This is a rebuild of Drinking Water Watch and not yet the official record. Use the agency’s current Drinking Water Watch for anything you need to rely on.
Chemical and radiological sample results
MS0620004 , High Hill Water Association
38 of the 74 analytes this system has been tested for have been detected at least once, across 360 samples on record.
The other 36 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.
Across all 360 samples on record, detections range from October 22, 2003 to July 13, 2026. These figures cover the whole record.
What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.
What has been detected, ever
Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.
| Analyte | Kind | Detected in | First detected | Last detected |
|---|---|---|---|---|
| Copper, Free 1022 | Inorganic Chemical | 81 of 81 results | Aug 16, 2007 | Aug 29, 2024 |
| TTHM 2950 | Organic Chemical | 63 of 67 results | Sep 13, 2004 | Dec 29, 2025 |
| Total Haloacetic Acids (Haa5) 2456 | Organic Chemical | 60 of 66 results | Sep 13, 2004 | Dec 29, 2025 |
| Chloroform 2941 | Organic Chemical | 54 of 56 results | May 23, 2006 | Dec 29, 2025 |
| Lead 1030 | Inorganic Chemical | 54 of 81 results | Aug 16, 2007 | Aug 29, 2024 |
| Dichloroacetic Acid 2451 | Organic Chemical | 50 of 50 results | Aug 23, 2007 | Dec 29, 2025 |
| Bromodichloromethane 2943 | Organic Chemical | 48 of 56 results | May 23, 2006 | Dec 29, 2025 |
| Trichloroacetic Acid 2452 | Organic Chemical | 44 of 50 results | Aug 23, 2007 | Nov 12, 2024 |
| Fluoride 1025 | Inorganic Chemical | 26 of 26 results | Oct 22, 2003 | Mar 24, 2025 |
| Barium 1010 | Inorganic Chemical | 25 of 25 results | Oct 22, 2003 | Mar 24, 2025 |
| Chromium 1020 | Inorganic Chemical | 18 of 25 results | Oct 22, 2003 | Mar 24, 2025 |
| Gross Alpha, Incl. Radon & U 4002 | Radionuclide | 10 of 10 results | Dec 12, 2011 | Jul 17, 2012 |
| Nickel 1036 | Inorganic Chemical | 9 of 25 results | Apr 18, 2005 | Mar 24, 2025 |
| Monochloroacetic Acid 2450 | Organic Chemical | 8 of 50 results | Dec 14, 2009 | Jul 20, 2015 |
| Sodium 1052 | Inorganic Chemical | 6 of 6 results | Oct 9, 2008 | Jul 13, 2026 |
| Xylenes, Total 2955 | Organic Chemical | 5 of 23 results | Aug 10, 2016 | Jul 13, 2026 |
| Monobromoacetic Acid 2453 | Organic Chemical | 4 of 50 results | Dec 14, 2009 | Feb 13, 2012 |
| Sulfate 1055 | Inorganic Chemical | 3 of 3 results | Oct 22, 2003 | Oct 9, 2008 |
| Toluene 2991 | Organic Chemical | 2 of 23 results | Jun 3, 2024 | Mar 11, 2025 |
| Cyanide 1024 | Inorganic Chemical | 1 of 27 results | Oct 23, 2025 | Oct 23, 2025 |
| Dibromoacetic Acid 2454 | Organic Chemical | 1 of 50 results | Nov 28, 2011 | Nov 28, 2011 |
| Dibromochloromethane 2944 | Organic Chemical | 1 of 56 results | Jun 15, 2009 | Jun 15, 2009 |
| Calcium 1016 | Inorganic Chemical | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Iron 1028 | Inorganic Chemical | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Magnesium 1031 | Inorganic Chemical | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Manganese 1032 | Inorganic Chemical | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Potassium 1042 | Inorganic Chemical | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Residue, Total, Filterable 1057 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Alkalinity, Caco3 Stability 1067 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Carbon Dioxide 1901 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Color 1905 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Hardness, Total (As Caco3) 1915 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| PH 1925 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Alkalinity, Total 1927 | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Iron, Field Result FEFD | Inorganic Chemical | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Calculated Sodium NACA | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| PH, Field Result PHFD | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
| Temperature, Field Result TEMP | Water Quality | 1 of 1 result | Oct 9, 2008 | Oct 9, 2008 |
No date range is applied: this list draws on every sample on record. Show the last two years only.
The most recent samples, result by result
The table below lists 351–360 of 360 samples, newest first — collected October 22, 2003 to March 22, 2004. The summary above covers all 360.
90 results from the 10 samples listed here: 12 detected, 78 not detected. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.
| Result | Analyte | Monitoring period |
|---|---|---|
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.004 mg/l , sample collected Mar 22, 2004, sampling point TF102 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.001 mg/l , sample collected Mar 22, 2004, sampling point TF102 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.003 mg/l , sample collected Mar 22, 2004, sampling point TF101 | Barium 1010 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| 0.001 mg/l , sample collected Mar 22, 2004, sampling point TF101 | Chromium 1020 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Mercury 1035 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Selenium 1045 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Mar 22, 2004, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | 1,2,4-Trichlorobenzene 2378 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Cis-1,2-Dichloroethylene 2380 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Xylenes, Total 2955 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Dichloromethane 2964 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | O-Dichlorobenzene 2968 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | P-Dichlorobenzene 2969 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Vinyl Chloride 2976 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | 1,1-Dichloroethylene 2977 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Trans-1,2-Dichloroethylene 2979 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | 1,2-Dichloroethane 2980 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | 1,1,1-Trichloroethane 2981 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Carbon Tetrachloride 2982 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | 1,2-Dichloropropane 2983 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Trichloroethylene 2984 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | 1,1,2-Trichloroethane 2985 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Tetrachloroethylene 2987 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Chlorobenzene 2989 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Benzene 2990 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Toluene 2991 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Ethylbenzene 2992 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF102 | Styrene 2996 | Jan 1, 2004 – Mar 31, 2004 |
|
||
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | 1,2,4-Trichlorobenzene 2378 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Cis-1,2-Dichloroethylene 2380 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Xylenes, Total 2955 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Dichloromethane 2964 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | O-Dichlorobenzene 2968 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | P-Dichlorobenzene 2969 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Vinyl Chloride 2976 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | 1,1-Dichloroethylene 2977 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Trans-1,2-Dichloroethylene 2979 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | 1,2-Dichloroethane 2980 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | 1,1,1-Trichloroethane 2981 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Carbon Tetrachloride 2982 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | 1,2-Dichloropropane 2983 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Trichloroethylene 2984 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | 1,1,2-Trichloroethane 2985 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Tetrachloroethylene 2987 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Chlorobenzene 2989 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Benzene 2990 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Toluene 2991 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Ethylbenzene 2992 | Jan 1, 2004 – Mar 31, 2004 |
| Not detected below 0.0005 mg/l Method Detection Limit , sample collected Mar 1, 2004, sampling point TF101 | Styrene 2996 | Jan 1, 2004 – Mar 31, 2004 |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Arsenic 1005 EPA method 200.8 | Not recorded |
| 0.004 mg/l , sample collected Oct 22, 2003, sampling point TF102 | Barium 1010 EPA method 200.8 | Not recorded |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Cadmium 1015 EPA method 200.8 | Not recorded |
| 0.002 mg/l , sample collected Oct 22, 2003, sampling point TF102 | Chromium 1020 EPA method 200.8 | Not recorded |
| 0.232 mg/l , sample collected Oct 22, 2003, sampling point TF102 | Fluoride 1025 EPA method 300.0 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Mercury 1035 EPA method 200.8 | Not recorded |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Selenium 1045 EPA method 200.8 | Not recorded |
| 3.58 mg/l , sample collected Oct 22, 2003, sampling point TF102 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Antimony, Total 1074 EPA method 200.8 | Not recorded |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Beryllium, Total 1075 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Thallium, Total 1085 EPA method 200.8 | Not recorded |
|
||
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Arsenic 1005 EPA method 200.8 | Not recorded |
| 0.006 mg/l , sample collected Oct 22, 2003, sampling point TF101 | Barium 1010 EPA method 200.8 | Not recorded |
| Not detected below 0.0001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Cadmium 1015 EPA method 200.8 | Not recorded |
| 0.003 mg/l , sample collected Oct 22, 2003, sampling point TF101 | Chromium 1020 EPA method 200.8 | Not recorded |
| 0.25 mg/l , sample collected Oct 22, 2003, sampling point TF101 | Fluoride 1025 EPA method 300.0 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Mercury 1035 EPA method 200.8 | Not recorded |
| Not detected below 0.005 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Nickel 1036 EPA method 200.8 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Selenium 1045 EPA method 200.8 | Not recorded |
| 4.64 mg/l , sample collected Oct 22, 2003, sampling point TF101 | Sulfate 1055 EPA method 300.0 | Not recorded |
| Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Antimony, Total 1074 EPA method 200.8 | Not recorded |
| Not detected below 0.0003 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Beryllium, Total 1075 EPA method 200.8 | Not recorded |
| Not detected below 0.0005 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Thallium, Total 1085 EPA method 200.8 | Not recorded |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF102 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
|
||
| Not detected below 0.01 mg/l Minimum Reporting Level , sample collected Oct 22, 2003, sampling point TF101 | Cyanide 1024 EPA method QC10204001X | Jan 1, 2002 – Dec 31, 2004 |
-
- Collected
- Mar 22, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040323-075CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Mar 22, 2004
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 040323-073CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Mar 22, 2004
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 040323-062IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.004 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Mar 22, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040323-061IN
- Laboratory
- MSDH Lab
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Barium 1010 EPA method 200.8
- Result
- 0.003 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Chromium 1020 EPA method 200.8
- Result
- 0.001 mg/l
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
- Monitoring period
- Not recorded
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
- Collected
- Mar 1, 2004
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 040302-058VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Mar 31, 2004
-
1,2,4-Trichlorobenzene 2378
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Mar 1, 2004
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 040302-057VO
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2004 – Mar 31, 2004
-
1,2,4-Trichlorobenzene 2378
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Cis-1,2-Dichloroethylene 2380
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Xylenes, Total 2955
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Dichloromethane 2964
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
O-Dichlorobenzene 2968
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
P-Dichlorobenzene 2969
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Vinyl Chloride 2976
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1-Dichloroethylene 2977
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trans-1,2-Dichloroethylene 2979
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloroethane 2980
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,1-Trichloroethane 2981
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Carbon Tetrachloride 2982
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,2-Dichloropropane 2983
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Trichloroethylene 2984
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
1,1,2-Trichloroethane 2985
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Tetrachloroethylene 2987
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Chlorobenzene 2989
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Benzene 2990
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Toluene 2991
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Ethylbenzene 2992
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
Styrene 2996
- Result
- Not detected below 0.0005 mg/l Method Detection Limit
-
- Collected
- Oct 22, 2003
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 031023-046IN
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Barium 1010 EPA method 200.8
- Result
- 0.004 mg/l
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
-
Chromium 1020 EPA method 200.8
- Result
- 0.002 mg/l
-
Fluoride 1025 EPA method 300.0
- Result
- 0.232 mg/l
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Sulfate 1055 EPA method 300.0
- Result
- 3.58 mg/l
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Oct 22, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 031023-045IN
- Laboratory
- MSDH Lab
- Monitoring period
- Not recorded
-
Arsenic 1005 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Barium 1010 EPA method 200.8
- Result
- 0.006 mg/l
-
Cadmium 1015 EPA method 200.8
- Result
- Not detected below 0.0001 mg/l Minimum Reporting Level
-
Chromium 1020 EPA method 200.8
- Result
- 0.003 mg/l
-
Fluoride 1025 EPA method 300.0
- Result
- 0.25 mg/l
-
Mercury 1035 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
Nickel 1036 EPA method 200.8
- Result
- Not detected below 0.005 mg/l Minimum Reporting Level
-
Selenium 1045 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Sulfate 1055 EPA method 300.0
- Result
- 4.64 mg/l
-
Antimony, Total 1074 EPA method 200.8
- Result
- Not detected below 0.001 mg/l Minimum Reporting Level
-
Beryllium, Total 1075 EPA method 200.8
- Result
- Not detected below 0.0003 mg/l Minimum Reporting Level
-
Thallium, Total 1085 EPA method 200.8
- Result
- Not detected below 0.0005 mg/l Minimum Reporting Level
-
- Collected
- Oct 22, 2003
- Sampling point
- TF102 Treatment Plant T102
- Sample type
- Routine
- Lab sample
- 031023-033CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
-
- Collected
- Oct 22, 2003
- Sampling point
- TF101 Treatment Plant T101
- Sample type
- Routine
- Lab sample
- 031023-017CN
- Laboratory
- MSDH Lab
- Monitoring period
- Jan 1, 2002 – Dec 31, 2004
-
Cyanide 1024 EPA method QC10204001X
- Result
- Not detected below 0.01 mg/l Minimum Reporting Level
Routine (10).