This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0450005 , Cameron Community Water System, Inc
25 of the 57 analytes this system has been tested for have been detected at least once, across 269 samples on record.
The other 32 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 269 samples on record, detections range from November 24, 2003 to April 23, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 62 of 62 results | Sep 21, 2004 | Sep 11, 2023 |
| Lead 1030 | Inorganic Chemical | 43 of 62 results | Sep 21, 2004 | Sep 11, 2023 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 40 of 40 results | Aug 2, 2004 | Apr 23, 2025 |
| TTHM 2950 | Organic Chemical | 39 of 39 results | Aug 2, 2004 | Apr 23, 2025 |
| Chloroform 2941 | Organic Chemical | 30 of 30 results | May 25, 2006 | Jul 10, 2018 |
| Bromodichloromethane 2943 | Organic Chemical | 28 of 30 results | May 25, 2006 | Jul 10, 2018 |
| Dichloroacetic Acid 2451 | Organic Chemical | 24 of 24 results | Jan 30, 2008 | Nov 12, 2020 |
| Trichloroacetic Acid 2452 | Organic Chemical | 24 of 24 results | Jan 30, 2008 | Nov 12, 2020 |
| Barium 1010 | Inorganic Chemical | 20 of 20 results | Nov 24, 2003 | Mar 11, 2025 |
| Fluoride 1025 | Inorganic Chemical | 18 of 20 results | Nov 24, 2003 | Mar 11, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 12 of 12 results | Dec 13, 2011 | Sep 16, 2019 |
| Chromium 1020 | Inorganic Chemical | 12 of 20 results | Nov 24, 2003 | Nov 23, 2015 |
| Monochloroacetic Acid 2450 | Organic Chemical | 9 of 24 results | Aug 26, 2008 | Nov 12, 2020 |
| Sodium 1052 | Inorganic Chemical | 6 of 6 results | Sep 29, 2019 | Feb 25, 2025 |
| Selenium 1045 | Inorganic Chemical | 4 of 20 results | Nov 24, 2003 | Apr 4, 2005 |
| Sulfate 1055 | Inorganic Chemical | 4 of 4 results | Nov 24, 2003 | Mar 8, 2004 |
| Nickel 1036 | Inorganic Chemical | 3 of 20 results | Nov 24, 2003 | Mar 20, 2006 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 2 of 12 results | Jun 12, 2018 | Sep 16, 2019 |
| Radium-226 4020 | Radionuclide | 2 of 12 results | Jun 12, 2018 | Sep 16, 2019 |
| Radium-228 4030 | Radionuclide | 1 of 12 results | Jun 12, 2018 | Jun 12, 2018 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 15 results | Jul 21, 2016 | Jul 21, 2016 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 24 results | Aug 17, 2009 | Aug 17, 2009 |
| Dibromoacetic Acid 2454 | Organic Chemical | 1 of 24 results | Aug 17, 2009 | Aug 17, 2009 |
| Dibromochloromethane 2944 | Organic Chemical | 1 of 30 results | May 18, 2009 | May 18, 2009 |
| Arsenic 1005 | Inorganic Chemical | 1 of 20 results | Apr 4, 2005 | Apr 4, 2005 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 121–130 of 269 samples, newest first — collected April 23, 2012 to July 16, 2012. The summary above covers all 269.
42 results from the 10 samples listed here: 8 detected, 34 not detected. Across the whole record it is 388 of 1,197. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 1 pci/l , sample collected Jul 16, 2012 13:30, sampling point TF102 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 13:30, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.347 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 13:30, sampling point TF102 | Radium-226 4020 EPA method 903.1 | Jul 1, 2012 – Sep 30, 2012 |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 13:30, sampling point TF102 | Radium-228 4030 EPA method 904.0 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| 0.8 pci/l , sample collected Jul 16, 2012 14:00, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 14:00, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.352 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 14:00, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Jul 1, 2012 – Sep 30, 2012 |
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 14:00, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 16, 2012 13:30, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 16, 2012 14:00, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.00849 mg/l , sample collected Jul 11, 2012 01:30, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.137 mg/l , sample collected Jul 11, 2012 01:30, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 01:30, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.00878 mg/l , sample collected Jul 11, 2012 02:00, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.132 mg/l , sample collected Jul 11, 2012 02:00, sampling point TF101 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 11, 2012 02:00, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 1 pci/l , sample collected Apr 23, 2012 13:00, sampling point TF102 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 13:00, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.347 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 13:00, sampling point TF102 | Radium-226 4020 EPA method 903.1 | Apr 1, 2012 – Jun 30, 2012 |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 13:00, sampling point TF102 | Radium-228 4030 EPA method 904.0 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| 0.8 pci/l , sample collected Apr 23, 2012 13:30, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 13:30, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.352 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 13:30, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Apr 1, 2012 – Jun 30, 2012 |
| Not detected below 0.4 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 13:30, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 23, 2012 13:00, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 23, 2012 13:30, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Apr 1, 2012 – Jun 30, 2012 |
-
- Collected
- Jul 16, 2012 13:30
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120718-007
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 1 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.347 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
- Collected
- Jul 16, 2012 14:00
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120718-006
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.8 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.352 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
- Collected
- Jul 16, 2012 13:30
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120718-007RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jul 16, 2012 14:00
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120718-006RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jul 11, 2012 01:30
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120712-021IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.00849 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.137 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- Jul 11, 2012 02:00
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120712-020IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.00878 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.132 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- Apr 23, 2012 13:00
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120424-047
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 1 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.347 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
- Collected
- Apr 23, 2012 13:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120424-046
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.8 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.352 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.4 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
- Collected
- Apr 23, 2012 13:00
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120424-047RU
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Apr 23, 2012 13:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120424-046RU
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
Routine (10).