This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0460011 , Morgantown Water Association
14 of the 56 analytes this system has been tested for have been detected at least once, across 117 samples on record.
The other 42 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 117 samples on record, detections range from October 8, 2003 to February 4, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 36 of 36 results | Sep 23, 2004 | Sep 6, 2023 |
| Lead 1030 | Inorganic Chemical | 24 of 36 results | Sep 23, 2004 | Sep 6, 2023 |
| Barium 1010 | Inorganic Chemical | 8 of 8 results | Oct 8, 2003 | Feb 7, 2024 |
| Fluoride 1025 | Inorganic Chemical | 7 of 8 results | Oct 8, 2003 | Feb 7, 2024 |
| Chromium 1020 | Inorganic Chemical | 5 of 8 results | Oct 8, 2003 | Feb 29, 2016 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 3 of 21 results | Mar 7, 2018 | Feb 4, 2026 |
| Nitrate 1040 | Inorganic Chemical | 3 of 21 results | Mar 7, 2018 | Feb 4, 2026 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 18, 2019 | Feb 26, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 2 of 7 results | Jun 9, 2010 | Oct 18, 2022 |
| TTHM 2950 | Organic Chemical | 2 of 7 results | Sep 17, 2007 | Jun 9, 2010 |
| Sulfate 1055 | Inorganic Chemical | 2 of 2 results | Oct 8, 2003 | Mar 8, 2004 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 1 of 6 results | Dec 15, 2015 | Dec 15, 2015 |
| Radium-226 4020 | Radionuclide | 1 of 6 results | Dec 15, 2015 | Dec 15, 2015 |
| Nickel 1036 | Inorganic Chemical | 1 of 8 results | Oct 18, 2010 | Oct 18, 2010 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 21–30 of 117 samples, newest first — collected August 16, 2017 to July 24, 2020. The summary above covers all 117.
29 results from the 10 samples listed here: 13 detected, 16 not detected. Across the whole record it is 98 of 485. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0073 mg/l , sample collected Jul 24, 2020 04:30, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0006 mg/l , sample collected Jul 24, 2020 04:30, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0057 mg/l , sample collected Jul 24, 2020 06:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0005 mg/l , sample collected Jul 24, 2020 06:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0102 mg/l , sample collected Jul 23, 2020 06:20, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0036 mg/l , sample collected Jul 23, 2020 06:20, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.11 mg/l , sample collected Apr 8, 2020 14:45, sampling point WL001 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
| 0.1 mg/l , sample collected Apr 8, 2020 14:45, sampling point WL001 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Apr 8, 2020 14:45, sampling point WL001 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2020 – Dec 31, 2020 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 12:30, sampling point WL001 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 12:30, sampling point WL001 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 12:30, sampling point WL001 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2019 – Dec 31, 2019 |
|
||
| 49000 ug/l , sample collected Sep 18, 2019 12:10, sampling point WL001 | Sodium 1052 EPA method 200.7 | Not recorded |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Arsenic 1005 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0071 mg/l , sample collected Apr 10, 2019 13:35, sampling point WL001 | Barium 1010 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Cadmium 1015 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Chromium 1020 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.167 mg/l , sample collected Apr 10, 2019 13:35, sampling point WL001 | Fluoride 1025 EPA method 300.0 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Mercury 1035 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Selenium 1045 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:35, sampling point WL001 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Apr 10, 2019 13:40, sampling point WL001 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2017 – Dec 31, 2019 |
|
||
| 0.21 mg/l , sample collected Mar 7, 2018 12:30, sampling point WL001 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2018 – Dec 31, 2018 |
| 0.21 mg/l , sample collected Mar 7, 2018 12:30, sampling point WL001 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 7, 2018 12:30, sampling point WL001 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2018 – Dec 31, 2018 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 16, 2017 13:30, sampling point WL001 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2017 – Sep 30, 2017 |
-
- Collected
- Jul 24, 2020 04:30
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200727-019PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0073 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0006 mg/l
-
- Collected
- Jul 24, 2020 06:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200727-018PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0057 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0005 mg/l
-
- Collected
- Jul 23, 2020 06:20
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 200727-020PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0102 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0036 mg/l
-
- Collected
- Apr 8, 2020 14:45
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 200409-059NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2020
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- 0.11 mg/l
-
Nitrate 1040 EPA method QC10107041C
- Result
- 0.1 mg/l
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Nov 13, 2019 12:30
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 191114-002NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2019 – Dec 31, 2019
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Sep 18, 2019 12:10
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 680-174388-202
- Laboratory
- Test America-Savannah
- Monitoring period
- Not recorded
-
Sodium 1052 EPA method 200.7
- Result
- 49000 ug/l
-
- Collected
- Apr 10, 2019 13:35
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 190411-021IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Barium 1010 EPA method 200.8
- Result
- 0.0071 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Fluoride 1025 EPA method 300.0
- Result
- 0.167 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
- Collected
- Apr 10, 2019 13:40
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 190411-018CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Mar 7, 2018 12:30
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 180308-010NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2018
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- 0.21 mg/l
-
Nitrate 1040 EPA method QC10107041C
- Result
- 0.21 mg/l
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Aug 16, 2017 13:30
- Sampling point
- WL001 Well W001
- Sample type
- Routine
- Lab sample
- 170818-006RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jul 1, 2017 – Sep 30, 2017
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
Routine (10).