | Styrene 2996 | Jan 1, 2004 – Mar 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.009 mg/l , sample collected Oct 6, 2003, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.002 mg/l , sample collected Oct 6, 2003, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.212 mg/l , sample collected Oct 6, 2003, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 2.5 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Oct 6, 2003, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
-
- Collected
- Sep 8, 2004
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 040909-006HA
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Dec 31, 2004
-
Total Haloacetic Acids (Haa5) 2456 EPA method 552.2
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Aug 9, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040810-063VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2004 – Sep 30, 2004
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955 EPA method 524.2
- Result
- 16.8 ug/l
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991 EPA method 524.2
- Result
- 1.14 ug/l
-
Ethylbenzene 2992 EPA method 524.2
- Result
- 2.65 ug/l
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Jun 30, 2004
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 040701-013TH
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Dec 31, 2004
-
TTHM 2950 EPA method 524.2
- Result
- 66.6 ug/l
-
- Collected
- Jun 7, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040608-213NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Dec 31, 2004
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- May 17, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040518-003VO
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2004 – Jun 30, 2004
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955 EPA method 524.2
- Result
- 5.78 ug/l
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992 EPA method 524.2
- Result
- 0.85 ug/l
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Mar 3, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040304-060CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Mar 3, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040304-046IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.012 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.237 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Feb 17, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040218-120VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Mar 31, 2004
-
1,2,4-Trichlorobenzene 2378
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Oct 6, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 031007-050IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.009 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.002 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Fluoride 1025 EPA method 300.0
- Result
- 0.212 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Sulfate 1055 EPA method 300.0
- Result
- Not detected below 2.5 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Oct 6, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 031007-047CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
Routine (10).