Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0520001 , Town of Brooksville

Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for Town of Brooksville, 22 summaries, every one on record. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2021 – Dec 31, 2023 10 0.43 mg/l DS000 Accepted
Lead Jan 1, 2021 – Dec 31, 2023 10 0.0006 mg/l DS000 Accepted
Copper Jan 1, 2018 – Dec 31, 2020 10 0.2607 mg/l DS000 Accepted
Lead Jan 1, 2018 – Dec 31, 2020 10 0.0014 mg/l DS000 Accepted
Copper Jan 1, 2015 – Dec 31, 2017 10 0.0674 mg/l DS000 Accepted
Lead Jan 1, 2015 – Dec 31, 2017 10 0 mg/l DS000 Accepted
Copper Jan 1, 2012 – Dec 31, 2014 10 0.0911 mg/l DS000 Accepted
Lead Jan 1, 2012 – Dec 31, 2014 10 0.0006 mg/l DS000 Accepted
Copper Jan 1, 2009 – Dec 31, 2011 10 0.0161 mg/l DS000 Accepted
Lead Jan 1, 2009 – Dec 31, 2011 10 0.0008 mg/l DS000 Accepted
Copper Jan 1, 2006 – Dec 31, 2008 10 0.007 mg/l DS000 Accepted
Lead Jan 1, 2006 – Dec 31, 2008 10 0 mg/l DS000 Accepted
Copper Jan 1, 2000 – Dec 31, 2002 10 0.343 mg/l DS000 Accepted
Lead Jan 1, 2000 – Dec 31, 2002 10 0.003 mg/l DS000 Accepted
Copper Jan 1, 1996 – Dec 31, 1996 10 0.199 mg/l DS000 Accepted
Lead Jan 1, 1996 – Dec 31, 1996 10 0.003 mg/l DS000 Accepted
Copper Jan 1, 1995 – Dec 31, 1995 10 0.172 mg/l DS000 Accepted
Lead Jan 1, 1995 – Dec 31, 1995 10 0.007 mg/l DS000 Accepted
Copper Jan 1, 1994 – Jun 30, 1994 21 0.339 mg/l DS000 Accepted
Lead Jan 1, 1994 – Jun 30, 1994 21 0.013 mg/l DS000 Accepted
Copper Jul 1, 1993 – Dec 31, 1993 21 0.237 mg/l DS000 Accepted
Lead Jul 1, 1993 – Dec 31, 1993 21 0.01 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.