This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0610086 , Thomasville W/A #2
24 of the 57 analytes this system has been tested for have been detected at least once, across 205 samples on record.
The other 33 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 205 samples on record, detections range from October 20, 2003 to July 30, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 37 of 37 results | Aug 23, 2007 | Aug 20, 2025 |
| Lead 1030 | Inorganic Chemical | 34 of 37 results | Aug 23, 2007 | Aug 20, 2025 |
| TTHM 2950 | Organic Chemical | 21 of 21 results | Aug 9, 2004 | Jun 4, 2026 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 20 of 21 results | Sep 13, 2007 | Jun 4, 2026 |
| Barium 1010 | Inorganic Chemical | 18 of 18 results | Oct 20, 2003 | Jul 30, 2026 |
| Fluoride 1025 | Inorganic Chemical | 18 of 18 results | Oct 20, 2003 | Jul 30, 2026 |
| Chloroform 2941 | Organic Chemical | 17 of 17 results | Sep 13, 2007 | Jun 4, 2026 |
| Bromodichloromethane 2943 | Organic Chemical | 17 of 17 results | Sep 13, 2007 | Jun 4, 2026 |
| Dichloroacetic Acid 2451 | Organic Chemical | 16 of 16 results | Jul 22, 2010 | Jun 4, 2026 |
| Trichloroacetic Acid 2452 | Organic Chemical | 16 of 16 results | Jul 22, 2010 | Jun 4, 2026 |
| Dibromochloromethane 2944 | Organic Chemical | 16 of 17 results | Sep 13, 2007 | Jun 4, 2026 |
| Chromium 1020 | Inorganic Chemical | 14 of 18 results | Oct 20, 2003 | May 8, 2019 |
| Dibromoacetic Acid 2454 | Organic Chemical | 11 of 16 results | Nov 7, 2013 | Jun 4, 2026 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 10 of 10 results | Dec 19, 2011 | Jul 11, 2012 |
| Nickel 1036 | Inorganic Chemical | 5 of 16 results | Mar 29, 2006 | May 8, 2019 |
| Selenium 1045 | Inorganic Chemical | 5 of 18 results | Mar 24, 2004 | Feb 1, 2010 |
| Sodium 1052 | Inorganic Chemical | 3 of 3 results | Dec 5, 2023 | Jul 30, 2026 |
| Monochloroacetic Acid 2450 | Organic Chemical | 2 of 16 results | Nov 7, 2013 | Sep 17, 2025 |
| Dichloromethane 2964 | Organic Chemical | 2 of 33 results | Aug 25, 2004 | Sep 2, 2004 |
| Arsenic 1005 | Inorganic Chemical | 2 of 18 results | Mar 24, 2004 | Mar 24, 2004 |
| Sulfate 1055 | Inorganic Chemical | 2 of 2 results | Oct 20, 2003 | Oct 20, 2003 |
| Mercury 1035 | Inorganic Chemical | 1 of 17 results | Jul 30, 2026 | Jul 30, 2026 |
| Nitrite 1041 | Inorganic Chemical | 1 of 41 results | Jan 27, 2026 | Jan 27, 2026 |
| Thallium, Total 1085 | Inorganic Chemical | 1 of 18 results | Oct 20, 2010 | Oct 20, 2010 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 61–70 of 205 samples, newest first — collected March 21, 2018 to June 18, 2019. The summary above covers all 205.
57 results from the 10 samples listed here: 16 detected, 41 not detected. Across the whole record it is 289 of 1,357. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Jun 18, 2019 12:50, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2017 – Dec 31, 2019 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Arsenic 1005 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0035 mg/l , sample collected May 8, 2019 08:05, sampling point ST004 | Barium 1010 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Cadmium 1015 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0235 mg/l , sample collected May 8, 2019 08:05, sampling point ST004 | Chromium 1020 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.379 mg/l , sample collected May 8, 2019 08:05, sampling point ST004 | Fluoride 1025 EPA method 300.0 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Mercury 1035 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0168 mg/l , sample collected May 8, 2019 08:05, sampling point ST004 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Selenium 1045 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:05, sampling point ST004 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
|
||
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0084 mg/l , sample collected May 8, 2019 08:34, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.0769 mg/l , sample collected May 8, 2019 08:34, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.385 mg/l , sample collected May 8, 2019 08:34, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| 0.055 mg/l , sample collected May 8, 2019 08:34, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected May 8, 2019 08:34, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2017 – Dec 31, 2019 |
|
||
| 0.0081 mg/l , sample collected Aug 1, 2018 06:45, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0014 mg/l , sample collected Aug 1, 2018 06:45, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0046 mg/l , sample collected Aug 1, 2018 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2018 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0043 mg/l , sample collected Aug 1, 2018 07:30, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Aug 1, 2018 07:30, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.013 mg/l , sample collected Aug 1, 2018 06:30, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0008 mg/l , sample collected Aug 1, 2018 06:30, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| 0.0054 mg/l , sample collected Aug 1, 2018 07:00, sampling point DS000 | Copper, Free 1022 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
| 0.0007 mg/l , sample collected Aug 1, 2018 07:00, sampling point DS000 | Lead 1030 EPA method 200.8 | Jan 1, 2018 – Dec 31, 2020 |
|
||
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Xylenes, Total 2955 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Dichloromethane 2964 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | O-Dichlorobenzene 2968 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | P-Dichlorobenzene 2969 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Vinyl Chloride 2976 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | 1,1-Dichloroethylene 2977 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | 1,2-Dichloroethane 2980 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | 1,1,1-Trichloroethane 2981 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Carbon Tetrachloride 2982 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | 1,2-Dichloropropane 2983 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Trichloroethylene 2984 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | 1,1,2-Trichloroethane 2985 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Tetrachloroethylene 2987 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Chlorobenzene 2989 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Benzene 2990 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Toluene 2991 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Ethylbenzene 2992 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.5 ug/l Minimum Reporting Level , sample collected Jul 17, 2018 09:35, sampling point TF101 | Styrene 2996 EPA method 524.2 | Jan 1, 2018 – Dec 31, 2018 |
|
||
| Not detected below 0.1 mg/l Minimum Reporting Level , sample collected Mar 21, 2018 14:42, sampling point ST004 | Nitrate-Nitrite 1038 EPA method QC10107041C | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.08 mg/l Minimum Reporting Level , sample collected Mar 21, 2018 14:42, sampling point ST004 | Nitrate 1040 EPA method QC10107041C | Jan 1, 2018 – Dec 31, 2018 |
| Not detected below 0.02 mg/l Minimum Reporting Level , sample collected Mar 21, 2018 14:42, sampling point ST004 | Nitrite 1041 EPA method QC10107041C | Jan 1, 2018 – Dec 31, 2018 |
-
- Collected
- Jun 18, 2019 12:50
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 190619-027CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.015 mg/l Minimum Reporting Level
-
- Collected
- May 8, 2019 08:05
- Sampling point
- ST004 Tank S060
- Sample type
- Routine
- Lab sample
- 190509-006IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Barium 1010 EPA method 200.8
- Result
- 0.0035 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Chromium 1020 EPA method 200.8
- Result
- 0.0235 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Fluoride 1025 EPA method 300.0
- Result
- 0.379 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Nickel 1036 EPA method 200.8
- Result
- 0.0168 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
- Collected
- May 8, 2019 08:34
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 190509-003IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Barium 1010 EPA method 200.8
- Result
- 0.0084 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Chromium 1020 EPA method 200.8
- Result
- 0.0769 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Fluoride 1025 EPA method 300.0
- Result
- 0.385 mg/l
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Nickel 1036 EPA method 200.8
- Result
- 0.055 mg/l
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2017 – Dec 31, 2019
-
- Collected
- Aug 1, 2018 06:45
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 180803-071PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0081 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0014 mg/l
-
- Collected
- Aug 1, 2018 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 180803-063PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0046 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Aug 1, 2018 07:30
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 180803-053PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0043 mg/l
-
Lead 1030 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Aug 1, 2018 06:30
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 180803-047PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.013 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0008 mg/l
-
- Collected
- Aug 1, 2018 07:00
- Sampling point
- DS000 Distribution
- Sample type
- Routine
- Lab sample
- 180803-042PB
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2020
-
Copper, Free 1022 EPA method 200.8
- Result
- 0.0054 mg/l
-
Lead 1030 EPA method 200.8
- Result
- 0.0007 mg/l
-
- Collected
- Jul 17, 2018 09:35
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 180718-011VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2018
-
1,2,4-Trichlorobenzene 2378 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Cis-1,2-Dichloroethylene 2380 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Xylenes, Total 2955 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Dichloromethane 2964 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
O-Dichlorobenzene 2968 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
P-Dichlorobenzene 2969 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Vinyl Chloride 2976 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1-Dichloroethylene 2977 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trans-1,2-Dichloroethylene 2979 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloroethane 2980 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,1-Trichloroethane 2981 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Carbon Tetrachloride 2982 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,2-Dichloropropane 2983 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Trichloroethylene 2984 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
1,1,2-Trichloroethane 2985 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Tetrachloroethylene 2987 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Chlorobenzene 2989 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Benzene 2990 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Toluene 2991 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Ethylbenzene 2992 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
Styrene 2996 EPA method 524.2
- Result
- Not detected below 0.5 ug/l Minimum Reporting Level
-
- Collected
- Mar 21, 2018 14:42
- Sampling point
- ST004 Tank S060
- Sample type
- Routine
- Lab sample
- 180322-048NI
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2018 – Dec 31, 2018
-
Nitrate-Nitrite 1038 EPA method QC10107041C
- Result
- Not detected below 0.1 mg/l Minimum Reporting Level
-
Nitrate 1040 EPA method QC10107041C
- Result
- Not detected below 0.08 mg/l Minimum Reporting Level
-
Nitrite 1041 EPA method QC10107041C
- Result
- Not detected below 0.02 mg/l Minimum Reporting Level
Routine (10).