Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Chemical and radiological sample results

MS0440097 , South Lowndes W/A

23 of the 57 analytes this system has been tested for have been detected at least once, across 184 samples on record.

The other 34 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 184 samples on record, detections range from October 6, 2003 to September 9, 2025. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for South Lowndes W/A, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 35 of 35 results Sep 20, 2004 Sep 18, 2023
Barium 1010 Inorganic Chemical 16 of 16 results Oct 6, 2003 Sep 9, 2025
Fluoride 1025 Inorganic Chemical 14 of 16 results Oct 6, 2003 Sep 9, 2025
TTHM 2950 Organic Chemical 11 of 18 results Sep 17, 2007 Mar 6, 2025
Gross Alpha, Incl. Radon & U 4002 Radionuclide 10 of 10 results Dec 6, 2011 Jul 10, 2012
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 9 of 18 results Aug 20, 2007 Mar 6, 2025
Chromium 1020 Inorganic Chemical 9 of 16 results Oct 6, 2003 May 5, 2020
Chloroform 2941 Organic Chemical 6 of 15 results May 20, 2024 Mar 6, 2025
Nitrate-Nitrite 1038 Inorganic Chemical 4 of 37 results Nov 13, 2019 Mar 19, 2025
Nitrate 1040 Inorganic Chemical 4 of 37 results Nov 13, 2019 Mar 19, 2025
Bromoform 2942 Organic Chemical 4 of 15 results Aug 21, 2024 Nov 6, 2024
Bromodichloromethane 2943 Organic Chemical 4 of 15 results May 20, 2024 Nov 6, 2024
Dibromochloromethane 2944 Organic Chemical 4 of 15 results May 20, 2024 Nov 6, 2024
Dichloroacetic Acid 2451 Organic Chemical 4 of 14 results May 20, 2024 Aug 21, 2024
Xylenes, Total 2955 Organic Chemical 4 of 28 results Dec 18, 2006 Nov 2, 2009
Nickel 1036 Inorganic Chemical 3 of 16 results Dec 5, 2006 Mar 31, 2014
Trichloroacetic Acid 2452 Organic Chemical 2 of 14 results Mar 6, 2025 Mar 6, 2025
Dibromoacetic Acid 2454 Organic Chemical 2 of 14 results Aug 21, 2024 Aug 21, 2024
Nitrite 1041 Inorganic Chemical 2 of 37 results Nov 22, 2021 Nov 22, 2021
Sodium 1052 Inorganic Chemical 2 of 2 results Oct 14, 2019 Oct 14, 2019
Lead 1030 Inorganic Chemical 2 of 35 results Jul 10, 2017 Jul 10, 2017
Ethylbenzene 2992 Organic Chemical 2 of 28 results Aug 12, 2008 Oct 21, 2008
Selenium 1045 Inorganic Chemical 1 of 16 results Apr 14, 2008 Apr 14, 2008

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 111–120 of 184 samples, newest first — collected April 18, 2011 to December 6, 2011. The summary above covers all 184.

51 results from the 10 samples listed here: 9 detected, 42 not detected. Across the whole record it is 154 of 1,182. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for South Lowndes W/A, every result from 111 to 120 of 184 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Dec 6, 2011 13:55
Sampling point
TF102
Sample type
Routine
Lab sample
111207-060
Laboratory
Radiation Safety Engineering
0.8 pci/l , sample collected Dec 6, 2011 13:55, sampling point TF102 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.47 pci/l Minimum Reporting Level , sample collected Dec 6, 2011 13:55, sampling point TF102 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.409 pci/l Minimum Reporting Level , sample collected Dec 6, 2011 13:55, sampling point TF102 Radium-226 4020 EPA method 903.1 Oct 1, 2011 – Dec 31, 2011
Not detected below 0.47 pci/l Minimum Reporting Level , sample collected Dec 6, 2011 13:55, sampling point TF102 Radium-228 4030 EPA method 904.0 Oct 1, 2011 – Dec 31, 2011
Collected
Dec 6, 2011 13:15
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
111207-059
Laboratory
Radiation Safety Engineering
1.4 pci/l , sample collected Dec 6, 2011 13:15, sampling point TF101 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.68 pci/l Minimum Reporting Level , sample collected Dec 6, 2011 13:15, sampling point TF101 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.493 pci/l Minimum Reporting Level , sample collected Dec 6, 2011 13:15, sampling point TF101 Radium-226 4020 EPA method 903.1 Oct 1, 2011 – Dec 31, 2011
Not detected below 0.68 pci/l Minimum Reporting Level , sample collected Dec 6, 2011 13:15, sampling point TF101 Radium-228 4030 EPA method 904.0 Oct 1, 2011 – Dec 31, 2011
Collected
Jun 27, 2011 01:05
Sampling point
TF102
Sample type
Routine
Lab sample
110628-020VO
Laboratory
MSDH Lab
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 1,2,4-Trichlorobenzene 2378 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Cis-1,2-Dichloroethylene 2380 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Xylenes, Total 2955 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Dichloromethane 2964 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 O-Dichlorobenzene 2968 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 P-Dichlorobenzene 2969 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Vinyl Chloride 2976 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 1,1-Dichloroethylene 2977 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Trans-1,2-Dichloroethylene 2979 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 1,2-Dichloroethane 2980 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 1,1,1-Trichloroethane 2981 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Carbon Tetrachloride 2982 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 1,2-Dichloropropane 2983 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Trichloroethylene 2984 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 1,1,2-Trichloroethane 2985 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Tetrachloroethylene 2987 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Chlorobenzene 2989 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Benzene 2990 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Toluene 2991 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Ethylbenzene 2992 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jun 27, 2011 01:05, sampling point TF102 Styrene 2996 EPA method 524.2 Jan 1, 2011 – Dec 31, 2011
Collected
Jun 14, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110615-013PB
Laboratory
MSDH Lab
0.0149 mg/l , sample collected Jun 14, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 14, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
Jun 13, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110615-016PB
Laboratory
MSDH Lab
0.0634 mg/l , sample collected Jun 13, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 13, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
Jun 13, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110615-015PB
Laboratory
MSDH Lab
0.1831 mg/l , sample collected Jun 13, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 13, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
Jun 13, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110615-014PB
Laboratory
MSDH Lab
0.012 mg/l , sample collected Jun 13, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 13, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
Jun 13, 2011
Sampling point
DS000 Distribution
Sample type
Routine
Lab sample
110615-012PB
Laboratory
MSDH Lab
0.2188 mg/l , sample collected Jun 13, 2011, sampling point DS000 Copper, Free 1022 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 13, 2011, sampling point DS000 Lead 1030 EPA method 200.8 Jan 1, 2009 – Dec 31, 2011
Collected
May 2, 2011
Sampling point
TF102
Sample type
Routine
Lab sample
110503-019CN
Laboratory
MSDH Lab
Not detected below 15 ug/l Minimum Reporting Level , sample collected May 2, 2011, sampling point TF102 Cyanide 1024 EPA method QC10204001X Jan 1, 2010 – Dec 31, 2012
Collected
Apr 18, 2011
Sampling point
TF102
Sample type
Routine
Lab sample
110419-065IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Arsenic 1005 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
0.048971 mg/l , sample collected Apr 18, 2011, sampling point TF102 Barium 1010 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Cadmium 1015 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Chromium 1020 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
0.104 mg/l , sample collected Apr 18, 2011, sampling point TF102 Fluoride 1025 EPA method 380-75WE Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Mercury 1035 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Selenium 1045 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Antimony, Total 1074 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 18, 2011, sampling point TF102 Thallium, Total 1085 EPA method 200.8 Jan 1, 2010 – Dec 31, 2012

Routine (10).