This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0580002 , East Pontotoc Water Assn
26 of the 59 analytes this system has been tested for have been detected at least once, across 410 samples on record.
The other 33 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 410 samples on record, detections range from October 15, 2003 to July 14, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 140 of 140 results | Sep 6, 2007 | Jul 1, 2025 |
| Lead 1030 | Inorganic Chemical | 53 of 140 results | Sep 6, 2007 | Jul 1, 2025 |
| Barium 1010 | Inorganic Chemical | 45 of 45 results | Oct 15, 2003 | Jul 14, 2026 |
| Fluoride 1025 | Inorganic Chemical | 33 of 43 results | Oct 15, 2003 | Jul 14, 2026 |
| Arsenic 1005 | Inorganic Chemical | 31 of 45 results | Mar 17, 2004 | Jul 14, 2026 |
| Chromium 1020 | Inorganic Chemical | 25 of 45 results | Oct 15, 2003 | Sep 4, 2018 |
| Nickel 1036 | Inorganic Chemical | 23 of 41 results | Mar 17, 2004 | Jan 8, 2024 |
| Selenium 1045 | Inorganic Chemical | 18 of 45 results | Mar 17, 2004 | Jul 14, 2026 |
| Sodium 1052 | Inorganic Chemical | 12 of 12 results | Sep 24, 2019 | Mar 4, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 11 of 16 results | Mar 14, 2012 | Jul 2, 2020 |
| Combined Radium (-226 & -228) 4010 | Radionuclide | 11 of 18 results | Nov 29, 2011 | Oct 9, 2012 |
| Radium-228 4030 | Radionuclide | 11 of 18 results | Nov 29, 2011 | Oct 9, 2012 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 6 of 17 results | Sep 4, 2007 | Nov 4, 2024 |
| Nitrite 1041 | Inorganic Chemical | 6 of 85 results | Nov 7, 2012 | Apr 8, 2024 |
| Radium-226 4020 | Radionuclide | 6 of 18 results | Mar 14, 2012 | Jul 2, 2020 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 5 of 85 results | Jun 9, 2004 | Apr 8, 2024 |
| Thallium, Total 1085 | Inorganic Chemical | 5 of 45 results | Jan 25, 2010 | Jun 20, 2011 |
| Cadmium 1015 | Inorganic Chemical | 3 of 45 results | Apr 11, 2005 | Apr 11, 2005 |
| Xylenes, Total 2955 | Organic Chemical | 2 of 34 results | Jul 14, 2026 | Jul 14, 2026 |
| TTHM 2950 | Organic Chemical | 2 of 18 results | Sep 4, 2007 | Jun 30, 2010 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 11 results | Nov 4, 2024 | Nov 4, 2024 |
| Cyanide 1024 | Inorganic Chemical | 1 of 39 results | Feb 23, 2016 | Feb 23, 2016 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 11 results | Aug 28, 2013 | Aug 28, 2013 |
| Gross Alpha Particle Activity 4109 | Radionuclide | 1 of 4 results | Jun 26, 2012 | Jun 26, 2012 |
| Bromoform 2942 | Organic Chemical | 1 of 13 results | Jun 30, 2010 | Jun 30, 2010 |
| Nitrate 1040 | Inorganic Chemical | 1 of 85 results | Jun 9, 2004 | Jun 9, 2004 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 61–70 of 410 samples, newest first — collected July 26, 2022 to October 12, 2022. The summary above covers all 410.
72 results from the 10 samples listed here: 11 detected, 61 not detected. Across the whole record it is 454 of 2,031. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0025 mg/l , sample collected Oct 12, 2022 12:57, sampling point TF104 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.099 mg/l , sample collected Oct 12, 2022 12:57, sampling point TF104 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.134 mg/l , sample collected Oct 12, 2022 12:57, sampling point TF104 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0007 mg/l , sample collected Oct 12, 2022 12:57, sampling point TF104 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:57, sampling point TF104 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 0.0024 mg/l , sample collected Oct 12, 2022 12:30, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0975 mg/l , sample collected Oct 12, 2022 12:30, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.151 mg/l , sample collected Oct 12, 2022 12:30, sampling point TF101 | Fluoride 1025 EPA method QC 10-109-12-2-A | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 0.0007 mg/l , sample collected Oct 12, 2022 12:30, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 12, 2022 12:30, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Benzene 2990 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Toluene 2991 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:00, sampling point TF103 | Styrene 2996 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Benzene 2990 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Toluene 2991 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Sep 6, 2022 13:20, sampling point TF102 | Styrene 2996 EPA method 524.2 | Jan 1, 2017 – Dec 31, 2022 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 30, 2022 12:22, sampling point TF104 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 30, 2022 12:05, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 30, 2022 12:45, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 30, 2022 13:11, sampling point TF103 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 0.029 mg/l , sample collected Jul 26, 2022 08:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| 31.1 ug/l , sample collected Jul 26, 2022 08:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
|
||
| 0.0138 mg/l , sample collected Jul 26, 2022 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 26, 2022 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2020 – Dec 31, 2022 |
-
- Collected
- Oct 12, 2022 12:57
- Sampling point
- TF104
- Sample type
- Routine
- Lab sample
- IN-221013-034
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0025 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.099 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.134 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.0007 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
- Collected
- Oct 12, 2022 12:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- IN-221013-033
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0024 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Barium 1010 EPA method 200.8
- Result
- 0.0975 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Chromium 1020 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Fluoride 1025 EPA method QC 10-109-12-2-A
- Result
- 0.151 mg/l
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Nickel 1036 EPA method 200.8
- Result
- 0.0007 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
- Collected
- Sep 6, 2022 13:00
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- VO-220907-015
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2022
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Sep 6, 2022 13:20
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- VO-220907-014
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2022
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Aug 30, 2022 12:22
- Sampling point
- TF104
- Sample type
- Routine
- Lab sample
- CN-220831-030
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Aug 30, 2022 12:05
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- CN-220831-029
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Aug 30, 2022 12:45
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- CN-220831-028
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Aug 30, 2022 13:11
- Sampling point
- TF103 Treatment Plant T103
- Sample type
- Routine
- Lab sample
- CN-220831-027
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- Jul 26, 2022 08:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- PB-220729-030
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.029 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 31.1 ug/l
-
- Collected
- Jul 26, 2022 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- PB-220729-020
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2020 – Dec 31, 2022
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0138 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
Routine (10).