Chemical and radiological sample results

MS0580007 , Randolph Water Association #1

21 of the 58 analytes this system has been tested for have been detected at least once, across 297 samples on record.

The other 37 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 297 samples on record, detections range from October 15, 2003 to August 19, 2025. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Randolph Water Association #1, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Copper, Free 1022 Inorganic Chemical 90 of 90 results Aug 9, 2004 Jun 24, 2025
Lead 1030 Inorganic Chemical 60 of 90 results Aug 9, 2004 Jun 24, 2025
Barium 1010 Inorganic Chemical 27 of 27 results Oct 15, 2003 Mar 19, 2025
Fluoride 1025 Inorganic Chemical 25 of 27 results Oct 15, 2003 Mar 19, 2025
Nickel 1036 Inorganic Chemical 19 of 27 results Mar 15, 2004 Mar 19, 2025
Arsenic 1005 Inorganic Chemical 17 of 27 results Mar 15, 2004 Mar 19, 2025
Chromium 1020 Inorganic Chemical 11 of 27 results Oct 15, 2003 Apr 1, 2020
Nitrite 1041 Inorganic Chemical 10 of 56 results Sep 26, 2005 Apr 9, 2024
Selenium 1045 Inorganic Chemical 10 of 27 results Mar 15, 2004 Apr 1, 2020
Gross Alpha, Incl. Radon & U 4002 Radionuclide 10 of 10 results Dec 5, 2011 Jul 10, 2012
TTHM 2950 Organic Chemical 9 of 11 results Sep 4, 2007 Aug 19, 2025
Sodium 1052 Inorganic Chemical 6 of 6 results Sep 19, 2019 Mar 3, 2025
Combined Radium (-226 & -228) 4010 Radionuclide 6 of 11 results Dec 5, 2011 Jun 9, 2020
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 5 of 11 results Sep 4, 2007 Jun 12, 2024
Radium-226 4020 Radionuclide 5 of 11 results Dec 5, 2011 Jul 10, 2012
Nitrate-Nitrite 1038 Inorganic Chemical 5 of 56 results Sep 26, 2005 Jun 1, 2009
Nitrate 1040 Inorganic Chemical 3 of 56 results Sep 26, 2005 Jul 14, 2008
Bromoform 2942 Organic Chemical 2 of 5 results Aug 8, 2016 Dec 14, 2020
Xylenes, Total 2955 Organic Chemical 2 of 37 results Aug 17, 2010 Aug 17, 2010
Radium-228 4030 Radionuclide 1 of 11 results Jun 9, 2020 Jun 9, 2020
Cadmium 1015 Inorganic Chemical 1 of 27 results Apr 11, 2005 Apr 11, 2005

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 81–90 of 297 samples, newest first — collected November 13, 2019 to August 26, 2020. The summary above covers all 297.

40 results from the 10 samples listed here: 12 detected, 28 not detected. Across the whole record it is 324 of 1,587. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Randolph Water Association #1, every result from 81 to 90 of 297 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Aug 26, 2020 15:30
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
CN-200827-005
Laboratory
MSDH Lab
Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 26, 2020 15:30, sampling point TF103 Cyanide 1024 EPA method QC10204001X Jul 1, 2020 – Sep 30, 2020
Collected
Jun 9, 2020 15:00
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
4650613
Laboratory
Eurofins Eaton Analytical South Bend in
2 pci/l , sample collected Jun 9, 2020 15:00, sampling point TF103 Combined Radium (-226 & -228) 4010 EPA method 7500-RA Not recorded
Not detected below 0.3 pci/l Minimum Reporting Level , sample collected Jun 9, 2020 15:00, sampling point TF103 Radium-226 4020 EPA method 7500-RAB Apr 1, 2020 – Jun 30, 2020
2 pci/l , sample collected Jun 9, 2020 15:00, sampling point TF103 Radium-228 4030 EPA method 7500-RAD Apr 1, 2020 – Jun 30, 2020
Collected
Jun 9, 2020 15:00
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
200610-009CN
Laboratory
MSDH Lab
Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Jun 9, 2020 15:00, sampling point TF103 Cyanide 1024 EPA method QC10204001X Apr 1, 2020 – Jun 30, 2020
Collected
Apr 28, 2020 14:40
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
200429-024NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:40, sampling point TF103 Nitrate-Nitrite 1038 EPA method QC10107041C Apr 1, 2020 – Jun 30, 2020
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:40, sampling point TF103 Nitrate 1040 EPA method QC10107041C Apr 1, 2020 – Jun 30, 2020
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:40, sampling point TF103 Nitrite 1041 EPA method QC10107041C Apr 1, 2020 – Jun 30, 2020
Collected
Apr 28, 2020 14:30
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
200429-023NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:30, sampling point TF103 Nitrate-Nitrite 1038 EPA method QC10107041C Apr 1, 2020 – Jun 30, 2020
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:30, sampling point TF103 Nitrate 1040 EPA method QC10107041C Apr 1, 2020 – Jun 30, 2020
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:30, sampling point TF103 Nitrite 1041 EPA method QC10107041C Apr 1, 2020 – Jun 30, 2020
Collected
Apr 28, 2020 14:45
Sampling point
TF101 Treatment Plant T101
Sample type
Routine
Lab sample
200429-022NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:45, sampling point TF101 Nitrate-Nitrite 1038 EPA method QC10107041C Jan 1, 2020 – Dec 31, 2020
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:45, sampling point TF101 Nitrate 1040 EPA method QC10107041C Jan 1, 2020 – Dec 31, 2020
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Apr 28, 2020 14:45, sampling point TF101 Nitrite 1041 EPA method QC10107041C Jan 1, 2020 – Dec 31, 2020
Collected
Apr 28, 2020
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
200429-021NI
Laboratory
MSDH Lab
Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Apr 28, 2020, sampling point TF102 Nitrate-Nitrite 1038 EPA method QC10107041C Jan 1, 2020 – Dec 31, 2020
Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Apr 28, 2020, sampling point TF102 Nitrate 1040 EPA method QC10107041C Jan 1, 2020 – Dec 31, 2020
Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Apr 28, 2020, sampling point TF102 Nitrite 1041 EPA method QC10107041C Jan 1, 2020 – Dec 31, 2020
Collected
Apr 1, 2020 15:00
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
200402-013IN
Laboratory
MSDH Lab
0.0034 mg/l , sample collected Apr 1, 2020 15:00, sampling point TF103 Arsenic 1005 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
0.073 mg/l , sample collected Apr 1, 2020 15:00, sampling point TF103 Barium 1010 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2020 15:00, sampling point TF103 Cadmium 1015 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
0.0005 mg/l , sample collected Apr 1, 2020 15:00, sampling point TF103 Chromium 1020 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
0.15 mg/l , sample collected Apr 1, 2020 15:00, sampling point TF103 Fluoride 1025 EPA method QC 10-109-12-2-A Jan 1, 2020 – Dec 31, 2020
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2020 15:00, sampling point TF103 Mercury 1035 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
0.0006 mg/l , sample collected Apr 1, 2020 15:00, sampling point TF103 Nickel 1036 EPA method 200.8 Not recorded
0.0029 mg/l , sample collected Apr 1, 2020 15:00, sampling point TF103 Selenium 1045 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2020 15:00, sampling point TF103 Antimony, Total 1074 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2020 15:00, sampling point TF103 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Apr 1, 2020 15:00, sampling point TF103 Thallium, Total 1085 EPA method 200.8 Jan 1, 2020 – Dec 31, 2020
Collected
Feb 18, 2020 15:00
Sampling point
TF103 Treatment Facility TF103
Sample type
Routine
Lab sample
200219-005CN
Laboratory
MSDH Lab
Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Feb 18, 2020 15:00, sampling point TF103 Cyanide 1024 EPA method QC10204001X Jan 1, 2020 – Mar 31, 2020
Collected
Nov 13, 2019 11:15
Sampling point
TF102 Treatment Plant T102
Sample type
Routine
Lab sample
191114-011IN
Laboratory
MSDH Lab
0.002 mg/l , sample collected Nov 13, 2019 11:15, sampling point TF102 Arsenic 1005 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
0.0808 mg/l , sample collected Nov 13, 2019 11:15, sampling point TF102 Barium 1010 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Cadmium 1015 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
0.0006 mg/l , sample collected Nov 13, 2019 11:15, sampling point TF102 Chromium 1020 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
0.168 mg/l , sample collected Nov 13, 2019 11:15, sampling point TF102 Fluoride 1025 EPA method QC 10-109-12-2-A Jan 1, 2017 – Dec 31, 2019
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Mercury 1035 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Nickel 1036 EPA method 200.8 Not recorded
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Selenium 1045 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Antimony, Total 1074 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Beryllium, Total 1075 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019
Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Nov 13, 2019 11:15, sampling point TF102 Thallium, Total 1085 EPA method 200.8 Jan 1, 2017 – Dec 31, 2019

Routine (10).