This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0580020 , Mud Creek Water Association #2
20 of the 57 analytes this system has been tested for have been detected at least once, across 242 samples on record.
The other 37 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 242 samples on record, detections range from October 22, 2003 to July 23, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 124 of 124 results | Oct 7, 2004 | Sep 30, 2024 |
| Lead 1030 | Inorganic Chemical | 74 of 124 results | Oct 7, 2004 | Sep 30, 2024 |
| Barium 1010 | Inorganic Chemical | 16 of 16 results | Oct 22, 2003 | Jul 23, 2026 |
| Fluoride 1025 | Inorganic Chemical | 16 of 16 results | Oct 22, 2003 | Jul 23, 2026 |
| Arsenic 1005 | Inorganic Chemical | 15 of 16 results | Oct 22, 2003 | Jul 23, 2026 |
| Chromium 1020 | Inorganic Chemical | 10 of 16 results | Oct 22, 2003 | Oct 9, 2024 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 5 of 5 results | Dec 14, 2011 | Jul 17, 2012 |
| Nickel 1036 | Inorganic Chemical | 4 of 15 results | Mar 15, 2004 | Nov 13, 2023 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Sep 25, 2019 | Jul 23, 2026 |
| TTHM 2950 | Organic Chemical | 3 of 9 results | Sep 6, 2007 | Dec 20, 2022 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 3 of 10 results | Jul 1, 2010 | Oct 1, 2020 |
| Nitrite 1041 | Inorganic Chemical | 2 of 30 results | Jul 16, 2008 | Sep 11, 2023 |
| Cyanide 1024 | Inorganic Chemical | 2 of 15 results | May 4, 2005 | Feb 22, 2010 |
| Sulfate 1055 | Inorganic Chemical | 2 of 2 results | Oct 22, 2003 | Mar 15, 2004 |
| Selenium 1045 | Inorganic Chemical | 1 of 16 results | Jul 12, 2023 | Jul 12, 2023 |
| Dichloroacetic Acid 2451 | Organic Chemical | 1 of 5 results | Oct 1, 2020 | Oct 1, 2020 |
| Monobromoacetic Acid 2453 | Organic Chemical | 1 of 5 results | Oct 1, 2020 | Oct 1, 2020 |
| Nitrate-Nitrite 1038 | Inorganic Chemical | 1 of 30 results | Dec 11, 2019 | Dec 11, 2019 |
| Nitrate 1040 | Inorganic Chemical | 1 of 30 results | Dec 11, 2019 | Dec 11, 2019 |
| Monochloroacetic Acid 2450 | Organic Chemical | 1 of 5 results | Dec 7, 2016 | Dec 7, 2016 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 111–120 of 242 samples, newest first — collected July 16, 2012 to June 11, 2013. The summary above covers all 242.
34 results from the 10 samples listed here: 14 detected, 20 not detected. Across the whole record it is 285 of 1,051. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| 0.0596 mg/l , sample collected Jun 11, 2013 05:10, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.0014 mg/l , sample collected Jun 11, 2013 05:10, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.1115 mg/l , sample collected Jun 11, 2013 06:25, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 11, 2013 06:25, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.1804 mg/l , sample collected Jun 11, 2013 08:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 11, 2013 08:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.1218 mg/l , sample collected Jun 11, 2013 06:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 11, 2013 06:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.0232 mg/l , sample collected Jun 11, 2013 07:30, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 11, 2013 07:30, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.1515 mg/l , sample collected Jun 10, 2013 10:50, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Jun 10, 2013 10:50, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| 0.0012 mg/l , sample collected May 8, 2013 02:30, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.0149 mg/l , sample collected May 8, 2013 02:30, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2013 02:30, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.004 mg/l , sample collected May 8, 2013 02:30, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 1.79 mg/l , sample collected May 8, 2013 02:30, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2013 02:30, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| 0.0191 mg/l , sample collected May 8, 2013 02:30, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0025 mg/l Minimum Reporting Level , sample collected May 8, 2013 02:30, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2013 02:30, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2013 02:30, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2013 02:30, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2011 – Dec 31, 2013 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 13, 2013 01:55, sampling point TF101 | Nitrate-Nitrite 1038 EPA method 353.2 | Jan 1, 2013 – Dec 31, 2013 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 13, 2013 01:55, sampling point TF101 | Nitrate 1040 EPA method 353.2 | Jan 1, 2013 – Dec 31, 2013 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 13, 2013 01:55, sampling point TF101 | Nitrite 1041 EPA method 353.2 | Jan 1, 2013 – Dec 31, 2013 |
|
||
| 1.5 pci/l , sample collected Jul 17, 2012 12:20, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Jul 17, 2012 12:20, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.176 pci/l Minimum Reporting Level , sample collected Jul 17, 2012 12:20, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Jul 1, 2012 – Sep 30, 2012 |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Jul 17, 2012 12:20, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Jul 1, 2012 – Sep 30, 2012 |
|
||
| 1.5 pci/l , sample collected Jul 16, 2012 14:15, sampling point TF101 | Gross Alpha, Incl. Radon & U 4002 EPA method 00-02 | Not recorded |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 14:15, sampling point TF101 | Combined Radium (-226 & -228) 4010 | Not recorded |
| Not detected below 0.176 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 14:15, sampling point TF101 | Radium-226 4020 EPA method 903.1 | Jul 1, 2012 – Sep 30, 2012 |
| Not detected below 0.43 pci/l Minimum Reporting Level , sample collected Jul 16, 2012 14:15, sampling point TF101 | Radium-228 4030 EPA method 904.0 | Jul 1, 2012 – Sep 30, 2012 |
-
- Collected
- Jun 11, 2013 05:10
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 130612-099PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0596 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0014 mg/l
-
- Collected
- Jun 11, 2013 06:25
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 130612-098PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1115 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jun 11, 2013 08:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 130612-096PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1804 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jun 11, 2013 06:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 130612-095PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1218 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jun 11, 2013 07:30
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 130612-092PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0232 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Jun 10, 2013 10:50
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 130612-097PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.1515 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- May 8, 2013 02:30
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 130509-065IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- 0.0012 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Barium 1010 EPA method 200.8
- Result
- 0.0149 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Chromium 1020 EPA method 200.8
- Result
- 0.004 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Fluoride 1025 EPA method 300.0
- Result
- 1.79 mg/l
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Nickel 1036 EPA method 200.8
- Result
- 0.0191 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0025 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2011 – Dec 31, 2013
-
- Collected
- Mar 13, 2013 01:55
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 130314-069NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2013 – Dec 31, 2013
-
Nitrate-Nitrite 1038 EPA method 353.2
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method 353.2
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method 353.2
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
-
- Collected
- Jul 17, 2012 12:20
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 201210050209
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 1.5 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.176 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
- Collected
- Jul 16, 2012 14:15
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 120717-107
- Laboratory
- Radiation Safety Engineering
-
Gross Alpha, Incl. Radon & U 4002 EPA method 00-02
- Result
- 1.5 pci/l
- Monitoring period
- Not recorded
-
Combined Radium (-226 & -228) 4010
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Radium-226 4020 EPA method 903.1
- Result
- Not detected below 0.176 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
-
Radium-228 4030 EPA method 904.0
- Result
- Not detected below 0.43 pci/l Minimum Reporting Level
- Monitoring period
- Jul 1, 2012 – Sep 30, 2012
Routine (10).