This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0580001 , Algoma Water Association
25 of the 60 analytes this system has been tested for have been detected at least once, across 467 samples on record.
An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 467 samples on record, detections range from October 15, 2003 to June 22, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 121 of 121 results | Sep 6, 2007 | Sep 26, 2023 |
| Lead 1030 | Inorganic Chemical | 54 of 121 results | Sep 6, 2007 | Sep 26, 2023 |
| Barium 1010 | Inorganic Chemical | 51 of 51 results | Oct 15, 2003 | Jun 22, 2026 |
| Fluoride 1025 | Inorganic Chemical | 49 of 51 results | Oct 15, 2003 | Jun 22, 2026 |
| Chromium 1020 | Inorganic Chemical | 30 of 51 results | Oct 15, 2003 | Apr 9, 2019 |
| Arsenic 1005 | Inorganic Chemical | 29 of 51 results | Nov 16, 2004 | Mar 17, 2025 |
| Nickel 1036 | Inorganic Chemical | 20 of 47 results | Nov 16, 2004 | Mar 17, 2025 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 20 of 27 results | Sep 23, 2009 | Jul 2, 2020 |
| Sodium 1052 | Inorganic Chemical | 19 of 19 results | Sep 24, 2019 | Jun 22, 2026 |
| Selenium 1045 | Inorganic Chemical | 19 of 51 results | Oct 15, 2003 | May 6, 2013 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 15 of 21 results | Mar 14, 2012 | Oct 9, 2012 |
| Radium-226 4020 | Radionuclide | 14 of 27 results | Sep 23, 2009 | Jul 2, 2020 |
| Radium-228 4030 | Radionuclide | 9 of 27 results | Sep 23, 2009 | Jul 2, 2020 |
| Nitrite 1041 | Inorganic Chemical | 9 of 103 results | Aug 24, 2005 | Apr 20, 2015 |
| Gross Alpha Particle Activity 4109 | Radionuclide | 5 of 8 results | Sep 23, 2009 | Sep 12, 2012 |
| Nitrate 1040 | Inorganic Chemical | 5 of 103 results | Jul 24, 2006 | Nov 27, 2007 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 4 of 22 results | Sep 4, 2007 | Nov 2, 2021 |
| Gross Beta Particle Activity 4100 | Radionuclide | 4 of 4 results | Sep 23, 2009 | Sep 23, 2009 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 4 of 103 results | Nov 27, 2007 | Nov 27, 2007 |
| Cadmium 1015 | Inorganic Chemical | 4 of 51 results | Apr 11, 2005 | Apr 11, 2005 |
| Gross Alpha, Excl. Radon & U 4000 | Radionuclide | 3 of 6 results | Sep 23, 2009 | Sep 23, 2009 |
| TTHM 2950 | Organic Chemical | 2 of 23 results | Sep 4, 2007 | Jun 30, 2010 |
| Sulfate 1055 | Inorganic Chemical | 2 of 8 results | Mar 17, 2004 | Mar 17, 2004 |
| Xylenes, Total 2955 | Organic Chemical | 1 of 42 results | May 8, 2019 | May 8, 2019 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 16 results | Aug 28, 2013 | Aug 28, 2013 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 361–370 of 467 samples, newest first — collected May 18, 2009 to January 25, 2010. The summary above covers all 467.
62 results from the 10 samples listed here: 30 detected, 32 not detected. Across the whole record it is 494 of 2,415. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
Units in this table
Gross Alpha Particle Activity is recorded on this page in ug/l and pci/l.
Radium-226 is recorded on this page in ug/l and pci/l.
Radium-228 is recorded on this page in ug/l and pci/l.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0017 mg/l , sample collected Jan 25, 2010, sampling point TF103 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0918 mg/l , sample collected Jan 25, 2010, sampling point TF103 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF103 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF103 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.111 mg/l , sample collected Jan 25, 2010, sampling point TF103 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF103 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0006 mg/l , sample collected Jan 25, 2010, sampling point TF103 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.0069 mg/l , sample collected Jan 25, 2010, sampling point TF103 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF103 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF103 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF103 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| 0.0013 mg/l , sample collected Jan 25, 2010, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0915 mg/l , sample collected Jan 25, 2010, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.107 mg/l , sample collected Jan 25, 2010, sampling point TF102 | Fluoride 1025 EPA method 380-75WE | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0002 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| 0.0006 mg/l , sample collected Jan 25, 2010, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| 0.0053 mg/l , sample collected Jan 25, 2010, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jan 25, 2010, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2008 – Dec 31, 2010 |
|
||
| Not detected below 3 pci/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF102 | Gross Alpha, Excl. Radon & U 4000 | Jul 1, 2009 – Sep 30, 2009 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF102 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2009 – Sep 30, 2009 |
| 0.153 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF102 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 1 pci/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF102 | Radium-226 4020 EPA method 903 | Jul 1, 2009 – Sep 30, 2009 |
| 0.153 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF102 | Radium-228 4030 EPA method 904 | Jul 1, 2009 – Sep 30, 2009 |
| 0.489 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF102 | Gross Beta Particle Activity 4100 EPA method 900 | Not recorded |
| Not detected below 3 pci/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF102 | Gross Alpha Particle Activity 4109 EPA method 900 | Jul 1, 2009 – Sep 30, 2009 |
|
||
| 0.386 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF101 | Gross Alpha, Excl. Radon & U 4000 | Jul 1, 2009 – Sep 30, 2009 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF101 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2009 – Sep 30, 2009 |
| 0.111 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| 0.088 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF101 | Radium-226 4020 EPA method 903 | Jul 1, 2009 – Sep 30, 2009 |
| 0.023 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF101 | Radium-228 4030 EPA method 904 | Jul 1, 2009 – Sep 30, 2009 |
| 2.243 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF101 | Gross Beta Particle Activity 4100 EPA method 900 | Not recorded |
| 0.386 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF101 | Gross Alpha Particle Activity 4109 EPA method 900 | Jul 1, 2009 – Sep 30, 2009 |
|
||
| 0.144 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF103 | Gross Alpha, Excl. Radon & U 4000 | Jul 1, 2009 – Sep 30, 2009 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF103 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2009 – Sep 30, 2009 |
| 0.094 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF103 | Combined Radium (-226 & -228) 4010 | Not recorded |
| 0.094 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF103 | Radium-226 4020 EPA method 903 | Jul 1, 2009 – Sep 30, 2009 |
| Not detected below 1 pci/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF103 | Radium-228 4030 EPA method 904 | Jul 1, 2009 – Sep 30, 2009 |
| 1.667 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF103 | Gross Beta Particle Activity 4100 EPA method 900 | Not recorded |
| 0.144 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF103 | Gross Alpha Particle Activity 4109 EPA method 900 | Jul 1, 2009 – Sep 30, 2009 |
|
||
| 1.818 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF104 | Gross Alpha, Excl. Radon & U 4000 | Jul 1, 2009 – Sep 30, 2009 |
| Not detected below 1 ug/l Minimum Reporting Level , sample collected Sep 23, 2009, sampling point TF104 | Combined Uranium 4006 EPA method 200.8 | Jul 1, 2009 – Sep 30, 2009 |
| 0.183 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF104 | Combined Radium (-226 & -228) 4010 | Not recorded |
| 0.009 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF104 | Radium-226 4020 EPA method 903 | Jul 1, 2009 – Sep 30, 2009 |
| 0.174 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF104 | Radium-228 4030 EPA method 904 | Jul 1, 2009 – Sep 30, 2009 |
| 1.374 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF104 | Gross Beta Particle Activity 4100 EPA method 900 | Not recorded |
| 1.818 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType. , sample collected Sep 23, 2009, sampling point TF104 | Gross Alpha Particle Activity 4109 EPA method 900 | Jul 1, 2009 – Sep 30, 2009 |
|
||
| Not detected below 0.25 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF103 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.2 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF103 | Nitrate 1040 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF103 | Nitrite 1041 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
|
||
| Not detected below 0.25 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF102 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.2 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF102 | Nitrate 1040 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF102 | Nitrite 1041 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
|
||
| Not detected below 0.25 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF104 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.2 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF104 | Nitrate 1040 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF104 | Nitrite 1041 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
|
||
| Not detected below 0.25 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF101 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.2 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF101 | Nitrate 1040 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
| Not detected below 0.05 mg/l Minimum Reporting Level , sample collected May 18, 2009, sampling point TF101 | Nitrite 1041 EPA method 353.2 | Jan 1, 2009 – Dec 31, 2009 |
-
- Collected
- Jan 25, 2010
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 100126-048IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0017 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.0918 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.111 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0002 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- 0.0006 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.0069 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Jan 25, 2010
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 100126-047IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0013 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Barium 1010 EPA method 200.8
- Result
- 0.0915 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Fluoride 1025 EPA method 380-75WE
- Result
- 0.107 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0002 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Nickel 1036 EPA method 200.8
- Result
- 0.0006 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- 0.0053 mg/l
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2008 – Dec 31, 2010
-
- Collected
- Sep 23, 2009
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 02389-004
- Laboratory
- Laboratory, Ars
-
Gross Alpha, Excl. Radon & U 4000
- Result
- Not detected below 3 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Radium (-226 & -228) 4010
- Result
- 0.153 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903
- Result
- Not detected below 1 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Radium-228 4030 EPA method 904
- Result
- 0.153 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Gross Beta Particle Activity 4100 EPA method 900
- Result
- 0.489 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Gross Alpha Particle Activity 4109 EPA method 900
- Result
- Not detected below 3 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
- Collected
- Sep 23, 2009
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 02389-003
- Laboratory
- Laboratory, Ars
-
Gross Alpha, Excl. Radon & U 4000
- Result
- 0.386 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Radium (-226 & -228) 4010
- Result
- 0.111 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903
- Result
- 0.088 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Radium-228 4030 EPA method 904
- Result
- 0.023 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Gross Beta Particle Activity 4100 EPA method 900
- Result
- 2.243 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Gross Alpha Particle Activity 4109 EPA method 900
- Result
- 0.386 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
- Collected
- Sep 23, 2009
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 02389-002
- Laboratory
- Laboratory, Ars
-
Gross Alpha, Excl. Radon & U 4000
- Result
- 0.144 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Radium (-226 & -228) 4010
- Result
- 0.094 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903
- Result
- 0.094 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Radium-228 4030 EPA method 904
- Result
- Not detected below 1 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Gross Beta Particle Activity 4100 EPA method 900
- Result
- 1.667 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Gross Alpha Particle Activity 4109 EPA method 900
- Result
- 0.144 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
- Collected
- Sep 23, 2009
- Sampling point
- TF104 Treatment Plant T104
- Sample type
- Routine
- Lab sample
- 02389-001
- Laboratory
- Laboratory, Ars
-
Gross Alpha, Excl. Radon & U 4000
- Result
- 1.818 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Uranium 4006 EPA method 200.8
- Result
- Not detected below 1 ug/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Combined Radium (-226 & -228) 4010
- Result
- 0.183 pci/l The agency recorded which kind of limit this result was below, but stored nothing as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903
- Result
- 0.009 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Radium-228 4030 EPA method 904
- Result
- 0.174 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
Gross Beta Particle Activity 4100 EPA method 900
- Result
- 1.374 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Not recorded
-
Gross Alpha Particle Activity 4109 EPA method 900
- Result
- 1.818 pci/l The agency recorded which kind of limit this result was below, but stored 0.000000000 as the limit itself, which is not a level. The type is published and the value is null. What the limit was is not on record. Whether the result was a detection is a separate column: read resultType.
- Monitoring period
- Jul 1, 2009 – Sep 30, 2009
-
- Collected
- May 18, 2009
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- 090519-052NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2009
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.25 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.2 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
- Collected
- May 18, 2009
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 090519-049NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2009
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.25 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.2 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
- Collected
- May 18, 2009
- Sampling point
- TF104 Treatment Plant T104
- Sample type
- Routine
- Lab sample
- 090519-048NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2009
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.25 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.2 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
-
- Collected
- May 18, 2009
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 090519-047NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2009 – Dec 31, 2009
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.25 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.2 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.05 mg/l Minimum Reporting Level
Routine (10).