This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Lead and copper
MS0560008 , Janice W/A #2-South
Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.
| Analyte | Monitoring period | Samples | 90th percentile | Facility | Data quality |
|---|---|---|---|---|---|
| Copper | Jan 1, 2023 – Dec 31, 2025 | 5 | 0.014 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2023 – Dec 31, 2025 | 5 | 0.013 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2020 – Dec 31, 2022 | 5 | 0.0217 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2020 – Dec 31, 2022 | 5 | 0.0104 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2017 – Dec 31, 2019 | 8 | 0.064 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2017 – Dec 31, 2019 | 8 | 0.0087 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2016 – Dec 31, 2016 | 5 | 0.0136 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2016 – Dec 31, 2016 | 5 | 0.0095 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2015 – Dec 31, 2015 | 6 | 0.0411 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2015 – Dec 31, 2015 | 6 | 0.0123 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2014 – Dec 31, 2014 | 6 | 0.0331 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2014 – Dec 31, 2014 | 6 | 0.0015 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2013 – Dec 31, 2013 | 6 | 0.021 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2013 – Dec 31, 2013 | 6 | 0.0128 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2012 – Jun 30, 2012 | 10 | 0.0877 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2012 – Jun 30, 2012 | 10 | 0.0014 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2011 – Dec 31, 2011 | 10 | 0.0629 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2011 – Dec 31, 2011 | 10 | 0.0018 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2011 – Jun 30, 2011 | 11 | 0.1028 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2011 – Jun 30, 2011 | 11 | 0.0025 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2010 – Jun 30, 2010 | 10 | 0.0986 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2010 – Jun 30, 2010 | 10 | 0.0139 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2009 – Jun 30, 2009 | 10 | 0.081 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2009 – Jun 30, 2009 | 10 | 0.0014 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2008 – Dec 31, 2008 | 10 | 0.0214 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2008 – Dec 31, 2008 | 10 | 0.0182 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2007 – Dec 31, 2007 | 7 | 0.0916 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2007 – Dec 31, 2007 | 7 | 0.0184 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2004 – Dec 31, 2004 | 5 | 0.0677 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2004 – Dec 31, 2004 | 5 | 0.0048 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2003 – Dec 31, 2003 | 10 | 0.851 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2003 – Dec 31, 2003 | 10 | 0.004 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2003 – Jun 30, 2003 | 10 | 1.197 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2003 – Jun 30, 2003 | 10 | 0.009 mg/l | DS000 | Accepted |
| Copper | Jul 1, 2002 – Dec 31, 2002 | 10 | 5.768 mg/l | DS000 | Accepted |
| Lead | Jul 1, 2002 – Dec 31, 2002 | 10 | 0.025 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2001 – Dec 31, 2001 | 5 | 0.528 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2001 – Dec 31, 2001 | 5 | 0.017 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1996 – Dec 31, 1996 | 5 | 0.282 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1996 – Dec 31, 1996 | 5 | 0.001 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1995 – Jun 30, 1995 | 10 | 0.432 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1995 – Jun 30, 1995 | 10 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jul 1, 1994 – Dec 31, 1994 | 10 | 0.153 mg/l | DS000 | Accepted |
| Lead | Jul 1, 1994 – Dec 31, 1994 | 10 | 0.006 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1994 – Jun 30, 1994 | 10 | 1.53 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1994 – Jun 30, 1994 | 10 | 0.005 mg/l | DS000 | Accepted |
| Copper | Jul 1, 1993 – Dec 31, 1993 | 8 | 0.245 mg/l | DS000 | Accepted |
| Lead | Jul 1, 1993 – Dec 31, 1993 | 8 | 0 mg/l | DS000 | Accepted |
No date of receipt is recorded for any of these summaries.
What the 90th percentile is
The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.
From the help text published with these pages.