Skip to main content
Alpha

This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.

Lead and copper

MS0540029 , Hide-A-Way Hills Water Company

1–50 of 76 monitoring periods, newest first. This page applies no date range. The same list limited to the last two years.

Lead and copper 90th-percentile sample summaries for Hide-A-Way Hills Water Company, 1 to 50 of 76 summaries shown. The agency records no date of receipt for any of them.
Analyte Monitoring period Samples 90th percentile Facility Data quality
Copper Jan 1, 2025 – Dec 31, 2025 5 0.0038 mg/l DS000 Accepted
Lead Jan 1, 2025 – Dec 31, 2025 5 0 mg/l DS000 Accepted
Copper Jan 1, 2024 – Dec 31, 2024 5 0.0129 mg/l DS000 Accepted
Lead Jan 1, 2024 – Dec 31, 2024 5 0.0003 mg/l DS000 Accepted
Copper Jan 1, 2023 – Dec 31, 2023 5 0.04 mg/l DS000 Accepted
Lead Jan 1, 2023 – Dec 31, 2023 5 0.0028 mg/l DS000 Accepted
Copper Jul 1, 2022 – Dec 31, 2022 10 0.0829 mg/l DS000 Accepted
Lead Jul 1, 2022 – Dec 31, 2022 10 0.0021 mg/l DS000 Accepted
Copper Jan 1, 2022 – Jun 30, 2022 10 0.359 mg/l DS000 Accepted
Lead Jan 1, 2022 – Jun 30, 2022 10 0.0057 mg/l DS000 Accepted
Copper Jan 1, 2020 – Dec 31, 2020 5 0.3021 mg/l DS000 Accepted
Lead Jan 1, 2020 – Dec 31, 2020 5 0.009 mg/l DS000 Accepted
Copper Jan 1, 2019 – Dec 31, 2019 5 0.482 mg/l DS000 Accepted
Lead Jan 1, 2019 – Dec 31, 2019 5 0.0118 mg/l DS000 Accepted
Copper Jan 1, 2018 – Dec 31, 2018 5 0.5565 mg/l DS000 Accepted
Lead Jan 1, 2018 – Dec 31, 2018 5 0.0097 mg/l DS000 Accepted
Copper Jul 1, 2017 – Dec 31, 2017 10 0.3534 mg/l DS000 Accepted
Lead Jul 1, 2017 – Dec 31, 2017 10 0.0089 mg/l DS000 Accepted
Copper Jan 1, 2017 – Jun 30, 2017 10 0.501 mg/l DS000 Accepted
Lead Jan 1, 2017 – Jun 30, 2017 10 0.0116 mg/l DS000 Accepted
Copper Jan 1, 2016 – Dec 31, 2016 5 0.7207 mg/l DS000 Accepted
Lead Jan 1, 2016 – Dec 31, 2016 5 0.017 mg/l DS000 Accepted
Copper Jan 1, 2015 – Jun 30, 2015 10 0.3702 mg/l DS000 Accepted
Lead Jan 1, 2015 – Jun 30, 2015 10 0.0115 mg/l DS000 Accepted
Copper Jul 1, 2014 – Dec 31, 2014 10 0.5703 mg/l DS000 Accepted
Lead Jul 1, 2014 – Dec 31, 2014 10 0.0052 mg/l DS000 Accepted
Copper Jan 1, 2014 – Jun 30, 2014 10 0.5204 mg/l DS000 Accepted
Lead Jan 1, 2014 – Jun 30, 2014 10 0.016 mg/l DS000 Accepted
Copper Jul 1, 2013 – Dec 31, 2013 10 0.4882 mg/l DS000 Accepted
Lead Jul 1, 2013 – Dec 31, 2013 10 0.0144 mg/l DS000 Accepted
Copper Jan 1, 2013 – Jun 30, 2013 10 0.7236 mg/l DS000 Accepted
Lead Jan 1, 2013 – Jun 30, 2013 10 0.0115 mg/l DS000 Accepted
Copper Jul 1, 2012 – Dec 31, 2012 10 1.072 mg/l DS000 Accepted
Lead Jul 1, 2012 – Dec 31, 2012 10 0.0307 mg/l DS000 Accepted
Copper Jan 1, 2012 – Jun 30, 2012 10 1.2165 mg/l DS000 Accepted
Lead Jan 1, 2012 – Jun 30, 2012 10 0.0181 mg/l DS000 Accepted
Copper Jul 1, 2011 – Dec 31, 2011 10 0.7976 mg/l DS000 Accepted
Lead Jul 1, 2011 – Dec 31, 2011 10 0.0185 mg/l DS000 Accepted
Copper Jan 1, 2011 – Jun 30, 2011 10 0.5256 mg/l DS000 Accepted
Lead Jan 1, 2011 – Jun 30, 2011 10 0.0137 mg/l DS000 Accepted
Copper Jul 1, 2010 – Dec 31, 2010 5 1.6047 mg/l DS000 Accepted
Lead Jul 1, 2010 – Dec 31, 2010 5 0.0199 mg/l DS000 Accepted
Copper Jan 1, 2010 – Jun 30, 2010 10 0.6163 mg/l DS000 Accepted
Lead Jan 1, 2010 – Jun 30, 2010 10 0.0152 mg/l DS000 Accepted
Copper Jan 1, 2009 – Dec 31, 2009 6 0.6239 mg/l DS000 Accepted
Lead Jan 1, 2009 – Dec 31, 2009 6 0.0273 mg/l DS000 Accepted
Copper Jan 1, 2008 – Dec 31, 2008 5 0.8751 mg/l DS000 Accepted
Lead Jan 1, 2008 – Dec 31, 2008 5 0.0149 mg/l DS000 Accepted
Copper Jan 1, 2004 – Jun 30, 2004 10 0.4284 mg/l DS000 Accepted
Lead Jan 1, 2004 – Jun 30, 2004 10 0.0095 mg/l DS000 Accepted

No date of receipt is recorded for any of these summaries.

This system’s violations

What the 90th percentile is

The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.

From the help text published with these pages.