Chemical and radiological sample results

MS0640009 , Okatoma Water Association #1

27 of the 98 analytes this system has been tested for have been detected at least once, across 439 samples on record.

The other 71 were tested for and never found. An analyte is counted here if any result on record measured it, so this covers the whole history and not the samples listed below.

Across all 439 samples on record, detections range from October 22, 2003 to July 22, 2026. These figures cover the whole record.

What counts as a non-detect is defined in the help: Less than Indicator. This system’s violations.

What has been detected, ever

Every analyte measured above its reporting level at any point in this system’s record, most often detected first. This is not limited to the samples listed below.

Every analyte ever detected for Okatoma Water Association #1, with how many results found it and when it was first and last detected. Covers the whole record, not only the samples listed below.
Analyte Kind Detected in First detected Last detected
Nitrate-Nitrite 1038 Inorganic Chemical 124 of 138 results Jun 14, 2004 Jul 22, 2026
Nitrate 1040 Inorganic Chemical 124 of 138 results Jun 14, 2004 Jul 22, 2026
Copper, Free 1022 Inorganic Chemical 107 of 107 results Sep 6, 2007 Jul 8, 2025
Lead 1030 Inorganic Chemical 40 of 107 results Sep 6, 2007 Jul 8, 2025
Barium 1010 Inorganic Chemical 25 of 25 results Oct 22, 2003 Apr 7, 2025
TTHM 2950 Organic Chemical 18 of 20 results Aug 16, 2004 Jun 4, 2025
Nickel 1036 Inorganic Chemical 17 of 25 results Mar 22, 2004 Apr 7, 2025
Combined Radium (-226 & -228) 4010 Radionuclide 14 of 14 results Mar 14, 2012 Oct 8, 2019
Radium-226 4020 Radionuclide 14 of 14 results Mar 14, 2012 Oct 8, 2019
Radium-228 4030 Radionuclide 14 of 14 results Mar 14, 2012 Oct 8, 2019
Bromodichloromethane 2943 Organic Chemical 13 of 14 results Sep 10, 2007 Jun 4, 2025
Dibromochloromethane 2944 Organic Chemical 12 of 14 results Sep 10, 2007 Jun 4, 2025
Gross Alpha, Incl. Radon & U 4002 Radionuclide 11 of 14 results Mar 14, 2012 Oct 15, 2018
Fluoride 1025 Inorganic Chemical 9 of 25 results Apr 10, 2006 Apr 7, 2025
Total Haloacetic Acids (Haa5) 2456 Organic Chemical 8 of 20 results Jul 6, 2010 Apr 7, 2025
Chloroform 2941 Organic Chemical 7 of 14 results Sep 10, 2007 Jun 4, 2025
Bromoform 2942 Organic Chemical 6 of 14 results Jul 6, 2010 Jun 4, 2025
Sodium 1052 Inorganic Chemical 5 of 5 results Sep 17, 2019 Jul 22, 2026
Dibromoacetic Acid 2454 Organic Chemical 3 of 13 results Sep 4, 2013 Jun 4, 2025
Chromium 1020 Inorganic Chemical 3 of 25 results Oct 22, 2003 Apr 7, 2025
Arsenic 1005 Inorganic Chemical 2 of 25 results Feb 8, 2010 Feb 12, 2024
Xylenes, Total 2955 Organic Chemical 1 of 29 results Nov 29, 2022 Nov 29, 2022
Monobromoacetic Acid 2453 Organic Chemical 1 of 13 results Oct 12, 2020 Oct 12, 2020
Monochloroacetic Acid 2450 Organic Chemical 1 of 13 results Dec 6, 2016 Dec 6, 2016
Selenium 1045 Inorganic Chemical 1 of 25 results Feb 8, 2010 Feb 8, 2010
Cadmium 1015 Inorganic Chemical 1 of 25 results Nov 3, 2008 Nov 3, 2008
Cyanide 1024 Inorganic Chemical 1 of 27 results Apr 10, 2006 Apr 10, 2006

No date range is applied: this list draws on every sample on record. Show the last two years only.

The most recent samples, result by result

The table below lists 271–280 of 439 samples, newest first — collected August 5, 2013 to September 4, 2013. The summary above covers all 439.

32 results from the 10 samples listed here: 6 detected, 26 not detected. Across the whole record it is 582 of 1,978. A sample is analysed for many analytes at once, so one sample appears on as many rows as it had results.

Chemical and radiological sample results for Okatoma Water Association #1, every result from 271 to 280 of 439 samples shown, newest first. Not detected means the amount was below the level the laboratory can reliably report, which is given beside it.
Result Analyte Monitoring period
Collected
Sep 4, 2013 01:00
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
130905-001TH
Laboratory
MSDH Lab
Not detected below 1 ug/l Minimum Reporting Level , sample collected Sep 4, 2013 01:00, sampling point MRT000 Chloroform 2941 EPA method 524.2 Not recorded
2.97 ug/l , sample collected Sep 4, 2013 01:00, sampling point MRT000 Bromoform 2942 EPA method 524.2 Not recorded
1.1 ug/l , sample collected Sep 4, 2013 01:00, sampling point MRT000 Bromodichloromethane 2943 EPA method 524.2 Not recorded
1.96 ug/l , sample collected Sep 4, 2013 01:00, sampling point MRT000 Dibromochloromethane 2944 EPA method 524.2 Not recorded
6 ug/l , sample collected Sep 4, 2013 01:00, sampling point MRT000 TTHM 2950 EPA method 524.2 Jan 1, 2011 – Dec 31, 2013
Collected
Sep 4, 2013 01:00
Sampling point
MRT000 Max. Res. Time
Sample type
Routine
Lab sample
130905-001HA
Laboratory
MSDH Lab
Not detected below 0.002 mg/l Minimum Reporting Level , sample collected Sep 4, 2013 01:00, sampling point MRT000 Monochloroacetic Acid 2450 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 4, 2013 01:00, sampling point MRT000 Dichloroacetic Acid 2451 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 4, 2013 01:00, sampling point MRT000 Trichloroacetic Acid 2452 EPA method 552.2 Not recorded
Not detected below 0.001 mg/l Minimum Reporting Level , sample collected Sep 4, 2013 01:00, sampling point MRT000 Monobromoacetic Acid 2453 EPA method 552.2 Not recorded
0.001 mg/l , sample collected Sep 4, 2013 01:00, sampling point MRT000 Dibromoacetic Acid 2454 EPA method 552.2 Not recorded
0.001 mg/l , sample collected Sep 4, 2013 01:00, sampling point MRT000 Total Haloacetic Acids (Haa5) 2456 Jan 1, 2011 – Dec 31, 2013
Collected
Aug 19, 2013 02:05
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
130820-030CN
Laboratory
MSDH Lab
Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 19, 2013 02:05, sampling point TF080 Cyanide 1024 EPA method QC10204001X Jan 1, 2011 – Dec 31, 2013
Collected
Aug 19, 2013 02:00
Sampling point
TF081 Treatment Plant 081
Sample type
Routine
Lab sample
130820-002CN
Laboratory
MSDH Lab
Not detected below 0.015 mg/l Minimum Reporting Level , sample collected Aug 19, 2013 02:00, sampling point TF081 Cyanide 1024 EPA method QC10204001X Jan 1, 2011 – Dec 31, 2013
Collected
Aug 5, 2013 13:15
Sampling point
TF081 Treatment Plant 081
Sample type
Routine
Lab sample
201308070532-SDI
Laboratory
Eurofins Eaton Analytical
Not detected below 0.005 ng/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 2,3,7,8-TCDD 2063 EPA method 1613 Not recorded
Collected
Aug 5, 2013 13:15
Sampling point
TF081 Treatment Plant 081
Sample type
Routine
Lab sample
201308070532-SEN
Laboratory
Eurofins Eaton Analytical
Not detected below 5 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Endothall 2033 EPA method 548.1 Not recorded
Collected
Aug 5, 2013 13:15
Sampling point
TF081 Treatment Plant 081
Sample type
Routine
Lab sample
201308070532-S15
Laboratory
Eurofins Eaton Analytical
Not detected below 1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Dalapon 2031 EPA method 515.4 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Picloram 2040 EPA method 515.4 Not recorded
Not detected below 0.2 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Dinoseb 2041 EPA method 515.4 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 2,4-D 2105 EPA method 515.4 Not recorded
Not detected below 0.2 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 2,4,5-TP 2110 EPA method 515.4 Not recorded
Not detected below 0.04 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Pentachlorophenol 2326 EPA method 515.4 Not recorded
Collected
Aug 5, 2013 13:15
Sampling point
TF081 Treatment Plant 081
Sample type
Routine
Lab sample
201308070532-SO5
Laboratory
Eurofins Eaton Analytical
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Alachlor Esa 2004 EPA method 505 Not recorded
Not detected below 0.01 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 BHC-Gamma 2010 EPA method 505 Not recorded
Not detected below 0.08 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1016 2388 EPA method 505 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1221 2390 EPA method 505 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1232 2392 EPA method 505 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1242 2394 EPA method 505 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1248 2396 EPA method 505 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1254 2398 EPA method 505 Not recorded
Not detected below 0.1 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF081 Aroclor 1260 2400 EPA method 505 Not recorded
Collected
Aug 5, 2013 13:15
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
201308070531-SDI
Laboratory
Eurofins Eaton Analytical
Not detected below 0.005 ng/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF080 2,3,7,8-TCDD 2063 EPA method 1613 Not recorded
Collected
Aug 5, 2013 13:15
Sampling point
TF080 Treatment Plant T080
Sample type
Routine
Lab sample
201308070531-SEN
Laboratory
Eurofins Eaton Analytical
Not detected below 5 ug/l Minimum Reporting Level , sample collected Aug 5, 2013 13:15, sampling point TF080 Endothall 2033 EPA method 548.1 Not recorded

Routine (10).