This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Lead and copper
MS0580004 , Oak Hill Water Assn
Every monitoring period on record is listed here. This page applies no date range. The same list limited to the last two years.
| Analyte | Monitoring period | Samples | 90th percentile | Facility | Data quality |
|---|---|---|---|---|---|
| Copper | Jan 1, 2021 – Dec 31, 2023 | 10 | 0.399 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2021 – Dec 31, 2023 | 10 | 0 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2018 – Dec 31, 2020 | 10 | 0.365 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2018 – Dec 31, 2020 | 10 | 0.0007 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2015 – Dec 31, 2017 | 10 | 0.4143 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2015 – Dec 31, 2017 | 10 | 0.0013 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2012 – Dec 31, 2014 | 10 | 0.3989 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2012 – Dec 31, 2014 | 10 | 0.0006 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2009 – Dec 31, 2011 | 11 | 0.4513 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2009 – Dec 31, 2011 | 11 | 0.005 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2006 – Dec 31, 2008 | 11 | 0.3312 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2006 – Dec 31, 2008 | 11 | 0.0015 mg/l | DS000 | Accepted |
| Copper | Jan 1, 2000 – Dec 31, 2002 | 10 | 0.309 mg/l | DS000 | Accepted |
| Lead | Jan 1, 2000 – Dec 31, 2002 | 10 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1996 – Dec 31, 1996 | 10 | 0.226 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1996 – Dec 31, 1996 | 10 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1995 – Dec 31, 1995 | 10 | 0.313 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1995 – Dec 31, 1995 | 10 | 0.002 mg/l | DS000 | Accepted |
| Copper | Jan 1, 1994 – Jun 30, 1994 | 20 | 0.463 mg/l | DS000 | Accepted |
| Lead | Jan 1, 1994 – Jun 30, 1994 | 20 | 0.003 mg/l | DS000 | Accepted |
| Copper | Jul 1, 1993 – Dec 31, 1993 | 20 | 0.448 mg/l | DS000 | Accepted |
| Lead | Jul 1, 1993 – Dec 31, 1993 | 20 | 0.002 mg/l | DS000 | Accepted |
No date of receipt is recorded for any of these summaries.
What the 90th percentile is
The 90th percentile of all samples collected from the distribution system is the standard that the US Environmental Protection Agency has chosen for determining compliance with the Lead and Copper Action Level under the federal Lead and Copper Rule. The 90th percentile is determined by ranking all sample results from lowest to highest and finding a result that is 90% of the number of sample results from the top. For example, if there are 10 sample results, the 90th percentile would be the 9th sample result from the top.
From the help text published with these pages.