Chemical and radiological sample results

MS0540003 , Love Joy Water Assn

15 of the 57 analytes this system has been tested for have been detected at least once, across 152 samples on record.

The other 42 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 152 samples on record, detections range from October 13, 2003 to March 24, 2026. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Love Joy Water Assn, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 62 of 62 results Aug 9, 2007 Sep 13, 2023
Lead 1030 Inorganic Chemical 24 of 62 results Aug 9, 2007 Sep 12, 2023
Barium 1010 Inorganic Chemical 10 of 10 results Oct 13, 2003 Mar 25, 2025
Nickel 1036 Inorganic Chemical 8 of 10 results Oct 13, 2003 Mar 25, 2025
TTHM 2950 Organic Chemical 7 of 21 results Jul 26, 2004 Mar 24, 2026
Gross Alpha, Incl. Radon & U 4002 Radionuclide 5 of 5 results Dec 13, 2011 Jul 17, 2012
Bromodichloromethane 2943 Organic Chemical 4 of 16 results Mar 5, 2025 Mar 24, 2026
Dibromochloromethane 2944 Organic Chemical 4 of 16 results Mar 5, 2025 Mar 24, 2026
Fluoride 1025 Inorganic Chemical 2 of 10 results Nov 1, 2004 Mar 25, 2025
Sodium 1052 Inorganic Chemical 1 of 1 result Sep 18, 2019 Sep 18, 2019
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 1 of 20 results Jun 21, 2010 Jun 21, 2010
Cadmium 1015 Inorganic Chemical 1 of 10 results Apr 11, 2005 Apr 11, 2005
Chromium 1020 Inorganic Chemical 1 of 10 results Apr 11, 2005 Apr 11, 2005
Selenium 1045 Inorganic Chemical 1 of 10 results Apr 11, 2005 Apr 11, 2005
Sulfate 1055 Inorganic Chemical 1 of 1 result Oct 13, 2003 Oct 13, 2003

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 91–100 of 152 samples, newest first — collected February 13, 2012 to June 3, 2013. The summary above covers all 152.

36 results from the 10 samples listed here: 6 detected, 30 not detected. Across the whole record it is 132 of 663. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Love Joy Water Assn, every result from 91 to 100 of 152 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Jun 3, 2013 02:05
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
130604-017CN
Laboratory
MSDH Lab
Not detected below 15 ug/l Minimum Reporting Level , sample collected Jun 3, 2013 02:05, sampling point TF080 Cyanide 1024 EPA method QC10204001X Jan 1, 2011 – Dec 31, 2013
Collected
Apr 29, 2013 12:40
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
130430-018IN
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Arsenic 1005 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
0.0385 mg/l , sample collected Apr 29, 2013 12:40, sampling point TF080 Barium 1010 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Cadmium 1015 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Chromium 1020 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Fluoride 1025 EPA method 300.0 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Mercury 1035 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
0.0051 mg/l , sample collected Apr 29, 2013 12:40, sampling point TF080 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Selenium 1045 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Antimony, Total 1074 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 29, 2013 12:40, sampling point TF080 Thallium, Total 1085 EPA method 200.8 Jan 1, 2011 – Dec 31, 2013
Collected
Mar 4, 2013 01:15
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
130305-098NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 4, 2013 01:15, sampling point TF080 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2013 – Dec 31, 2013
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 4, 2013 01:15, sampling point TF080 Nitrate 1040 EPA method 353.2 Jan 1, 2013 – Dec 31, 2013
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 4, 2013 01:15, sampling point TF080 Nitrite 1041 EPA method 353.2 Jan 1, 2013 – Dec 31, 2013
Collected
Jul 17, 2012 15:00
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
201211140273
Laboratory
Radiation Safety Engineering
1.2 pci/l , sample collected Jul 17, 2012 15:00, sampling point TF080 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Jul 17, 2012 15:00, sampling point TF080 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Jul 17, 2012 15:00, sampling point TF080 Radium-226 4020 EPA method 903.1 Jul 1, 2012 – Sep 30, 2012
Not detected below 0.39 pci/l Minimum Reporting Level , sample collected Jul 17, 2012 15:00, sampling point TF080 Radium-228 4030 EPA method 904.0 Jul 1, 2012 – Sep 30, 2012
Collected
Jul 16, 2012 13:45
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
120717-026
Laboratory
Radiation Safety Engineering
1.2 pci/l , sample collected Jul 16, 2012 13:45, sampling point TF080 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 13:45, sampling point TF080 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 13:45, sampling point TF080 Radium-226 4020 EPA method 903.1 Jul 1, 2012 – Sep 30, 2012
Not detected below 0.39 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 13:45, sampling point TF080 Radium-228 4030 EPA method 904.0 Jul 1, 2012 – Sep 30, 2012
Collected
Jul 16, 2012 13:45
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
120717-026RU
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jul 16, 2012 13:45, sampling point TF080 Combined Uranium 4006 EPA method 200.8 Jul 1, 2012 – Sep 30, 2012
Collected
Apr 23, 2012 15:15
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
120424-035
Laboratory
Radiation Safety Engineering
1.2 pci/l , sample collected Apr 23, 2012 15:15, sampling point TF080 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 15:15, sampling point TF080 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 15:15, sampling point TF080 Radium-226 4020 EPA method 903.1 Apr 1, 2012 – Jun 30, 2012
Not detected below 0.39 pci/l Minimum Reporting Level , sample collected Apr 23, 2012 15:15, sampling point TF080 Radium-228 4030 EPA method 904.0 Apr 1, 2012 – Jun 30, 2012
Collected
Apr 23, 2012 15:15
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
120424-035RU
Laboratory
MSDH Lab
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 23, 2012 15:15, sampling point TF080 Combined Uranium 4006 EPA method 200.8 Apr 1, 2012 – Jun 30, 2012
Collected
Mar 5, 2012 01:40
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
120306-040NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 5, 2012 01:40, sampling point TF080 Nitrate-Nitrite 1038 EPA method 353.2 Jan 1, 2012 – Dec 31, 2012
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 5, 2012 01:40, sampling point TF080 Nitrate 1040 EPA method 353.2 Jan 1, 2012 – Dec 31, 2012
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 5, 2012 01:40, sampling point TF080 Nitrite 1041 EPA method 353.2 Jan 1, 2012 – Dec 31, 2012
Collected
Feb 13, 2012 13:00
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
120214-026
Laboratory
Radiation Safety Engineering
1.2 pci/l , sample collected Feb 13, 2012 13:00, sampling point TF080 Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Feb 13, 2012 13:00, sampling point TF080 Combined Radium (-226 & -228) 4010 Not recorded
Not detected below 0.496 pci/l Minimum Reporting Level , sample collected Feb 13, 2012 13:00, sampling point TF080 Radium-226 4020 EPA method 903.1 Jan 1, 2012 – Mar 31, 2012
Not detected below 0.39 pci/l Minimum Reporting Level , sample collected Feb 13, 2012 13:00, sampling point TF080 Radium-228 4030 EPA method 904.0 Jan 1, 2012 – Mar 31, 2012

Routine (10).