This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0550004 , Picayune Utilities, City of
25 of the 60 analytes this system has been tested for have been detected at least once, across 541 samples on record.
The other 35 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 541 samples on record, detections range from July 23, 2002 to October 21, 2025. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 224 of 225 results | Jun 22, 2004 | Jun 25, 2024 |
| Lead 1030 | Inorganic Chemical | 125 of 225 results | Jun 22, 2004 | Jun 25, 2024 |
| Fluoride 1025 | Inorganic Chemical | 41 of 41 results | Jul 23, 2002 | Mar 17, 2025 |
| Barium 1010 | Inorganic Chemical | 40 of 40 results | Jul 23, 2002 | Mar 17, 2025 |
| TTHM 2950 | Organic Chemical | 39 of 43 results | Oct 18, 2004 | Oct 21, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 38 of 43 results | Sep 27, 2006 | Oct 21, 2025 |
| Dichloroacetic Acid 2451 | Organic Chemical | 30 of 30 results | Jul 2, 2008 | Oct 21, 2025 |
| Chloroform 2941 | Organic Chemical | 30 of 30 results | Jul 2, 2008 | Oct 21, 2025 |
| Bromodichloromethane 2943 | Organic Chemical | 30 of 30 results | Jul 2, 2008 | Oct 21, 2025 |
| Trichloroacetic Acid 2452 | Organic Chemical | 29 of 30 results | Jul 2, 2008 | Oct 21, 2025 |
| Dibromochloromethane 2944 | Organic Chemical | 28 of 30 results | Jun 27, 2011 | Oct 21, 2025 |
| Chromium 1020 | Inorganic Chemical | 23 of 40 results | Jul 23, 2002 | Mar 17, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 15 of 30 results | Jun 27, 2011 | Jun 27, 2016 |
| Nickel 1036 | Inorganic Chemical | 8 of 40 results | Mar 15, 2004 | Mar 17, 2025 |
| Sulfate 1055 | Inorganic Chemical | 8 of 8 results | Jul 23, 2002 | Mar 15, 2004 |
| Monochloroacetic Acid 2450 | Organic Chemical | 5 of 30 results | Apr 7, 2014 | Jun 12, 2018 |
| Sodium 1052 | Inorganic Chemical | 4 of 4 results | Sep 17, 2019 | Sep 17, 2019 |
| Cyanide 1024 | Inorganic Chemical | 4 of 45 results | Feb 10, 2010 | Jun 15, 2015 |
| Radium-226 4020 | Radionuclide | 2 of 12 results | Jul 9, 2018 | Jul 9, 2018 |
| Arsenic 1005 | Inorganic Chemical | 1 of 40 results | May 6, 2013 | May 6, 2013 |
| Selenium 1045 | Inorganic Chemical | 1 of 40 results | May 6, 2013 | May 6, 2013 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 30 results | Sep 2, 2009 | Sep 2, 2009 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 1 of 93 results | May 14, 2007 | May 14, 2007 |
| Nitrate 1040 | Inorganic Chemical | 1 of 93 results | May 14, 2007 | May 14, 2007 |
| Nitrite 1041 | Inorganic Chemical | 1 of 93 results | May 14, 2007 | May 14, 2007 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 391–400 of 541 samples, newest first — collected September 2, 2009 to July 27, 2010. The summary above covers all 541.
75 results from the 10 samples listed here: 17 detected, 58 not detected. Across the whole record it is 729 of 2,244. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
Units in this table
Cyanide is recorded on this page in ug/l and mg/l. 1 mg/l = 1,000 ug/l.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Benzene 2990 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Toluene 2991 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Jul 27, 2010, sampling point TF101 | Styrene 2996 EPA method 524.2 | Jan 1, 2005 – Dec 31, 2010 |
|
||
| Not detected below 15 ug/l Minimum Reporting Level , sample collected Feb 10, 2010, sampling point TF104 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0176 mg/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Feb 10, 2010, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0494 mg/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Feb 10, 2010, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0405 mg/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Feb 10, 2010, sampling point TF105 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.006684 mg/l , sample collected Jan 27, 2010, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.004371 mg/l , sample collected Jan 27, 2010, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.514 mg/l , sample collected Jan 27, 2010, sampling point TF101 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.002812 mg/l , sample collected Jan 27, 2010, sampling point TF104 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.000836 mg/l , sample collected Jan 27, 2010, sampling point TF104 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.982 mg/l , sample collected Jan 27, 2010, sampling point TF104 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF104 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.007085 mg/l , sample collected Jan 27, 2010, sampling point TF105 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.973 mg/l , sample collected Jan 27, 2010, sampling point TF105 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF105 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.006665 mg/l , sample collected Jan 27, 2010, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.001008 mg/l , sample collected Jan 27, 2010, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.803 mg/l , sample collected Jan 27, 2010, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 27, 2010, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Sep 2, 2009, sampling point MRT000 | Monochloroacetic Acid 2450 EPA method 552.2 | Not recorded |
| 0.004 mg/l , sample collected Sep 2, 2009, sampling point MRT000 | Dichloroacetic Acid 2451 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 2, 2009, sampling point MRT000 | Trichloroacetic Acid 2452 EPA method 552.2 | Not recorded |
| 0.003 mg/l , sample collected Sep 2, 2009, sampling point MRT000 | Monobromoacetic Acid 2453 EPA method 552.2 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 2, 2009, sampling point MRT000 | Dibromoacetic Acid 2454 EPA method 552.2 | Not recorded |
| 0 mg/l This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here. , sample collected Sep 2, 2009, sampling point MRT000 | Total Haloacetic Acids (Haa5) 2456 | Jan 1, 2009 – Dec 31, 2009 |
-
- Collected
- Jul 27, 2010
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 100728-004VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2005 – Dec 31, 2010
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Feb 10, 2010
- Sampling point
- TF104 Treatment Plant T104
- Sample type
- Routine
- Lab sample
- 100211-020CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 15 ug/l Minimum Reporting Level
-
- Collected
- Feb 10, 2010
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 100211-018CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- 0.0176 mg/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
-
- Collected
- Feb 10, 2010
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 100211-017CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- 0.0494 mg/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
-
- Collected
- Feb 10, 2010
- Sampling point
- TF105 Treatment Plant T105
- Sample type
- Routine
- Lab sample
- 100211-015CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cyanide 1024 EPA method QC10204001X
- Result
- 0.0405 mg/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
-
- Collected
- Jan 27, 2010
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 100128-009IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.006684 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- 0.004371 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.514 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Jan 27, 2010
- Sampling point
- TF104 Treatment Plant T104
- Sample type
- Routine
- Lab sample
- 100128-008IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.002812 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- 0.000836 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.982 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Jan 27, 2010
- Sampling point
- TF105 Treatment Plant T105
- Sample type
- Routine
- Lab sample
- 100128-007IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.007085 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.973 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Jan 27, 2010
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 100128-006IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.006665 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- 0.001008 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.803 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Sep 2, 2009
- Sampling point
- MRT000 Max. Res. Time
- Sample type
- Routine
- Lab sample
- 090903-001HA
- Laboratory
- MSDH Lab
-
Monochloroacetic Acid 2450 EPA method 552.2
- Result
- Not detected below 0.002 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Dichloroacetic Acid 2451 EPA method 552.2
- Result
- 0.004 mg/l
- Monitoring period
- Not recorded
-
Trichloroacetic Acid 2452 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Monobromoacetic Acid 2453 EPA method 552.2
- Result
- 0.003 mg/l
- Monitoring period
- Not recorded
-
Dibromoacetic Acid 2454 EPA method 552.2
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Total Haloacetic Acids (Haa5) 2456
- Result
- 0 mg/l This result is recorded as a detection, and the figure the agency wrote — "0.00" — is zero to the precision it was written to. Read the zero as "smaller than the written figure resolves", not as "none present". SDWIS holds a separate numeric concentration that Drinking Water Watch does not publish, so this endpoint does not carry it either; no more precise magnitude is available here.
- Monitoring period
- Jan 1, 2009 – Dec 31, 2009
Routine (10).