This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0460013 , West Marion Water Association
19 of the 56 analytes this system has been tested for have been detected at least once, across 241 samples on record.
The other 37 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 241 samples on record, detections range from October 8, 2003 to July 7, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 60 of 60 results | Jul 31, 2007 | Sep 6, 2023 |
| Lead 1030 | Inorganic Chemical | 32 of 60 results | Jul 31, 2007 | Sep 6, 2023 |
| Barium 1010 | Inorganic Chemical | 22 of 22 results | Oct 8, 2003 | Oct 8, 2025 |
| Fluoride 1025 | Inorganic Chemical | 21 of 22 results | Oct 8, 2003 | Oct 8, 2025 |
| TTHM 2950 | Organic Chemical | 19 of 19 results | Jul 12, 2004 | Aug 18, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 14 of 20 results | Aug 20, 2007 | Aug 18, 2025 |
| Chloroform 2941 | Organic Chemical | 14 of 14 results | Aug 20, 2007 | Aug 18, 2025 |
| Bromodichloromethane 2943 | Organic Chemical | 11 of 14 results | Aug 20, 2007 | Aug 18, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 10 of 14 results | Aug 20, 2007 | Aug 18, 2025 |
| Chromium 1020 | Inorganic Chemical | 10 of 22 results | Mar 8, 2004 | Jul 9, 2025 |
| Dichloroacetic Acid 2451 | Organic Chemical | 9 of 14 results | Jun 15, 2010 | Aug 18, 2025 |
| Trichloroacetic Acid 2452 | Organic Chemical | 9 of 14 results | Aug 13, 2013 | Aug 18, 2025 |
| Sodium 1052 | Inorganic Chemical | 7 of 7 results | Sep 17, 2019 | Jul 7, 2026 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 10 results | Mar 12, 2012 | Oct 10, 2012 |
| Nickel 1036 | Inorganic Chemical | 4 of 22 results | Sep 27, 2022 | Apr 7, 2025 |
| Sulfate 1055 | Inorganic Chemical | 4 of 4 results | Oct 8, 2003 | Mar 8, 2004 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 22 results | Apr 1, 2025 | Apr 1, 2025 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 14 results | Sep 14, 2020 | Sep 14, 2020 |
| Nitrite 1041 | Inorganic Chemical | 1 of 48 results | Aug 22, 2005 | Aug 22, 2005 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 161–170 of 241 samples, newest first — collected February 27, 2012 to July 9, 2012. The summary above covers all 241.
34 results from the 10 samples listed here: 5 detected, 29 not detected. Across the whole record it is 254 of 1,224. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.00473 mg/l , sample collected Jul 9, 2012 02:40, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.00115 mg/l , sample collected Jul 9, 2012 02:40, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.158 mg/l , sample collected Jul 9, 2012 02:40, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 9, 2012 02:40, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.4 pci/l , sample collected May 21, 2012 14:00, sampling point TF102 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.47 pci/l Minimum Reporting Level , sample collected May 21, 2012 14:00, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.47 pci/l Minimum Reporting Level , sample collected May 21, 2012 14:00, sampling point TF102 | Radium-226 4020 EPA method 903.1 | Apr 1, 2012 – Jun 30, 2012 |
| Not detected below 0.39 pci/l Minimum Reporting Level , sample collected May 21, 2012 14:00, sampling point TF102 | Radium-228 4030 EPA method 904.0 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.31 pci/l Minimum Reporting Level , sample collected May 21, 2012 13:15, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.552 pci/l Minimum Reporting Level , sample collected May 21, 2012 13:15, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.552 pci/l Minimum Reporting Level , sample collected May 21, 2012 13:15, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Apr 1, 2012 – Jun 30, 2012 |
| Not detected below 0.46 pci/l Minimum Reporting Level , sample collected May 21, 2012 13:15, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 21, 2012 13:15, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 21, 2012 14:00, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Apr 1, 2012 – Jun 30, 2012 |
|
||
| 0.4 pci/l , sample collected Mar 12, 2012 12:53, sampling point TF102 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.47 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 12:53, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.47 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 12:53, sampling point TF102 | Radium-226 4020 EPA method 903.1 | Jan 1, 2012 – Mar 31, 2012 |
| Not detected below 0.39 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 12:53, sampling point TF102 | Radium-228 4030 EPA method 904.0 | Jan 1, 2012 – Mar 31, 2012 |
|
||
| Not detected below 0.31 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 13:25, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.552 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 13:25, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.552 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 13:25, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Jan 1, 2012 – Mar 31, 2012 |
| Not detected below 0.46 pci/l Minimum Reporting Level , sample collected Mar 12, 2012 13:25, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Jan 1, 2012 – Mar 31, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 12, 2012 13:25, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Jan 1, 2012 – Mar 31, 2012 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 12, 2012 12:53, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Jan 1, 2012 – Mar 31, 2012 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Feb 27, 2012 10:05, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Feb 27, 2012 10:05, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Feb 27, 2012 10:05, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2012 – Dec 31, 2012 |
-
- Collected
- Jul 9, 2012 02:40
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120710-027IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.00473 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- 0.00115 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.158 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- May 21, 2012 14:00
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120522-092
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.4 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.47 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.47 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.39 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
- Collected
- May 21, 2012 13:15
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120522-142
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- Not detected below 0.31 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.552 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.552 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.46 pci/l Minimum Reporting Level
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
- Collected
- May 21, 2012 13:15
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120522-142RU
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- May 21, 2012 14:00
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120522-092RU
- Laboratory
- MSDH Lab
- Monitoring period
- Apr 1, 2012 – Jun 30, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Mar 12, 2012 12:53
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120313-010
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 0.4 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.47 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.47 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2012 – Mar 31, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.39 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2012 – Mar 31, 2012
-
- Collected
- Mar 12, 2012 13:25
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120313-131
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- Not detected below 0.31 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.552 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.552 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2012 – Mar 31, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.46 pci/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2012 – Mar 31, 2012
-
- Collected
- Mar 12, 2012 13:25
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120313-131RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2012 – Mar 31, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Mar 12, 2012 12:53
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120313-010RU
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2012 – Mar 31, 2012
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Feb 27, 2012 10:05
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 120228-062NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2012 – Dec 31, 2012
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
Routine (10).